Page 92
– Bulletin 100-50-9.1
7. PASSWORDS
7.1
S3C PASSWORDS
Access to the S3C Case Control system configuration
parameters and service functions are password protected.
There are two levels of password protection; Administrator
and Technician. The Administrator password allows access
to all system control and configuration parameters for pur-
poses of setting up the S3C control system for an intended
application. The Technician password allows access to the
Service Menu where a service technician can access ser-
vice functions such as forcing a valve position or changing
operating modes (See Service Section). Parameter changes
made with the Administrator level are permanent whereas
Technician level changes are temporary and revert to their
original values when exiting the Service Menu. Passwords
are numeric and can range from 0 – 4999.
Note: The
default Administrator password is 19 and the default
Technician password is 81.
7.1.1 SETTING PASSWORDS
To set the two levels of passwords:
1. From the
default
display, press the
button. The
display will show
.
2. Use the
▲▼
buttons to enter the
administrator
password and press
SET.
3. The display will show
(will skip to Process Values
if system is self-contained).
4. Press the
SET
button and
(Process Values) will be
displayed.
5. Press the
▼
button until
d
(Display) is showing.
6. Press the
SET
button and
d
(Administrator
Password) will be displayed.
7. Press the
SET
button and use the
▲▼
buttons to
adjust the password value.
8. Press the
SET
button to enter the new value. The
display will revert to
d
.
9. Press the
ESC
button 3 times to revert to the
default
display.
To set the Technician password:
1. From the
default
display, press the
button. The
display will show
.
2. Use the
▲▼
buttons to enter the
administrator
password and press
SET.
3. The display will show
(will skip to Process Values
if system is self-contained).
4. Press the
SET
button and
will be displayed.
5. Press the
▼
button until
d
is showing.
6. Press the
SET
button and
d
(Administrator
Password) will be displayed.
7. Press the
▼
button until
(Technician Password)
will be displayed.
8. Press the
SET
button and use the
▲▼
buttons to
adjust the password value.
9. Press the
SET
button to enter the new value. The
display will revert to
.
10. Press the
ESC
button 3 times to revert to the
default
display.
8. MENU STRUCTURE
The S3C Case Control system has a structured menu
design that allows Administrators and Service Technicians
to access key parameters independently. The structure
includes menus for the Case, Line-Up and Evaporator. Each
menu has viewable parameters related to that subsystem.
See following figure. Subsequent sections will define each
menu in more detail.
A new controller starts with the Set-Up menu. This enables
the product to be set-up through the display. The controller
may also go into the Set-Up menu after a factory reset.
See Service Section for more information on factory reset
option. After the control system has been set-up, it will enter
the “default display” which shows the case temperature
or mode of operation such as defrost. The default display
menu is read only and does not require a password. This
top level view may be used for a quick check on system
variables, such as case superheat or EEPR position. For
example, to view Case superheat:
From the
default
display, press the
▲
button to
then
press
SET.
1. Press the
▲
button and scroll to
.
2. Press
SET
button to show current superheat value.
3. Press
ESC
button three times to return to
defu
display (discharge air).
Default Display
View/Case
Evaporator 1 Parameters
View/Case
Line-up Parameters
View/Case
Evaporator 3 Parameters
View
Evaporator 2 Parameters
▲▼
▼
▼
▼