Description

The Kelvin II is a standalone superheat controller. The Kelvin 

II may be connected with a MODBUS master or a Network 

Master  to  give  remote  access  to  pressure  and  temperature 

readings  in  addition  to  viewing  and  editing  the  controller’s 

setpoints. The user can also take advantage of the easy to use 

local  display  or  a  Remote  Display  to  accomplish  the  same 

tasks.

1. Kelvin II Configuration

Specifications

n

  Input Voltage: 24 VAC (± 10%), 40 VA minimum to board 

with external transformer

n

  Operating ambient temperature: -40°F to 120°F

n

  LED: One Power LED

n

  Communications: 1 RS485 Port, 1 USB port 

  (Not operational)

n

  4 Digit 7 segment display

n

  Inputs: 

  – Optical Encoder (Knob)

  – One Pressure Input

  – Three Temperature inputs

n

  Valve  Control  of  all  Sporlan  Electric  Expansion  Valves 

“EEV”

n

   3 amp Solid State Relay for Liquid Line Solenoid Kelvin II 

w/o Local Display

n

  1  amp Solid State Relay for Liquid Line Solenoid Kelvin II 

w/Local Display

2. Kelvin II Connections

The  Kelvin  II  has  screw  terminals  on  the  each  side  of  the 

controller. The controller should be wired as follows and as 

shown in Figure 1.

Item

Wire (line)

Kelvin II 

connect point

Power 

24VAC

1

24 VAC

2

Valve

SEI, SER, SEH ESX

N/C

Gray

4

Black

Orange

5

White

Yellow

6

Green

Red

7

Red

Black

8

RS-485

Ground

13

A+

14

B-

15

Liquid Line Solenoid

Line

19

Load

20

Auxiliary Temperature Sensor

(Displayed menu item: S-3)

T3

27
28

Room Temperature Sensor

(Displayed menu item:  CtP)

T2

29
30

Coil Out Temperature Sensor

(Display option: tout)

T1

31
32

Pressure Transducer

(Displayed menu item: SucP)

Sense (WHITE)

33

Ground (GREEN)

34

+5 VDC (BLACK)

35

3. Kelvin II Display

 

Upon the first power-up from Sporlan, the Kelvin II will en

-

ter  the  setup  menu. This  menu  allows  the  user  to  set  some 

critical setpoint values, seen in Table 1, before the controller 

will operate. These critical values can be set via the local or 

remote displays, MODBUS, or Network Master. (Note: Only 

the Valve Type and Refrigerant have to be set via MODBUS 

or Network Master for the controller to operate) Once these 

values are entered the Kelvin II will then begin its control. If 

the setup menu is displayed on the local or remote displays 

1

24 VAC

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

19

36

35

34

33

32

31

30

29

28

27

26

25

24

23

22

21

20

24 VAC

N/C

N/C

N/C

N/C

N/C

Ground

RS-485 A+

RS-485 B-

N/C

N/C

N/C

Load

Line

N/C

N/C

N/C

N/C

N/C

N/C

T3-

T3+

T2-

T2+

T1-

T1+

PWR

Room

Tout

RS485

Valve

LL Sol

N/C

Pressure

Aux

SER, SEI, SEH      ESX 
Red 

 

Black

Green   

Red

White   

Yellow

Black 

 

Orange

N/C 

 

Gray

  

Black

Green
White
  

+5VDC

Ground 
Sense  

Figure 1