English
7 / 8
ICEP002-005
4.9 Alarm/Warning history
ALHi
HySP
esc
set
Y
esc
set
Y
Y
0
1
2
set
HySP
HySC
04
18.06
HySd
HySt
13.46
HyS1
28
set
Y
Y
Y
esc
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
esc
Y
set
Y
esc
Y
Y
set
Y
esc
Y
Y
set
Y
esc
Y
Y
set
Y
Menu
Code
DESCRIPTION
ALHi
HySP
Alarm number
HySC
See alarm code
HySd
See day and month of the alarm
(if the clock option is present)
HySt
See hour and minutes of the alarm
(if the clock option is present)
HyS1
b1 temperature at time of the alarm
HyS2
b2 temperature at time of the alarm
HyS3
SET conditions at time of the alarm
Press the button “
set
” to enter in the menu, using the buttons “
”and “
” select the parameter “
ALHi
”.
Press the button “
set
” to enter in the menu, using the buttons “
”and “
” select the parameter “HySP”.
Press the button “
set
” to enter in the menu, using the buttons “
”and “
” select the alarm number insert (0,1,2......39) and confi rm
with “
set
” (the number 0 is the last alarm started) .
“HySP” appears again, press “
set
” to enter and see the date of the
alarm: “HySC” code (es:HP), “HySd” Date (day, month), “HySt” hour
(hour, minutes), “HyS1” “HyS2” “HyS3” sensor b1, b2 and set when the
alarm occurred.
Press “
esc
” to exit.
4.10 Automatic restart
In the event of a power failure, when power is restored the chiller will
assume the On-Off status held at the moment the power was lost.
5 Maintenance
a) The machine is designed and built to guarantee continuous opera-
tion; however, the life of its components depends on the mainte-
nance performed.
b) When requesting assistance or spare parts, identify the machine
(model and serial number) by reading the dataplate located on the
unit.
(www.polewr.com.
)
5.1 General instructions
!
Before performing any maintenance, make sure the power to the
refrigerator is disconnected.
Y
Always use the Manufacturer’s original spare parts: otherwise the
Manufacturer is relieved of all liability regarding machine malfunction-
ing.
Y
In case of refrigerant leakage, contact qualifi ed and authorized
personnel.
Y
The Schrader valve must only be used in case of machine mal-
function: otherwise any damage caused by incorrect refrigerant charg-
ing will not be covered by the warranty.
5.2 Preventive maintenance
To guarantee lasting maximum chiller effi ciency and reliability, carry out:
a)
Z
every 6 months -
clean the condenser fi ns and make sure
compressor electrical absorption is within the dataplate values;
b)
Z
kit for maintenance
(par.7.5)
• kit for maintenance;
• service kit;
• individual spare parts.
5.3 Refrigerant
Z
Charging: any damage caused by incorrect charging carried out
by unauthorized personnel will not be covered by the warranty.
Y
The equipment contains fl uorinated greenhouse gases.
At normal temperature and pressure, the R407C refrigerant is a colour-
less gas classifi ed in SAFETY GROUP A1 - EN378 (group 2 fl uid ac-
cording to Directive PED 2014/68/EU);
GWP (Global Warming Potential) = 1774.
!
In case of refrigerant leakage, air the room.
5.4 Dismantling
The refrigerant and the lubricating oil contained in the circuit must be
recovered in conformity with current local environmental regulations.
The refrigerant fl uid is recovered before fi nal scrapping of the equip-
ment ((EU) No. 517/2014 art.8).
%
Recycling
Disposal
frame and panels
steel/epoxy resin polyester
tank
aluminium/copper/steel
pipes/collectors
copper/aluminium/carbon steel
pipe insulation
NBR rubber
compressor
steel/copper/aluminium/oil
condensator
steel/copper/aluminium
pump
steel/cast iron/brass
fan
aluminium
refrigerant
R407C (HFC)
valve
brass/copper
electrical cable
copper/PVC
Equipment containing electrical components
must be disposed separately collected with
electrical and electronic waste according to
local and currently legislation.
Summary of Contents for Hyperchill Plus ICEP002
Page 2: ......
Page 130: ...8 8 ICEP002 005 6...
Page 138: ...8 8 ICEP002 005 6...
Page 140: ......
Page 155: ...7 6 Circuit Diagram ICEP002 14 ICEP002 005...
Page 157: ...7 7 Wiring diagram ICEP002 16 ICEP002 005 Sheet 1 6...
Page 158: ...7 7 Wiring diagram ICEP002 17 ICEP002 005 Sheet 2 6...
Page 159: ...7 7 Wiring diagram ICEP002 18 ICEP002 005 Sheet 3 6...
Page 160: ...7 7 Wiring diagram ICEP002 19 ICEP002 005 Sheet 4 6...
Page 161: ...7 7 Wiring diagram ICEP002 20 ICEP002 005 Sheet 5 6...
Page 162: ...7 7 Wiring diagram ICEP002 21 ICEP002 005 Sheet 6 6...
Page 163: ...Wiring diagram ICEP003 005 22 ICEP002 005 Sheet 1 6...
Page 164: ...Wiring diagram ICEP003 005 23 ICEP002 005 Sheet 2 6...
Page 165: ...Wiring diagram ICEP003 005 24 ICEP002 005 Sheet 3 6...
Page 166: ...Wiring diagram ICEP003 005 25 ICEP002 005 Sheet 4 6 Opzione CPT Option CPT...
Page 167: ...Wiring diagram ICEP003 005 26 ICEP002 005 Sheet 5 6...
Page 169: ...Wiring diagram ICEP003 005 28 ICEP002 005 Sheet 1 7...
Page 170: ...Wiring diagram ICEP003 005 29 ICEP002 005 Sheet 2 7...
Page 171: ...Wiring diagram ICEP003 005 30 ICEP002 005 Sheet 3 7...
Page 172: ...Wiring diagram ICEP003 005 31 ICEP002 005 Sheet 4 7...
Page 173: ...Wiring diagram ICEP003 005 32 ICEP002 005 Sheet 5 7...
Page 174: ...Wiring diagram ICEP003 005 33 ICEP002 005 Sheet 6 7...
Page 175: ...Wiring diagram ICEP003 005 34 ICEP002 005 Sheet 7 7...
Page 176: ......