Parker Hi-drive Quick Installation Manual Download Page 5

Parker Hannifin S.p.A. – S.B.C. Division 

 

quick installation guide Hi-drive 

 
 

Page 5 of 12 

 

 

3 WIRING 

CONNECTIONS 

 

• 

Wire up the panel/drive/motor in accordance with the instructions in the operator's manual and applicable 

safety regulations. In case of any doubts, contact our After-Sales Service. 

• 

Check the correct dimensioning of the drive/motor. Compare the rated voltages and currents. 

• 

Make sure the maximum power voltage to terminals L1, L2, L3 does not exceed the specifications (see 

EN60204-1, section 4.3.1) to avoid damaging the drive. 

• 

Make sure the system is properly earthed. 

• 

The user is responsible for the cutout fuses on the AC or DC supply of the converter. 

• 

Be careful of the cable cross sections; refer to the "connections" table and ensure conformity with IEC227-2. 

• 

The cables connected to the drive by means of the terminal board should not be strengthened by soldering 

Sn-Pb (EN60065, art.15.3.5). 

• 

DO NOT remove the power connections from the drive when this is energised. 

• 

After interrupting the power supply and after the converter has been switched off, allow at least 5 minutes to 

pass before disconnecting the motor leads from the drive, as hazardous voltages could persist. 

• 

DO NOT  open the converter. This could be hazardous and immediately invalidate the warranty. 

 

3.1 Protection 

devices 

 

The drive can be connected to an A.C. mains having at most 5kA of short-circuit current and maximum voltage 

of 480V. The drive is without integrated overload protection. 

Table for dimensioning the fuses: 

 

Type of Hi-drive 

Mechanism size 

16 

25 

Fuse size (delayed) on AC mains 

6A rit 

10A rit 

16A rit 

20A rit 

50A rit 

Fuse sizes on control supply VDC 

3.15A 

Instead of the fuses, a thermal magnetic circuit breaker can be used with the same effectiveness as the fuses. 

Table for using ultra fast fuses to UL standards: 

 

fuse type 

Drive type 

HID2 

HID5 HID8 HID16 HID25 

AC mains 

(three fuses) 

Bussmann 

FWP10A14F 

Ferraz-Shawmut 

A70P10-1 

Bussmann 

FWP20A14F 

Ferraz-Shawmut 

A70P20-1 

Bussmann 

FWP30A14F 

Ferraz-Shawmut 

A70P30-1 

Bussmann  

FWP-50B 

Ferraz-Shawmut 

A70P50-4 

Bussmann  

FWP-60B 

Ferraz-Shawmut 

A70P60-4 

Braking 

(two fuses) 

Bussmann 

FWP10A14F 

Ferraz-Shawmut 

A70P10-1 

Bussmann 

FWP20A14F 

Ferraz-Shawmut 

A70P20-1 

Bussmann 

FWP20A14F 

Ferraz-Shawmut 

A70P30-1 

Bussmann 

FWP30A14F 

Ferraz-Shawmut 

A70P30-1 

Bussmann  

FWP-35B 

Ferraz-Shawmut 

A70P35-1 

DC Bus 

(two fuses) 

Bussmann 

FWP10A14F 

Ferraz-Shawmut 

A70P10-1 

Bussmann 

FWP20A14F 

Ferraz-Shawmut 

A70P20-1 

Bussmann 

FWP30A14F 

Ferraz-Shawmut 

A70P30-1 

Bussmann  

FWP-50B 

Ferraz-Shawmut 

A70P50-4 

Bussmann  

FWP-60B 

Ferraz-Shawmut 

A70P60-4 

 

3.2 Wiring 

harness 

 

The motor cable must be shielded. The mains power cables must not necessarily be shielded.  In the case of 

cable chains, cables for mobile installation will have to be chosen.  

Sections table: 

CABLE 

Type of Hi-drive 

Mechanism size 

HID2 

HID5 HID8 

HID16 

HID25 

Section 

1.5 mm

2

 

(AWG14) 

1.5 mm

2

 

(AWG14) 

2.5 mm

2

 

(AWG12) 

4 mm

2

 

(AWG8) 

6 mm

2

 

(AWG8) 

MOTOR 

(X2 terminal) 

Tightening torque 

0.5 – 0.6 Nm (M3) 

1.2 Nm (M4) 

Section 

2 mm

2

 

(AWG14) 

2 mm

2

 

(AWG14) 

2.5 mm

2

 

(AWG12) 

4 mm

2

 

(AWG8) 

6  mm

2

 

(AWG8) 

MAINS 

(X1 terminal) 

Tightening torque 

0.5 – 0.6 Nm (M3) 

1.2 Nm (M4) 

Section 

0.22 

$

 1 mm

2

 (AWG16) 

Signal 

(X5 terminal) 

Tightening torque 

0.22 – 0.25 Nm (M2) 

Section 1 

mm

2

 (AWG16) 

Parking brake  

Tightening torque 

0.5 – 0.6 Nm (M3) 

Maximum length of motor cables 

60 m 

Max cable capacity 

< 150 pF/m 

The 

RESOLVER

 cable features 4 x 0.22 mm

pairs of minimum section, twisted and shielded  individually plus 

general shielding. The lead-lead capacity for the length used must not exceed 10nF. The max acceptable length is 

60 m

The 24V= power supply must be 

dedicated to the drive only

, and not shared with other devices (contactors, 

brake relays, solenoid valves, etc.). Prefer a shielded cable. 
The cables used for analogue signals (

minimum section 0.22 mm

2

) must feature twisted and shielded pairs. 

Also use shielded cables for the digital inputs and outputs. 

Summary of Contents for Hi-drive

Page 1: ...Hi drive Quick installation guide rev 0 November 2004 software rel 0...

Page 2: ...or the protective connection PE European countries see EN61800 5 1 section 4 2 5 4 2 USA see National Electrical Codes NEC National Electrical Manufacturers Association NEMA and local bulging codes Th...

Page 3: ...wer Pout W See diagrams Overvoltage cutout OV Vovl V 870 Undervoltage cutout UV Vund V 70 2 Vmains CONTROL D C power supply Vcc V 24 0 10 Maximum ripple Vcc ripple V Do not exceed range Max power inpu...

Page 4: ...ir entering the converter must not come from or pass through other heat source parts Fit a suitable ventilation filter inside the switchboard 2 3 DIMENSION size HID2 5 8 HID16 25 A 87mm 122mm Measurem...

Page 5: ...ype HID2 HID5 HID8 HID16 HID25 AC mains three fuses Bussmann FWP10A14F Ferraz Shawmut A70P10 1 Bussmann FWP20A14F Ferraz Shawmut A70P20 1 Bussmann FWP30A14F Ferraz Shawmut A70P30 1 Bussmann FWP 50B Fe...

Page 6: ...drive is in RUN mode flashing with interval between the 2 series of flashes the converter is disabled and an alarm has tripped the tripped alarm can be identified by counting the number of flashes be...

Page 7: ...on 6 EIN C 7 N C 7 0VF 8 N C 8 SHIELD 9 0V F 9 5V F X10 encoder output DB9 male X11 CAN DB9 male 1 EOUT A 1 N C 2 EOUT A 2 CANL 3 EOUT B 3 GND CAN 4 EOUT B 4 Reserved 5 EOUT C 5 SHIELD 6 EOUT C 6 Rese...

Page 8: ...Before entering the motor data parameter Pr31 must be defined write 0 for brushless motor default or 1 for asynchronous motor 7 Resolver When the resolver is connected do not use the Less Wiring enc...

Page 9: ...open loop is regulated To the in encoder connector a fixed isolated voltage of 5V is available 8 1 Encoder connection Refer to the diagrams in the Operator s Manual at website www sbcelettronica com...

Page 10: ...Connect the motor to the converter carefully following the manual diagrams 2 Make sure the converter is disabled 3 Start the converter 4 Make sure no alarm has tripped 5 Set the analogue reference at...

Page 11: ...ion see PicoPLC program 8 Auxiliary alarm Depends on application see PicoPLC program 10 Check sum PLC Set the default parameters save switch back on and reprogramme the drive 11 Check sum param Set th...

Page 12: ...MI HI 00 11 04 EN...

Reviews: