Page 28
ENTER AND EDIT ACTIVITY
Message
Description
Type Units Default
Range
Fieldbus
address
Name Activity
Alphanumeric name of the activity.
Alphanumeric
setup
0
Max. 14
alphanumeric
characters
0252-
0258
Type of activity
Selection of the activity type. (*)
Selection
0
[0] AUTO DOS.
[1] MAN. DOS.
[2] TOT. UNL.
[3] INT. UNL
[4] SET ACT.
[5] TIMER
[6] OUTPUT
[7] INPUT
[8] UNL. DOS.
0259
Fine
Fine is the amount of weight that
you want to batch at reduced
speed. This value must be less than
the set value set in the recipe. By
programming this value to zero, the
component is batched entirely at
Coarse output.
Parameter used only for "activity
type”” =
AUTO DOS.
.
Numeric setup
W
eight measurement
unit
0
0÷Cell capacity
0260
(MSW)
-
0261
(LSW)
Inflight
The Inflight is the amount of material
that by inertia of the system is
added to the batched material
after the Fine batching output has
switched off.
The settable value must be less
than the set value set. Load output
deactivation set point = value set -
Inflight
Parameter used only for "activity
type”” =
AUTO DOS.
.
Numeric setup
W
eight measurement unit
0
0÷Cell capacity
0262
(MSW)
-
0263
(LSW)
Inflight compensation
This parameter, if different from
zero, applies an automatic
correction of the inflight value. At
the end of each automatic batching
activity, the difference between
the batched value and the set is
checked. This difference is used
to calculate the new inflight value,
based on the percentage set in this
parameter. The value obtained is
limited to 10% of the activity set
value and in any case cannot be
higher than the tolerance value.
Numeric setup
%
0.0 0.0 ÷ 100.0
0275