87 - PVD 3622_GB_TM_January 2014.Docx
According to the table “Parker Hiross Chiller selection vs TMW series” given
The motor needs a chiller:
ICE022
with
0%
glycol,
ICE029
with
20%
glycol,
ICE029
with
40%
glycol.
Glycol concentration
0%
20%
40%
Flow rate requested [l/min]
25
26.5
29.4
Chiller type:
ICE022
ICE029
ICE029
Flow rate capability [l/min]
25.5
33.1
33.1
Main formulas
p
C
n
dissipatio
Power
rate
Flow
*
60
*
_
_
With:
Flow rate
[l/min]
Power_dissipation
[W]
°
Gradient inlet-outlet [°C]
Cp
thermal specific capacity of the water as coolant [J/kg°K]
(
Cp
depends on the % glycol concentration please see below)
Thermal specific capacity
Cp
according to % glycol concentration and
temperature
We have considered an average temperature of the coolant of 30°C.
Glycol concentration
[%]
Average temperature of the water as
coolant [°C]
Thermal specific capacity of the water
Cp
[J/kg°K]
0
30
4176
30
30
3755
40
30
3551
50
30
3354
Summary of Contents for TM Series
Page 1: ...1 PVD 3622_GB_TM_January 2014 Docx Torque Motors TM Series Technical Manual PVD 3622...
Page 57: ...57 PVD 3622_GB_TM_January 2014 Docx 3 3 1 2 Shaft Height 200 mm Thrust bearing 29424...
Page 61: ...61 PVD 3622_GB_TM_January 2014 Docx 3 3 2 2 Shaft Height 315 mm Thrust Bearing 29426...
Page 62: ...62 PVD 3622_GB_TM_January 2014 Docx 3 3 2 3 Shaft Height 315 mm Thrust Bearing 29430...
Page 66: ...66 PVD 3622_GB_TM_January 2014 Docx 3 3 3 2 Shaft Height 400 mm Thrust Bearing 29434...
Page 67: ...67 PVD 3622_GB_TM_January 2014 Docx 3 3 3 3 Shaft Height 400 mm Thrust Bearing 29440...