I.
SENSOR RESISTANCE
See Figure 8.4 for typical resistance of the boiler sensors.
J.
MULTIPLE BOILERS
1.
P
URE
F
IRE
®
boiler controls can operate together to
control up to 16 boilers for one central heat or
domestic hot water demand. Only the addition of a
system sensor (54156) is required to provide this
operation. The System Sensor must be placed on the
Primary loop downstream of the Boiler loop for proper
Cascade operation. See Figure 8.4 and 8.5 for
examples of System sensor location.
2.
Overview:
a. Master Boiler: In a multiple boiler system, a boiler
designated as the “Master” boiler controls the
function of the boiler system.
• Attached to a system sensor which monitors
the system water temperature.
• Can also be connected to an outdoor sensor
(54112), included with each boiler, as well as
an optional DHW sensor (54157) or a
standard DHW thermostat.
• Determines which boiler operates first (lead)
and when to bring on additional boilers.
• Determines the setpoint temperature of
individual boilers.
• Shuts down all boilers in the system if the
LWCO contacts are opened.
b. Dependent Boilers: The “dependent” boilers
operate at the setpoint temperature that the
Master boiler specifies.
• Maintain all of their own safety parameters
such as safety limit, vent temperature limit,
and freeze protection.
• Control their own general circulator that is
energized whenever there is a call for either
Central Heat or Domestic Hot Water.
• Shuts down the individual boiler if the
dependent boiler LWCO contacts are opened.
3.
System Piping & Wiring:
a. Multiple boilers with multiple zones with zone valves.
• Figure 8.4 shows a typical system which uses a
CH circulator, a DHW circulator and zone valves
to distribute the heating load to the building.
• A three zone valve control panel (not included)
controls circulation to individual zones.
• A call from any of the heating zones initiates a
contact closure from the zone relay across the
CH thermostat connections (terminals #1 &2)
on the master boiler. This initiates ignition of
the “lead” boiler and its general pump. In
addition, the CH circulator is energized.
• A call for domestic hot water can either be
initiated internally by the control when it sees
a drop in indirect tank temperature or by a
tank thermostat. In either case, the lead boiler
is ignited and its general pump operates. The
DHW circulator is also energized.
b. Multiple boilers with multiple zones with zone
circulators.
• Figure 8.5 shows a typical system which uses a
circulator zone control panel to control the
central heating zones.
• The DHW circulator can be operated by the
priority zone or can be connected directly to
the boiler (as shown). In either case, the
priority zone cannot be used for heating.
• Again, a call for heat from any of the heating
zones causes the master boiler to initiate
operation of the lead boiler and its general
circulator. The CH circulators are controlled by
the zone control relay panel.
• A DHW call results in the operation of the lead
boiler and its general pump. The DHW pump is
also energized.
• Wiring for a typical circulator zone relay is
shown in Figure 7.4.
49
BOILER CONTROL: INTERNAL WIRING & OPERATION
Figure 8.3: Sensor Resistance
The central heating (CH) circulator and the domestic
hot water (DHW) circulator must be sized in
accordance with good Engineering practices based
on the required flow and pressure drop of the
system. Failure to do so may result in system
performance problems.
NOTICE
Before selecting cascade operation, connect the
System sensor to terminals #7 & #8. Failure to do
this will result in a blinking screen warning as
covered in Section 10.D.
NOTICE
Summary of Contents for PureFire PF-110
Page 77: ...75 REPAIR PARTS Figure 13 3 General Repair Parts PF 200 PF 210 PF 300 PF 399 ...
Page 82: ...80 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS ...
Page 83: ...81 APPENDIX A STATUS SCREENS ...
Page 84: ...82 APPENDIX A STATUS SCREENS ...
Page 85: ...83 APPENDIX A STATUS SCREENS ...
Page 86: ...84 APPENDIX B USER MENU APPENDIX B USER MENU ...
Page 87: ...85 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU ...
Page 88: ...86 APPENDIX C INSTALLER MENU ...
Page 89: ...87 APPENDIX C INSTALLER MENU ...
Page 90: ...88 APPENDIX C INSTALLER MENU ...
Page 91: ...89 APPENDIX C INSTALLER MENU ...