Page 75
FIELDBUS PROTOCOL
INPUT DATA AREA
The following table lists the input area registers (prepared by the instrument and read from the master),
common to all PROFINET, ETHERCAT, ETHERNET/IP fieldbuses. The registers have a size of 16 bits.
The input area is updated to a maximum frequency of 90 Hz (60 Hz for PROFIBUS fieldbus). The size
of the Input area set in the fieldbus master must coincide with the dimension set in the instrument.
Byte
Register
address
INPUT AREA REGISTER
Notes
1-2
0
Register Status
See the relevant table
3-4
1
Gross weight (MSW)
Value INT. - Most significant word
5-6
2
Gross weight (LSW)
Value INT. - Less significant word
7-8
3
Net weight (MSW)
Value INT. - Most significant word
9-10
4
Net weight (LSW)
Value INT. - Less significant word
11-12
5
Digital inputs on board the
MCT
See the relevant table.
13-14
6
Digital outputs on board the
MCT
See the relevant table.
15-16
7
Digital inputs of external
modules
See the relevant table.
17-18
8
Digital outputs of external
modules (MSB)
Value INT. - Most significant word
See the relevant table
9
Digital outputs of external
modules (LSB)
. Value INT. - Most significant word
See the relevant table
19-20
10
Cell signal
Value INT.
21-22
11
Tare (MSW)
Value INT. - Most significant word
23-24
12
Tare (LSW)
Value INT. - Less significant word
25-26
13
Batching operation
See the relevant table
27-28
14
Batching status
See the relevant table
29-30
15
Current cycle
Value INT.
31-32
16
Current step
Value INT.
33-34
17
Current activity
Value INT.
35-36
18
Current batching setpoint (MSB) Value INT. - Most significant word
37-38
19
Current batching setpoint (LSB)
Value INT. - Less significant word
39-40
20
Dosed net (last MSW step
finished)
Value INT. - Most significant word
41-42
21
Dosed net (last LSW step
finished)
Value INT. - Less significant word
43-44
22
Dosed net alarm (last step
finished)
Value INT.
45-46
23
Monitor Register
This value corresponds to the equivalent register in the output
area.
47-48
24
Active recipe
Value INT.
49-50
25
Active recipe correction factor
(MSW)
Value INT. - Most significant word
51-52
26
Active recipe correction factor
(LSW)
Value INT. - Less significant word
53-54
27
Batching cycles
Value INT. - Less significant word
55-56
28
Selected recipe total (MSW)
Value INT. - Most significant word See command/data register
57-58
29
Selected recipe total (LSW)
Value INT. - Less significant word See command/data register