All-in-one solar charge inverter V11 28
Parameter
no.
Parameter
name
Settings
Description
18
Battery
equalized time
[18] 120
default
Equalizing charge time; setting range: 5min~900min,
with a step of 5 minutes; valid for vented lead-acid
battery and sealed lead-acid battery
19
Battery
equalized time
out
[19] 120
default
Equalizing charge delay; setting range: 5min~900min,
with a step of 5 minutes; valid for vented lead-acid
battery and sealed lead-acid battery
20
Battery
equalization
interval
[20] 30
default
Equalizing charge derating time, 0~30days, with a
step of 1 day; valid for vented lead-acid battery and
sealed lead-acid battery
21
Battery
equalization
immediately
[21] DIS
default
Stop equalizing charge immediately.
[21] ENA
Start equalizing charge immediately.
22
Power saving
mode
[22] DIS
default
Power saving mode disabled.
[22] ENA
After the power saving mode is enabled, if the load is
null or less than 50W, the inverter output is turned off
after a delay for a certain period of time. When the
load is more than 50W, the inverter automatic restart.
23
Restart when
over load
[23] DIS
Automatic restart when overload is disabled. If an
overload occurs and the output is turned off, the
machine will not restart.
[23] ENA
default
Automatic restart when overload is enabled. If an
overload occurs and the output is turned off, the
machine will restart after a delay of 3 minutes. After it
reaches 5 cumulative times, the machine will not
restart.
24
Restart when
over
temperature
[24] DIS
Automatic restart when over temperature is disabled.
If an over-temperature shutdown occurs, machine will
not restart to turn the output on.
[24] ENA
default
Automatic restart when over temperature is enabled.
If an over-temperature shutdown occurs, the machine
will restart when the temperature drops.
25
Alarm enable
[25] DIS
Alarm is disabled
[25] ENA
default
Alarm is enabled
26
[26] DIS
Alarm beep is disabled when the status of the main
input source changes