6.22 WALK-IN SINGLE EVAPORATOR WITH EEV AND EEPR – CONFIGURATION V
The S3C case controller is capable of controlling and monitoring walk-in coolers and freezers equipped with electric
defrost. For a single coil walk-in with an EEV and EEPR, one S3C case controller and one S3C valve module are required.
In the scenario detailed above, the typical control method involves controlling return air temperature (box temp) with the
EEPR and controlling superheat with the EEV. As with all evaporators equipped with an EEV, a liquid line solenoid (LLS) or
suction stop solenoid is optional as flow through the evaporator can be stopped by closing the EEV.
To configure the S3C control package for Configuration V
shown above, follow these directions:
If the controller has not been factory set, then upon initial
start-up, the controller will be in set-up mode and the screen
will display
(for self-contained case).
1. Press the
SET
button, then use
▲▼
buttons to scroll
to
o
; press
SET.
This will configure the controller to
support a remote case.
2. Press the
SET
button when
(Rack Identifier)
is displayed. Use the
▲▼
buttons to configure the 4
character Rack Identifier.
Note: Push
▲
button for
numeric,
▼
for alpha characters.
When satisfied
with each digit, press the
SET
button to go to the next
digit. Pressing
SET
multiple times will move to the
next parameter.
3. Press the
SET
button when
ud
(Line-up Identifier)
is displayed. Use the
▲▼
buttons to configure the 4
character Line-up Identifier.
Note: Push
▲
button
for numeric,
▼
for alpha characters.
When
satisfied with each digit, press the
SET
button to go to
the next digit. Pressing
SET
multiple times will move
to the next parameter.
4. Press the
SET
button when
d
(Case Identifier)
is displayed. Use the
▲▼
buttons to configure the 4
character Case Identifier.
Note: Push
▲
button for
numeric,
▼
for alpha characters.
When satisfied
with each digit, press the
SET
button to go to the next
digit. Pressing
SET
multiple times will move to the next
parameter.
5. Press the
SET
button when
(Application Type) is
displayed. Use the
▲
button and scroll to
(Walk-In);
press
SET.
6. Press the
SET
button when
(Local Stepper Valve
Configuration) is displayed. Use the
▲
button to scroll to
(Electronic Expansion Valve); press
SET.
This is the
valve that is attached to the main S3C Case Controller.
7. Press the
SET
button when
(Expansion Valve Type)
is displayed. Use
▲▼
buttons to choose the Expansion
Valve Type based on the below chart; press
SET.
8. Press the
SET
button when
e
(Number of
Evaporators) is displayed. Use the
▲
button and scroll to
1
(1 Evaporator); press
SET.
9. Press the SET button when
(Building Automation
System Expected) is displayed. Use the
▲▼
buttons to
choose
e
or
o
; press
SET.
Display
Meaning
u
Pulse Width Modulation Valve
5
500 Step Valve
1596
1596 Step Valve
25
2500 Step Valve
3193
3193 Step Valve
6386
6386 Step Valve
u
Custom Stepper Valve (See Section 11)
EEV 1
EEPR (CDS)
Suction
CASE
Liquid
Liquid Line
Solenoid
(optional)
WALK-IN SINGLE EVAPORATOR WITH EEV AND EEPR – CONFIGURATION V