The OEM750X has one dedicated fault output
.
This output
may be used to signal peripheral devices if an OEM750X
failure occurs. The Fault output's default state is logic high. If
a fault occurs, internal circuitry energizes the transistor’s
base, pulling the output low. The figure represents a typical
configuration of this output.
Internal Connections
• Minimum high level output: 5V
• Maximum low-level output: 0.8V
• Output can sink up to 50mA
from the load
Dedicated Fault Output
BS170
8
9
10
11
12
13
+5V
4.75K
Ω
External Devices
Dedicated Fault Output
S
EQUENCE
I
NPUTS
#1 – #3 (P
INS
11 – 13)
The OEM750X has three dedicated sequence inputs that allow
you to control seven different sequences. The default active
state is
high
. You must use the
X
commands (particularly the
XP
command) to configure these inputs. Sequence #Ø is not a
valid sequence.
Internal Connections
+5V
4.75K
Ω
HCT244
+5V
4.75K
Ω
HCT244
+5V
4.75K
Ω
HCT244
External Devices
Sequence Input #1
Sequence Input #3
Sequence Input #2
• Maximum low-level input: 0.8V
• Minimum high level input: 2V
7
8
9
10
11
12
13
Normally Closed
Switches
Sequence Inputs