Get Messages
i)
GetABV
A “1” will be returned if an Automatic Bypass Valve (ABV) is fitted across
inlet and outlet ports of the dryer.
ii)
GetAES
A “1” will be returned if Active Exhaust Silencers (AES) are fitted to the
exhaust ports of the dryer.
iii)
GetAFR
A “1” will be returned if an Automatic Fault Reset (AFR) is activated.
iv)
GetARS
A “1” will be returned if Automatic Re-start (ARS) is activated.
v)
GetCurrentSequenceTime
Requests the current position in the cycle in seconds. PNEUDRI electronic
Microprocessor dryer sequence counters, count down from a half cycle time
entered at commissioning. The return value will be from 0s to 10800s
(maximum) for DHE product and from 0s to 600s (maximum) for DXE and
MPXE product.
vi)
GetDDS
A “1” will be returned if Dewpoint dependent Switching (DDS) is activated.
vii)
GetDDSOverride (3.5 only)
A”1” will be returned if Dewpoint Dependent Switching Over-ride is Activated
viii)
GetDDSOverride Delay (3.5 only)
The Depoint Dependent Switching Over-ride Time Delay will be returned in
minutes, the returned valve will be 1 to 360
ix)
GetDewpoint
The outlet dewpoint from the dryer bank will be returned in milliCelsius.
viii)
GetDewpointAFS
A “1” will be returned if Automatic Fault Shutdown (AFS) on the outlet dew
point is activated.
x)
GetDigitalInputs
Requests the status of the 8-digital inputs, each bit of the returned 8-bit
binary number represents a particular digital input, as listed below: -
LSB -“1” =emergency stop has been activated
-“1” =a drain fault
19