iii)
AdvDewpoint
The outlet dewpoint from the dryer bank will be returned in milliCelsius.
This will automatically be updated when a node status broadcast message
is received.
iv)
AdvPressure
The inlet pressure to the dryer bank will be returned in millibar (gauge).
This will automatically be updated when a node status broadcast message
is received.
v)
AdvStatus
A text string relating to the dryer status is displayed. A list of the status text
strings is given in <DHPNDRL1V3_3.cod> under [STATUS]. This will
automatically be updated when a node status broadcast message is
received.
vi)
AdvStatusRegister
Requests a summary of the system status, each bit of the returned 8-bit
binary number represents a particular System Status Message, as listed
below: -
LSB -“1” =dryer ONLINE and cycling, “0” =dryer in STANDBY
-“1” =FAULT SHUTDOWN for safety reasons
-“1” =FAULT SHUTDOWN on dewpoint
-“1” =FAULT SHUTDOWN on pressure
-“1” =FAULT SHUTDOWN on temperature
-“1” =WARNING ACTIVE
-“1” =START INHIBIT
MSB -“1” =SERVICE WARNING
Example of Command Messages - Pneudri Electronic V3.3
N.B.All the command (Cmd) items (except Start) listed below can
be performed via the dryer Control Panel when the dryer is
configured for REMOTE CONTROL.
Only the EnergyReset command can be performed remotely when the
dryer is configured for LOCAL CONTROL.
Selection of remote or local control is via the 2-position key switch
(see section 4.5.1)
17