Parker Sporlan Kelvin II User Manual Download Page 5

Page 4

MODBUS 

Function 

Code

Mapped 

Data

Data Map

Range

Read Input 

Registers 

(0x04)

Process 

Variables

8.   Alarm Status

If Bit set then alarm is 

active: 

Bit 0 = Suction 

Transducer Failure 

Bit 1 = Tout Sensor 

Failure 

Bit 2 = High Superheat 

Bit 3 = Low Superheat

9.   System Cycle  

 

Status

If Bit set then mode is 

active: 

Bit 1 = Setup Mode 

Bit 2 = Off Cycle 

Bit 3 = Cooling Cycle 

Bit 4 = Pump-down Cycle 

Bit 5 = Manual Valve 

Override Mode

Write Single 

Coil (0x05)

Manual 

Valve 

Control

Bit 0 = Manual Valve 

Enabled Flag

0 = Disabled, 

1 = Enabled. 

The Manual Valve 

duration Bit is read-only.

Write Single 

Register 

(0x06)

Setpoints Same as above.

The max number of 

registers written at a 

time is 

1.  The limits can be   

  seen above in the    

  ‘Read Holding  

 

  Register’ definition.

5. Kelvin II Features

5.1. Pumpdown Feature

The Kelvin II will initiate a pumpdown when Auxiliary Tem-

perature sensor terminals are shorted. If desired, this temper-

ature  connection  could  be  set  up  as  a  dry  contact. When  a 

pumpdown is desired the contact should be closed. The pump-

down will be ended when the short is removed provided that 

there are no sensor alarms.

5.2. Manual Valve Position Feature

The Kelvin II has the ability to manually control the valve. 

To enable this manual control via the local or remote displays 

simply open the setpoint menu and edit the ‘SPoS’ setpoint. 

When the value is displayed for this setpoint the user is manu-

ally controlling the valve. The valve position can be changed 

by rotating the knob clockwise or counterclockwise. There is 

an inactivity timer of 60 minutes while in manual control. The 

timer is reset each time the user moves the valve. The manual 

control of the valve is ended when the user presses the knob to 

go back to displaying ‘SPoS’ or a timeout has been reached.

6. Kelvin II Alarms

The  Kelvin  II  has  4  alarms.  The  following  table  lists  the 

possible  alarms  and  the  text  that  is  seen  on  the  controller. 

The controller’s alarm status can be viewed via MODBUS,  

Network Master, and local and remote displays. 

Table 5 Alarms

Alarm Text

Meaning

NoAL

No Alarms active

PSAL

Pressure Sensor alarm

TSAL

Tout Sensor alarm

HSAL

High Superheat alarm

LSAL

Low Superheat alarm

Normally,  on  the  process  value  screens,  the  process  value 

text alternates with its value. When an alarm is activated the 

alarm status “-AL-“screen is added to the rotation to make the 

user aware that an alarm has been activated. The Alarm Status 

menu display item ALS, will show the active alarms shown 

in Table 5.

7. Kelvin II Display Networking

The Kelvin II displays can be set up to access other Kelvin II 

controllers  on  the  network. The  controller’s  current  ‘CAdr’ 

value can be determined by pressing down the button on the 

display while viewing a process value.  To enable the display 

network the ‘CAdr’ setting MUST be set to a unique nonzero 

value with the RJ-45 connector on the side of the controller 

DISCONNECTED.

After ‘CAdr’ has been set, an ‘End’ screen is added just be-

fore  the  ‘SuPH’  process  value.  Pressing  the  button  on  the 

display while viewing the ‘End’ screen brings up a menu al-

lowing the selection of other Kelvin II controllers connected 

to  the  display  network.  Turning  the  knob  allows  the  selec-

tion of other Kelvin II controllers based on their appropriate 

‘CAdr’ address. The local controller is listed as ‘LocL’ by a 

local  display.  Note:  the  remote  display  always  includes  the 

‘End’ screen since it must be able to view any controller on the  

display network.

8. Kelvin II Factory Reset

A factory reset can be performed by holding the button down 

on the local or remote displays for 5 seconds when power is 

first  applied.  If  using  a  local  display  the  display  will  show 

‘FrSt’  while  the  factory  reset  is  being  performed  and  then  

automatically connect to the local controller.

If  using  a  remote  display  the  display  will  show  ‘FrSt’  and 

switch to a menu that allows the selection of the controller 

to reset. To perform a factory reset, select the controller with 

the appropriate ‘CAdr’ value. The display should show ‘----‘ 

while the reset is being performed. When finished perform

-

ing factory resets turn the knob counterclockwise until ‘ESC’ 

is shown on the display. Pressing the button while ‘ESC’ is 

shown on the display exits the factory reset menu and should 

automatically connect to a controller on the display network.

Table 6 Replacement Parts

Part Number

Description

952560

Kelvin II without display

952561

Kelvin II with local display

952562

Kelvin II Remote panel display

952662

Temperature Sensor Assembly

952795

Well Sensor Kit

953091

Pressure Transducer 150 psig with cable

952995

Pressure Transducer 150 psia with cable

952740

Pressure Transducer 300 psig with cable for 

R-410A applications only

952504

Pressure Transducer 500 psig with cable for 

R-477 applications only

Reviews: