background image

Page 2

and the user sets these values via MODBUS then the Kelvin 

II will automatically leave the setup menu.  

Table 1 Setup Menu

Displayed Menu Item

Description

Selections

StEP

Valve Type

1596, 3192, 2500, 6384, 400

rEFr

Refrigerant

r22, 134A, 402A, 404A, 

407A, 407C, 410A, 417A, 

r507, 422d, r744, 245F

PtYP

Pressure Sensor Type gAUg, AbSL

un_T

Temperature Units

FAHR, CELS

un_P

Pressure Units

PSI, BAR

After setup, the Kelvin II defaults to showing the Superheat 

value. The user can then turn the knob to view the other pro-

cess values of their system. The screen will alternate between 

the process values identity and value alternating every 3 sec-

onds. For ease of use, the value that is displayed for a process 

value may come in the form of text to eliminate the need of 

‘looking up the meaning’. The menu text and meanings for 

process values are described in Table 2.
The user may also view/edit the setpoints by pressing the knob 

and holding it down for 5 seconds. The user is then prompted 

for a password to verify his credentials. The knob should be 

rotated up to ‘111’ for the password. If the password is cor-

rect the user may change the setpoints to the value he desires 

in order to obtain optimum system performance. The menu 

text and meanings for setpoint values are described in Table 3. 

Setpoints are saved to the controller when the user leaves the 

Setpoint menu by pressing the knob when “ESC” is shown. 

The setpoint menu has a timeout of 60 seconds for inactiv-

ity. When this timeout is reached the controller goes back to 

showing the process values and does not save any setpoints 

that might have been changed. If the user is in the Manual 

Valve Position setpoint then this timeout length is 60 minutes.   

As long as the controller does not time out the 60 minutes, 

Setpoints are saved to the controller when the user leaves the 

Setpoint menu by pressing the knob when “ESC” is shown.

All process values and setpoints are accessible

1

 through the 

local and remote displays. 

Table 2 Process Value Menus

Displayed Menu Item

Description

Range

SuPH

Superheat

0 to 165°F, 0 to 91.6°C

SucP

Suction Pressure

4

0 to 150 PSI, 0 to 10.34 Bar 

tSAt

Saturation Temperature -60 to 150°F, -51.1 to 65.6°C

tout

Suction Temperature

-60 to 150°F, -51.1 to 65.6°C

CtP

System Temperature

-60 to 150°F, -51.1 to 65.6°C

PoSn

Valve Position

0 to 100% Open

S-3

Auxiliary Temperature

2

  -60 to 150°F, -51.1 to 65.6°C

rELA

Solenoid Status

dEng, Eng

StAt

System Cycle Status

Current cycle and manual 

valve position state

ALS

Alarm Status

3

 

noAL or all active alarms

Table 3 Setpoint Menu

Displayed 

Menu 

Item

Description

Range

Default 

Setting

User

Setpoints

ESC

Escape and save 

settings

SHSP

Superheat Setpoint 0 to 45°F, 0 to 25°C 8

rEFr

Refrigerant

r22, 134A, 402A, 

404A, 407A, 407C, 

410A, 417A, r507, 

422d, r744, 245F

404A

d_On

Delay On

0 to 60 seconds

0

dOFF

Delay Off

0 to 60 seconds

0

d_St

Delay Percent Open 

of Valve

0 to 100 percent

0

CtSP

Cut-out Suction 

Pressure

0 to 150

4

 

PSI, 

0 to 10.3

4

 Bar

0

H_oP

Maximum Operating 

Pressure

0 to 150

4

 PSI, 

0 to 10.3

4

 Bar

150

C_in

Cut-in Temperature -60 to 125°F, 

-51.1 to 51.6°C

-59

Cout

Cut-out Temperature -60 to 124°F, 

-51.1 to 51.1°C

-60

HiCP

Max Valve Capacity 20 to 100%

100

SUPS

Supermarket Setting OFF, ON

OFF

-P-

Proportional 

Coefficient

0 to 100

40

-I-

Integral Coefficient 0 to 100

25

-d-

Derivative 

Coefficient

0 to 100

5

StEP

Valve Type

1596, 3192, 2500, 

6384, 400

1596

SPoS

Manual Valve 

Position

0 to 100% Open

Present 

Position

nEt

Network Type 

(MODBUS or 

Network Master)

nbUS (MODBUS) 

or ProP (Network 

Master)

nbUS

Addr

MODBUS/Network 

Master Address

1 to 255

1

un_P

Pressure Units

PSI, BAR

PSI

un_T

Temperature Units

FAHR, CELS

FAHR

PtYP

Pressure Sensor 

Type

AbSL, gAUg

gAUg

CaLP

Pressure Sensor 

calibration value

-5 to 5 PSI, 

-0.34 to 0.34 Bar 

0

CLt1

Tout calibration 

value

-5 to 5°F, -2.7 to 

2.7°C

0

CLt2

Ctp calibration value -5 to 5°F, -2.7 to 

2.7°C

0

CLt3

S-3 calibration value -5 to 5°F, -2.7 to 

2.7°C

0

CAdr

Controller Display 

Address

0 to 99

0 or 1 

for local 

display

4. Kelvin II MODBUS

The  Kelvin  II  can  communicate  with  a  MODBUS  master. 

The Kelvin II will transfer process values and setpoints via  

MODBUS. 

1

  Setpoints can only be viewed and edited when the proper password is entered.

The Auxiliary Temperature sensor input has a special Pumpdown feature. If a “short” or switch closure is placed across these terminals, the valve will    

shut for pumpdown. The full details of this feature are described in Section 5.

3

  The Alarm Status process value is described in Section 6.

4

  The maximum value varies based on which refrigerant is selected. (R-410A is 300 PSI, R-744 is 500 PSI and all others are 150 PSI).