If testing the concrete casting side is in horizontal direction, then angular correction and 
casting  surface  correction  are  not  needed.  Before  the  test,  test  direction  and  concrete 
casting  surface  are  set,  so  the  apparatus  will  correct  the  average  rebound  value 
automatically.

 

Concrete  strength  value  of  testing  zone:

  after  testing,  it  needs to  calculate  the  average 

rebound  value  of  testing  zone  and  conduct  relevant  correction.  According  to  user’s 
requirement, it needs to choose “national standard-pumping” or “national standard-non 
pumping” and then get concrete strength value of testing zone according to carbonization 
depth value. For example, average rebound value is 24, test angle is 30 upward, casting 
surface is top surface, carbonization depth is 0.5mm. If angular correction is -2.8 and then 
the corrected rebound value is 21.2; if top surface correction value is +2.1, the corrected 
rebound value is 23.3; rebound value 23.3 and 0.5mm carbonization depth corresponds to 
the concrete strength of 13.4Mp.

 

Concrete  strength  value  and  standard  deviation  of  components:  after  testing  the 
components,  the  apparatus  shall  calculate  the  concrete  strength  value  and  standard 
deviation of components automatically and save them, according to the relevant formulas 
of 

Regulations

.

 

1.5.2.

 

Calculation of concrete strength under customized measuring mode. 

When  user’s  preset  parameter  does  not  confirm  to  Regulations,  that  is,  customized 
measuring mode, such as the test times are less than 16.

 

Calculation  of  average  rebound  value  of  testing  zones.  After  the  testing,  maximum  and 
minimum values are not taken out, only conduct the average calculation. 

 

For  angular  correction,  casting  surface  correction,  the  setting,  calculation,  standard 
measuring mode and correction method of these two parameters are the same.

 

Concrete  strength  value  of  testing  zone:  after  testing,  it  needs  to  calculate  the  average 
rebound  value  of  testing  zone  and  conduct  relevant  correction,  if  the  user  chooses 
“national  standard-pumping”  or  “national  standard-non  pumping”,  it  can  get  concrete 
strength  value  of  testing  zone  according  to  carbonization  depth  value.  This  concrete 
strength value can only be used as a reference value, because it does not conform to the 
relevant provisions of 

Regulations

. If the user has already formulated its own specific curve, 

and set the apparatus strength-measuring curve as this specific curve, the apparatus will 
refer to the table to get the concrete strength formulated by user itself.

 

Concrete  strength  value  and  standard  deviation  of  components:  after  testing  the 
components, the apparatus will average the contained concrete strength value of testing 
zone  and  get  the  concrete  strength of  component,  and  calculate  the  standard deviation 
automatically according to the relevant formulas.

 

If the parameters, calculating method and apparatus used by the user are different from 
the  set  ones,  the  original  rebound  value  can  be  transmitted  to  computer  taking 
components as unit via the equipped upper computer software.

 

 

 

Summary of Contents for PCE-HT 224E

Page 1: ...pce americas com PCE Instruments UK Ltd Unit 11 Southpoint Business Park Ensign way Hampshire Southampton United Kingdom SO31 4RF From outside UK 44 Tel 0 2380 98703 0 Fax 0 2380 98703 9 info pce inst...

Page 2: ...3 2 1 3 Setting the number of test zone 11 3 2 2 Test zone setup 12 3 2 2 1 Setting test angle 12 3 2 2 2 Setting poured surfaces 12 3 2 2 3 Setting carburized depth 12 3 2 2 4 Setting strength curve...

Page 3: ...ta collection without changing the original physical structure of mechanical rebound apparatus in which way the optical coupler sensor has no contact nor friction with the mechanical part of rebound a...

Page 4: ...guide bar 10 Hammer mass 11 Guide sleeve 12 Two part ring 13 Felt washer 14 Impact plunger 15 Cap 16 Retaining spring 17 Impact spring 18 Housing Aluminum ring 19 Housing upside 20 Pointer piece 21 Se...

Page 5: ...ing zones 16 Maximum number of test points in a testing zone 16 times National unified curve 1 Customized curve 2 Battery can charge high capacity Li ion battery Data interface Mini USB interface Type...

Page 6: ...at used for the rebound strength value achieved by completing testing zone or structure test According to the set parameters rebound value is corrected accordingly and then the strength result is calc...

Page 7: ...30 upward casting surface is top surface If the angular correction value is 2 8 then the corrected rebound value is 21 2 if the angular correction value is 2 1 then the corrected rebound value is 23 3...

Page 8: ...that is customized measuring mode such as the test times are less than 16 Calculation of average rebound value of testing zones After the testing maximum and minimum values are not taken out only con...

Page 9: ...g curve can be modified After modification choose ok to exit and the apparatus will save the corrected content automatically 1 6 2 Testing zone is completed If the recoiling times reach the set test t...

Page 10: ...2 Button Description...

Page 11: ...measuring from the menu and press to enter measuring mode In this mode you can take measurement 3 2 Test mode setup Select Test mode setup from the menu and press to enter test mode setup interface 3...

Page 12: ...t 3 2 1 2 Setting the number of test time In the interface of new part use upward and downward buttons to select Test time and press Enter button to enter setting interface Press and to adjust the num...

Page 13: ...e parameter interface of new test zone use upward and downward buttons to select pouring surface and click Enter button to set pouring surface There are a total of 3 surfaces available Top surface Bot...

Page 14: ...he parameter interface of test part After selection the default carburized depth of each test zone is the same as that of this test part The carburized depth of each test zone can be modified in the p...

Page 15: ...er main menu select Test mode setup and press to enter test mode setup interface Select Re testing the current zone and press to re test the current zone The test no will return to 0 3 2 4 Basic Measu...

Page 16: ......

Page 17: ...nu 1 Exit from current menu and enter measuring interface 2 Re view part data review the results of completed test parts 3 Re view zone data review the results of completed test zones Enter Re view zo...

Page 18: ...Data transfer Click Enter button to go to main menu Then select Data transfer and click Enter to enter Data transfer menu Before creating communication between instrument and PC use USB cable to conne...

Page 19: ...er limit setup Set up upper lower limit of rebound value 00 60 Press and to change the number then press to save 3 6 4 Rights management In this menu user can enable disable and change password for th...

Page 20: ...Press to move cursor to next number press to change current number from 0 to 9...

Page 21: ...g interface in 30 power consumption in this mode the instrument could work 13 16 hours after fully charging In power saving measuring modes press to switch to normal measuring interface press again an...

Page 22: ...3 6 8 Battery power Show the percentage of battery capacity 0 100...

Page 23: ...the completion interface of test part and the measurement for the current test part is completed The completion interface of test part contains Review test part result Review test zone result New par...

Page 24: ...wed After maintenance calibration test shall be conducted according to the requirements and the calibration value shall be 80 2 5 Introduction of PC software Thedata communication software is designed...

Page 25: ......

Page 26: ...n the desktop automatically Double click the shortcut to run the program The main interface of the software is a standard windows form containing the title bar menu bar and toolbar Please note After r...

Page 27: ...ocess pointer block 22 shakes moves up to a certain place and stops there pointer block 22 rubs or bumps spring back hammer body 7 File the upper surface or two shoulders of pointer block 22 appropria...

Page 28: ...The shock surface of recoiling hammer mass 10 is dirty Clean the dirt on casting surface 5 The friction between recoiling hammer mass 10 and central guide rod increases Wipe the hammer guide bar 9 wi...

Page 29: ...28 2 29 1 31 17 6 18 9 19 6 21 0 24 9 28 2 29 1 30 0 30 9 32 19 1 20 8 21 2 22 7 26 5 29 8 30 7 31 6 32 5 33 20 8 22 0 22 7 24 3 28 2 31 6 32 5 33 5 34 4 34 22 4 23 6 24 5 26 0 30 0 33 3 34 2 35 2 36...

Reviews: