VII. DATALOGGING OF TRANSIENT DETECTION
Set the rotary switch to the
Transient
position, the following display is shown.
It shows the reference voltage is AC 110.0V (
TRANS REF
), and the threshold is
5%. If the voltage exceeds 115.5V (
SWELL
) or is less than 104.5V (
DIP
), or is less
the 40.0V (
OUTAGE
), one transient event will be logged.
NOTE: Maximum 32000 events