A. GENERAL
1. Install the
P
URE
F
IRE
®
boiler venting system in accordance
with these instructions and with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, CAN/CGA B149, and/or
applicable provisions of local building codes.
2. The
P
URE
F
IRE
®
boiler is a direct vent appliance and is
ETL Listed as a Category IV appliance with Intertek
Testing Laboratories, Inc.
3. Sources of combustion air contaminated with chlorine,
ammonia or alkali agents must be avoided. Do not
install this boiler near a swimming pool, hot tubs or
laundry. Do not store chemicals near the boiler.
B. APPROVED MATERIALS
1. Table 3.1 lists approved materials for vent pipe (and
adhesives where applicable). Use only these materials
for exhaust vent piping.
2. PVC pipe and fittings are not to be used for venting in
confined spaces such as closet installations. Use only
CPVC or polypropylene (InnoFlue or PolyPro) vent
pipe under these conditions.
3. Cellular core piping is approved for inlet air piping only.
* PVC pipe/fittings are not to be used for venting within
confined spaces.
Notice: Installations in Canada require compliance with
ULC S636 - Standard for Type BH Gas Venting Systems.
C. EXHAUST VENT/AIR INTAKE PIPE
LOCATION
1. Install vent piping before installing water, fuel, or
condensate piping. Working from largest to smallest
diameter reduces the complexity of piping
interferences.
2. Vent and air intake piping is to be installed so that
there is sufficient access for routine inspection as
required in Section 11, of this manual.
3. The vent piping for this boiler is approved for zero
clearance to combustible construction. However, a fire
stop must be used where the vent pipe penetrates
walls or ceilings.
4. The Peerless
®
P
URE
F
IRE
®
boiler, like all high efficiency,
gas-fired appliances, is likely to produce a vapor
plume due to condensation. Surfaces near the vent
termination will likely become coated with
condensation.
5. The maximum combined vent and air inlet vent length
for the Peerless
®
P
URE
F
IRE
®
boiler is about 200
equivalent feet (60 m).Be sure that the boiler is located
such that the maximum vent length is not exceeded.
VENTING & AIR INLET PIPING
3. VENTING & AIR INLET PIPING
The venting system for this product is to be installed in
strict accordance with these venting instructions.
Failure to install the vent system properly may result in
severe personal injury, death or major property damage.
WARNING
This vent system operates under positive pressure.
Vent connectors serving appliances vented by
natural draft shall not be connected into any portion
of this venting system. Failure to comply may result
in serious injury, death or major property damage.
WARNING
Only the materials listed below are approved for use
with the
P
URE
F
IRE
®
boiler. Use only these components
in accordance with these instructions. Failure to use
the correct material may result in serious injury,
death, or major property damage.
WARNING
Table 3.1: Approved Materials for Exhaust Vent Pipe
Use of cellular core PVC (ASTM F891), cellular core
CPVC, or Radel
®
(polyphenolsulphone) for exhaust
vent is prohibited. Use of these materials as exhaust
vent may result in severe personal injury, death, or
major property damage.
WARNING
If the maximum equivalent vent length is exceeded,
the maximum burner input rate may be reduced.
NOTICE
Description
Material
Conforming to
Standard
Vent Piping
& Fittings
PVC (Sch 40 or 80)
*
ANSI/ASTM D1785
CPVC (Sch 40 or 80)
ANSI/ASTM F441
PVC-DWV
*
ANSI/ASTM D2665
FasNSeal
®
UL1738 & ULC-S636
PolyPro
®
ULC-S636
InnoFlue
®
ULC-S636
Z-DENS
®
ULC S636
Pipe Cement
(PVC & CPVC Only)
PVC/CPVC Cement
ANSI/ASTM D2564
9
Summary of Contents for PureFire PF-110
Page 77: ...75 REPAIR PARTS Figure 13 3 General Repair Parts PF 200 PF 210 PF 300 PF 399 ...
Page 82: ...80 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS ...
Page 83: ...81 APPENDIX A STATUS SCREENS ...
Page 84: ...82 APPENDIX A STATUS SCREENS ...
Page 85: ...83 APPENDIX A STATUS SCREENS ...
Page 86: ...84 APPENDIX B USER MENU APPENDIX B USER MENU ...
Page 87: ...85 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU ...
Page 88: ...86 APPENDIX C INSTALLER MENU ...
Page 89: ...87 APPENDIX C INSTALLER MENU ...
Page 90: ...88 APPENDIX C INSTALLER MENU ...
Page 91: ...89 APPENDIX C INSTALLER MENU ...