Bulletin 100-50-9.1 –
Page 55
7. Press the
SET
button when
(Expansion Valve
Type) is displayed. Use
▲▼
buttons to choose the
Expansion Valve Type based on the below chart; press
SET.
8. Press the
SET
button when
e
(Number of
Evaporators) is displayed. Use the
▲
button and scroll
to
2
(2 Evaporators); press
SET.
9. Press the
SET
button when
(Building Automation
System Expected) is displayed. Use the
▲▼
buttons to
choose
e
or
o
; press
SET.
a. If
e
is chosen, the display will show
(Building
Automation System Protocol). Press the
SET
button
then use
▲▼
buttons to choose the B.A.S. Protocol
based on the below chart; press
SET.
10. Press the
SET
button when
o
(Month) is shown. Use
the
▲
button to choose the current month; press
SET.
11. Press the
SET
button when
d
(Day) is shown. Use the
▲
button to choose the current day; press
SET.
12. Press the
SET
button when
d
(Day) is shown. Use the
▲
button to choose the current day; press
SET.
13. Press the
SET
button when
e
(Time) is shown.
Use the
▲
button to choose the current time in 24
hour format; press
SET.
Note: Holding the
▲
or
▼
down while setting the time will accelerate the
scrolling.
14. Press the
SET
button when
ef
(Refrigerant Type) is
shown. Use the
▲▼
buttons to choose the Refrigerant
Type; press
SET.
The list of refrigerants can be seen in
Table on page 99.
15. Press the
SET
button when
(Number of Cases
Expected in Line-up) is shown. Use the
▲▼
buttons to
choose the number of cases expected in the Line-up;
press
SET.
16. Press the
SET
button when
(Evaporator Pressure
Regulating Valve Type) is shown. Press the
▼
button to
scroll to
oe
(No EEPR); press
SET.
17. Press the
SET
button when
d
(Discharge Air
Temperature Setpoint) is shown. Use the
▲▼
buttons to
choose the setpoint in °F; press
SET.
18. Press the
SET
button when
def
(Defrost Type) is
shown. Use the
▲▼
buttons to choose the Defrost Type;
press
SET.
Defrost options are:
19. Press the
SET
button when
d
(Defrost Termination
Temperature Setpoint) is shown. Use the
▲▼
buttons to
choose the setpoint in °F; press
SET.
20. Press the
SET
button when
de
(Defrost Termination
Fail-safe Time) is shown. Use the
▲▼
buttons to choose
the fail-safe time in minutes; press
SET.
21. Press the
SET
button when
dfd
(Number of Defrosts
Per Day) is shown. Use the
▲▼
buttons to choose the
defrost per day; press
SET.
The S3C Case Control system is now set-up and will begin
controlling the refrigerated display case.
Display
Meaning
u
Pulse Width Modulation Valve
5
500 Step Valve
1596
1596 Step Valve
25
2500 Step Valve
3193
3193 Step Valve
6386
6386 Step Valve
u
Custom Stepper Valve (See Section 11)
Display
Meaning
hg
Hot gas
ee
Electric
Air
Display
Meaning
485
Modbus Protocol over RS-485
6485
Bacnet Protocol over RS-485
Bacnet Protocol over IP (Ethernet)
o
Modbus Protocol over IP (Ethernet)