50
Harmonics of AC Current in Percentage
(1 to 50
th
order, minimum current at 50
or 60 Hz > 20 A. If the current is 0 at 50 or 60 Hz, all the percentage (%) display is 0.)
Range
Resolution
Accuracy
1 – 20
th
0.1%
±2%
21 – 50
th
0.1%
4% of reading ±2.0%
Harmonics of AC Current in Magnitude
(1 to 50
th
order, minimum current at 50 or
60 Hz > 20A)
Range
Resolution
Accuracy
1 – 20
th
0.1%
±2% of reading ±0.4A
21 – 50
th
0.1%
±4% of reading ±0.4A
Power Factor
(PF)
Accuracy
Range
Resolution
> 20V and > 20A
< 20V or < 20A
0.000 – 1.000
0.001
± 0.04
±0.1
Phase Angle
(
Φ
)
Range
Resolution
Accuracy
-180° to 180°
0.1°
± 1°
0° to 360°
0.1°
± 1°
Total Harmonic Distortion
(THD-F with respect to the 50 or 60 Hz, min. value at 50
or 60 Hz > 80V and > 20 A, 1 to 50
th
Harmonics. If the voltage or current is 0 at 50 or
60 Hz, all the percentage (%) display is 0)
Range
Resolution
Accuracy
0.0 – 20%
0.1%
± 2%
20.1 – 100%
0.1%
± 6% of reading ± 1%
100.1 – 999.9 %
0.1%
± 10% of reading ± 1%
Peak Value of AC Voltage (peak value > 10V) or AC Current (peak value > 20A)
Range
Sampling Time
Accuracy of Reading
50 Hz
39
µ
s
± 5% ± 50 digits
60 Hz
33
µ
s
± 5% ± 50 digits
Summary of Contents for PCE-GPA 62
Page 1: ...Graphic AC Power Quality Analyzer PCE GPA 62 Users Manual PCE Group...
Page 11: ...6 HOUR MINUTE STOP TIME schedule when to stop datalogging HOUR...
Page 14: ...9 TOLERANCE...
Page 17: ...12 MONTH DAY...
Page 20: ...15 NOTE Frequency Hz is displayed in the second page Harmonics order 25 th to 50 th order...
Page 23: ...18 NOTE Frequency Hz is displayed in the second page Harmonics order 25 th to 50 th order...
Page 24: ...19 III 4 Waveforms of ACV andACAwith Phase Angle...
Page 30: ...25 III 5 6 RMS values of Voltage and Current...
Page 35: ...30...
Page 45: ...40 Press the FUNC button to start transient detection...
Page 48: ...43...
Page 58: ...53...