Page 10
– Bulletin 100-50-9.1
Temperature Out of Range
If the measured Discharge Air temperature transgresses the
user selected high or low alarm thresholds, the Quick View
indicators will change to
ORANGE
.
Temperature Alarm
If the measured Discharge Air temperature transgresses the
user selected high or low alarm thresholds for the appropriate
alarm delay period the
icon illuminates.
Service Required Alarm
The
icon illuminates as an indication that an alarm
condition exists not related to case temperature such as a
faulty sensor, loss of peer – peer communication, disconnected
EEPR or EEV, etc.
3. SYSTEM SPECIFICATIONS
3.1
S3C CASE CONTROL
Electrical
Supply 22 to 26 VDC @ 0.5A minimum
Notes:
1. External DC Power Supply must be Class 2 and
Class II rated.
2. Maximum wire length between power supply
and Case Control is 400 ft. (22AWG minimum).
Digital Inputs (4)
Dry contact or Open Collector connection only. Negative
reference to be supplied by the Case Control only.
Note: Occupancy Sensor 5V excitation voltage
.75mA maximum.
Analog Inputs (7)
Temperature Inputs (5)
2K, 3K, 10K Thermistor (Software selectable)
Note: Auxiliary Temperature input configurable via
software as current transformer (CT) input.
CT Output 0 - 5 VDC measuring 0 - 50 Amps AC 50/60 Hz.
Pressure Transducer (1)
.5 – 4.5 VDC Ratiometric output.
Pressure ranges: 150 PSI, 300 PSI, 500 PSI, 652 PSI and
Custom
(Absolute or Gauge software selectable)
Digital Sensor Inputs (1)
Proprietary 1-Wire Relative Humidity and Ambient Tem-
perature sensor
Note: Relative Humidity and Ambient Temperature
sensor 5V supply voltage 1.5mA maximum.
Relay Outputs (4)
Solenoid/Pulse EEV – 240VAC/1A
Defrost – 240VAC/6A
Fan(s) – 240VAC/6A
Lights – 240VAC/6A
Stepper Motor (1)
Unipolar/Bipolar 13.5VDC @ 400mA/Ø
200 pps/400 pps Software selectable
External Solid State Relay (1)
Anti-sweat Heater Control 5VDC @ 25mA
Analog Output (2)
0 – 10VDC @ 40mA maximum