C. ACCESSIBILITY CLEARANCES
1. The PureFire boiler is certified for closet installations
with zero clearance to combustible construction. In
addition, it is design certified for use on combustible
floors.
2. Figure 1.1 shows the minimum recommended
clearances to allow reasonable access to the boiler for
Models PFW-199, PFW-210 and PFW-399. However,
local codes or special conditions may require greater
clearances.
E. D. COMBUSTION AND
VENTILATION AIR
D. COMBUSTION AND VENTILATION AIR
1. The PureFire boiler is designed for operation with
combustion air piped directly to the boiler from
outside the building (sealed combustion). Combustion
air may be supplied from within the building only if
adequate combustion air and ventilation air is
provided in accordance with the National Fuel Gas
Code or applicable provisions of the local building
code. Subsections 3 through 10 as follows are based
on the National Fuel Gas Code requirements.
2. If the combustion air is piped directly to the boiler
from outside the building, no additional combustion
or ventilation air is required. Otherwise, follow the
National Fuel Gas Code
recommendations
summarized in subsections 3 through 10.
3.
Required Combustion Air Volume
: The total required
volume of indoor air is to be the sum of the required
volumes for all appliances located within the space.
Rooms communicating directly with the space in
which the appliances are installed and through
combustion air openings sized as indicated in
Subsection 3 are considered part of the required
volume. The required volume of indoor air is to be
determined by one of two methods.
a.
Standard Method
: The minimum required volume
of indoor air (room volume) shall be 50 cubic feet
per 1000 BTU/Hr (4.8 m3/kW). This method is to
be used if the air infiltration rate is unknown or if
the rate of air infiltration is known to be greater
than 0.6 air changes per hour. As an option, this
method may be used if the air infiltration rate is
known to be between 0.6 and 0.4 air changes per
hour. If the air infiltration rate is known to be
below 0.4 then the
Known Air Infiltration Rate
Method
must be used. If the building in which this
appliance is to be installed is unusually tight, PB
Heat recommends that the air infiltration rate be
determined.
b.
Known Air Infiltration Rate Method
:
where:
I
fan
= Input of the fan assisted appliances
assisted in Btu/hr
ACH = air change per hour (percent of the
volume of the space exchanged per
hour, expressed as a decimal)
Note: These calculations are not to be used for
infiltration rates greater than 0.60 ACH.
Figure 1.1: Minimum Accessibility Clearances – PFW199, PFW210 & PFW399
3
PREINSTALLATION
15 ft
3
I
fan
ACH
1000
Btu
/
hr
Required Volume
fan
=
⎛
⎜
⎝
⎛
⎜
⎝
Summary of Contents for PUREFIRE PFW-199
Page 20: ...18 WATER PIPING AND CONTROLS Figure 4 3 Schematic Piping One Boiler with a Single Storage Tank...
Page 60: ...58 Figure 13 2 Heat Exchanger Burner Assembly Repair Parts REPAIR PARTS...
Page 63: ...61 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS...
Page 64: ...62 APPENDIX A STATUS SCREENS...
Page 65: ...63 APPENDIX A STATUS SCREENS...
Page 66: ...64 APPENDIX B USER MENU APPENDIX B USER MENU...
Page 67: ...65 APPENDIX B USER MENU...
Page 68: ...66 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU...
Page 69: ...67 APPENDIX C INSTALLER MENU...
Page 70: ...68 APPENDIX C INSTALLER MENU...
Page 71: ...69 APPENDIX C INSTALLER MENU...