background image

Refrigerating Specialties Division

1

ELECTRONIC LIQUID
LEVEL CONTROL

Type ELL-1, ELL-2 and ELL-3

FOR AMMONIA, R-12, R-22, R-502

FEATURES

• Level indicated by Digital Read Out and Bar Chart

Display (LED)

• Calibration not affected by loss of power

• Up to five separate switching functions

• Field-replaceable relays, with 10 amp contacts

• Mix and Match Controller and Probe Assemblies

• Potted Probe Circuit Board

• 120/240 V, 60 Hz or 110/220 V, 50 Hz Power

• Refrigerant Temperature range:

-150° to 212° F (-100° to 100° C)

• Maximum Rated Pressure for Probe Assembly:

450 psig (31 bar)

• No moving mechanical parts

• 4-20 ma Output Signal

• Water resistant Q/D (Quick Disconnect) at Probe

BULLETIN 61-20D

Type ELL

February 1996

Installation, Service and Parts Information

Fig.1

Description

The Type ELL Electronic Liquid Level Control consists of four parts: a
Controller, a Probe Assembly, an Interconnecting Cable and a Pipe
Column Fitting. (See Fig. 1) There are three versions: ELL-1 for one
control level, ELL-2 for one control level plus one high and one low
level auxiliary switching operation, and ELL-3 for one control level
plus two high and two low levels of auxiliary switching operations.

The Probe Assembly measures a change in capacitance due to the
changing liquid level and the Controller converts this into an electrical
signal which then operates a self-contained relay(s).

All adjustments for level set-points are made at the Controller which
is installed remotely from the Probe Assembly. The liquid level is shown
on the face of the Controller by means of a Digital/Bar Graph Display
which is calibrated from 0 to 100 per cent of the active probe length.

The probe which is available in six different lengths will work with
R-717, R-12, R-22 or R-502, The interconnecting cable between the
Controller and the Probe Assembly can be as long as 5000 ft. (1524
M), although when purchased as a complete package with controller
and probe, a 30 ft. (11 M) cable will be supplied.

Purpose

The Type ELL Electronic Liquid Level Control is used to provide
electrical switching action in response to a change in refrigerant liquid
level. The point(s) of level control action are remotely adjusted. This
device can be used with refrigerants R-717, R-12, R-22 or R-502. It is
not effected by specific gravity. It may be used with liquid temperatures
in a range of -150° to 212°F (-100° to 100°C).

One Type ELL can replace as many as five Type LL Float Switches on
a vessel. It can be used to control and maintain the liquid level in
flooded surge drums, flooded shell and tube chillers, high and low
pressure receivers, intercoolers, transfer vessels and various kinds
of accumulators, including recirculating (liquid overfeed) types.

The Type ELL can also be used to activate or deactivate electrical
controls, to energize or de-energize magnetic starters controlling

050342

I S O   9 0 0 1   C E R T I F I E D

Summary of Contents for ELL-1

Page 1: ...a self contained relay s All adjustments for level set points are made at the Controller which is installed remotely from the Probe Assembly The liquid level is shown on the face of the Controller by...

Page 2: ...e installed as shown in Fig 2 The position and orientation of the column must be appropriate to the specific application and installation criteria The Pipe Column must always be in a vertical position...

Page 3: ...Refrigerating Specialties Division 3...

Page 4: ...Refrigerating Specialties Division 4 Parker Hannifin Corporation Refrigerating Specialties Division 2445 South 25th Avenue Broadview IL 60155 3891 Telephone 708 681 6300 Fax 708 681 6306...

Page 5: ...the power sources listed above but it is necessary to BE SURE THE SHUNT PLUG ABOVE TB3 IS IN THE CORRECTION POSITION With the Shunt Plug in the left hand position 120 VAC is revealed at the right hand...

Page 6: ...Refrigerating Specialties Division 6...

Page 7: ...level LOWERS to set point de energized on rise ELL R3 Can be set to activate at any level from 0 100 Differential fixed at approximately 4 Relay energized as liquid level RISES to set point de energi...

Page 8: ...Refrigerating Specialties Division 8 Electronic Liquid Level Kits 204643...

Page 9: ...NG OPERATING LEVEL The Level Control operates one relay with the ability to adjust its differential to as much as 98 or as little as 2 of its HIGH LEVEL SETTING Each Auxiliary Switch also operates one...

Page 10: ...Refrigerating Specialties Division 10...

Page 11: ...efect in workmanship and materials for a period of one year from date of shipment from the factory This warranty is in force only when these products are properly installed field assembled maintained...

Page 12: ...he left of the LED Digital display The chip that converts the incoming voltage to a signal for the Bar Graph has malfunctioned Replace Display Board Assembly part number 203393 Safe Operation See Also...

Reviews: