69
BOILER DIMENSIONS & RATINGS
Table 12.3: Combustion Air Fan Speeds
SERIES PEERLESS
®
PUREFIRE
®
COMBUSTION AIR FAN SPEEDS
Boiler
Model
Input
Rate
Fan Speed
Low Power
Ignition
High Power
PF-50
50 MBH
1350
2790
3360
PF-80
80 MBH
1470
3780
4800
PF-110
110 MBH
1590
4200
5280
PF-140
140 MBH
1440
3990
4800
PF-200
199 MBH
1350
4650
5940
PF-210
210 MBH
1350
4650
6150
PF-300
300 MBH
1440
5430
5640
PF-399
399 MBH
1710
5790
7740
Figure 12.2: Dimensional Drawing – PF-200, PF-210, PF-300 & PF-399
Table 12.2: Boiler Ratings
Series Peerless
®
P
URE
F
IRE
®
Boiler
Model
Input
(MBH)
Heating
Capacity
(MBH)
Net Rating
(MBH)
AFUE
(%)
Min.
Max.
PF-50
16
50
47
41
95.0
PF-80
20
80
75
65
95.0
PF-110
27.5
110
103
90
95.0
PF-140
35
140
131
114
95.0
PF-200
42
199
185
161
95.0
PF-210
42
210
195
170
95.1
Gross Output
(MBH)
Net Rating
(MBH)
Thermal Efficiency
(%)
PF-300
80
300
290
252
96.5
PF-399
80
399
373
324
93.4
SERIES PEERLESS
®
PUREFIRE
®
BOILER RATINGS
* For installations over 2000 Ft above sea level, the boiler will de-rate by 3.5% per every additional 1000 Ft in elevation with no adjustment to the
boiler. Input values based on manufactures recommended CO2 percentages.
Summary of Contents for PureFire PF-110
Page 77: ...75 REPAIR PARTS Figure 13 3 General Repair Parts PF 200 PF 210 PF 300 PF 399 ...
Page 82: ...80 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS ...
Page 83: ...81 APPENDIX A STATUS SCREENS ...
Page 84: ...82 APPENDIX A STATUS SCREENS ...
Page 85: ...83 APPENDIX A STATUS SCREENS ...
Page 86: ...84 APPENDIX B USER MENU APPENDIX B USER MENU ...
Page 87: ...85 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU ...
Page 88: ...86 APPENDIX C INSTALLER MENU ...
Page 89: ...87 APPENDIX C INSTALLER MENU ...
Page 90: ...88 APPENDIX C INSTALLER MENU ...
Page 91: ...89 APPENDIX C INSTALLER MENU ...