38 - PVD 3661 MGV_ commisionning manual_March 2012.docx
Colour codes are as follow:
Signal
Colour
U
black
V
white
W
red
Earth
green/yellow
Thermal sensor KTY84-130 (+)
Brown
Thermal sensor KTY84-130 (-)
White
Thermal protector PTC 150°C
yellow
Thermal protector PTC 150°C
yellow
4.4. Maintenance Operations
Generality
DANGER:
The installation, commissioning and maintenance operations must be performed
by qualified personnel, in conjunction with this documentation.
The qualified personnel must know the safety (C18510 authorization, standard VDE 0105 or
IEC 0364) and local regulations.
They must be authorized to install, commissioning and operate in accordance with
established practices and standards.
Please contact PARKER for technical assistance.
Operation
Periodicity
Section number
Vibration and bearings temperature checking
Every 3000h
§3.4.7
Alignment checking
Every year
§4.2.4
Cooling water quality inspection
Every year
§3.6
Check all tightening torques on all screws in
the terminals box
Every year
§4.2
Clean the motor
Every year