23 - PVD 3661 MGV_ commisionning manual_March 2012.docx
3.6.3.
MGV servomotors are cooled by water. An anti-corrosion product must be mixed to the water. The main
characteristics of cooling are given in the table bellow:
Motor cooling circuit data and chiller selection
Chiller must be able to evacuate motor power loss (see table above).
Chiller pump must provide water flow through motor and pipe pressure drop.
Inlet temperature must be inferior to 25°C.
You can find various chillers solutions in Parker Hiross -
Motor
Average flow
necessary
for cooling
(with water +
25% glycol)
Maxi drop
pressure
@
nominal
water
flow
Motor power
losses at max
speed and
continuous
operation
Series Hyperchill type ICE
Chiller
Power
dissipation
capability
Flowrate
capability
l/min
Bars
kW
kW
l/min
MGV420
2
3 maxi
0,75
ICE003
2
5.8
MGV430
3
1,1
MGV620
3
1,2
ICE003
2
5.8
MGV635
5
1,8
ICE005
4.2
12.16
MGV820
5
1,7
ICE005
4.2
12.16
MGV840
10
5
ICE010
7.4
21.3
MGV930
10
4
ICE007
5.7
16.5
MGV950
16
6,4
ICE010
7.4
21.3
MGV970
22
12
ICE022
17.8
51.16
MGVA30
18
6
ICE010
7.4
21.3
MCVA50
25
10
ICE015
11
31.5