61
[I:03_Hot (Highest Outdoor Temperature)]
(page 53)
1 sec.
This should be set to the highest average outdoor
temperature during the winter season.
(not the highest possible outdoor temperature.)
settings:
[Min Set-point + 10°F (5°C)] or more 110°F (43°C)
[I:04_Lot (Lowest Outdoor Temperature)]
(page 53)
1 sec.
This should be set to the lowest average outdoor
temperature during the winter season.
(not the lowest possible outdoor temperature.)
NOTE
When [I:02_tHS] setting is “7:CU”,
[I:03_Hot] and [I:04_Lot] functions
will appear.
[I:03_Hot] and [I:04_Lot] are for changing the
highest and the lowest outdoor temperature range.
You can set the Highest Outdoor Temperature
[I:03_Hot] and the Lowest Outdoor Temperature
[I:04_Lot], when [I:02_tHS]_“7:CU” is selected.
settings:
-4
°F
(-20
°C
) or more [Max Set-point - 10
°F
(5
°C
)]
(Default setting =
70°F (21°C)
)
(Default setting =
20°F (-7°C)
)
[I:05_HHt (Heating High Temp Range)]
(page 53,57)
1 sec.
settings:
[Min Set-point + 30
°F
(17
°C
)] or more 180
°F
(82
°C
)
[I:06_HLt (Heating Low Temp Range)]
(page 53,57)
1 sec.
settings:
80
°F
(27
°C
) or more [Max Set-point - 30
°F
(17
°C
)]
(Default setting =
180°F (82°C)
)
(Default setting =
100°F (38°C)
)
[[I:05_HHt] and [I:06_HLt] are for changing
the heating high temperature range and low
temperaturerange.
You can change the Highest Set Temperature [I:05_
HHt] and the Lowest Set Temperature [I:06_HLt] by
adjusting the numbers on the display.
If [I:01_HCt]_“2:or” is selected then the settings
for [I:05_HHt] and [I:06_HLt] will beoverridden by
[I:02_tHS] settings. (except below)
If [I:02_tHS]_“7:CU” is selected then the settings
for [I:05_HHt] will be the heating hightemperature
range and [I:06_HLt] will be heating low
temperature range.
Installer Mode (Parameter Settings)