Typical Applications

The ELL-1 Controller is for single level control. It can be field adjusted
to operate the SPDT relay at any two points along 100% of the active
probe length. Those level set-points might be at 48% and 52% for a
typical accumulator, or at 10% and 90% for a typical dump tank or
transfer vessel.

The ELL-2 has three levels of operation: the high and low level auxiliary
switches can be used to shut down a system, or to sound a warning;
the middle level is the same as described for the ELL-1.

The ELL-3 has five levels of operation. The middle level is the same
as for the ELL-1 and the ELL-2, with “On-Off” control of the liquid
level, plus the ELL-3 has two high level and two low level auxiliary
switches. All four of these auxiliary switches may be set at any suitable
height. A typical application would utilize the middle switch to control
operating level on a pumped liquid recirculation package. The two
high level auxiliary switches could be wired to sound an alarm prior to
shutting down the compressor. Low level auxiliary switches could
further be wired to sound an alarm prior to shutting off a pump.

Each of the high and low level auxiliary switches have a 4% differential
built-in to eliminate nuisance cycling.

Warranty

All Refrigerating Specialties Products are warranted against defect in
workmanship and materials for a period of one year from date of
shipment from the factory. This warranty is in force only when these
products are properly installed, field assembled, maintained and
operated in use and service as specifically stated in Refrigerating
Specialties Catalogs or Bulletins for normal refrigeration applications,
unless otherwise approved in writing by Refrigerating Specialties
Division. Defective products, or parts thereof, returned to the factory
with transportation charges prepaid and found to be defective by factory
inspection will be replaced at Refrigerating Specialties option, free of
charge, F.O.B. factory. Warranty does not cover products which have
been altered or repaired in the field, damaged in transit, or have
suffered accidents, misuse, or abuse. Products disabled by dirt, or
other foreign substances will not be considered defective.

THE EXPRESS WARRANTY SET FORTH ABOVE CONSTITUTES
THE ONLY WARRANTY APPLICABLE TO REFRIGERATING
SPECIALTIES PRODUCTS, AND IS IN LIEU OF ALL OTHER
WARRANTIES, EXPRESSED OR IMPLIED, WRITTEN OR ORAL,
INCLUDING ANY WARRANTY OF MERCHANTABILITY, OR FITNESS
FOR A PARTICULAR PURPOSE. No employee, agent, dealer or other
person is authorized to give any warranties on behalf of Refrigerating
Specialties, nor to assume, for Refrigerating Specialties, any other
liability in connection with any of its products.

P

Probe

24”

36”

48”

72”

96”

120”

`

Length

(61.0 cm)

(91.4 cm)

(121.9 cm)

(182.9 cm)

(243 cm)

(304 cm)

T

Total

30”

42”

54”

78”

102”

126”

Length

(76.2 cm)

(106.7 cm)

(137.2 cm)

(198.1 cm)

(259 cm)

(320 cm)

Summary of Contents for ELL-1

Page 1: ...a self contained relay s All adjustments for level set points are made at the Controller which is installed remotely from the Probe Assembly The liquid level is shown on the face of the Controller by...

Page 2: ...e installed as shown in Fig 2 The position and orientation of the column must be appropriate to the specific application and installation criteria The Pipe Column must always be in a vertical position...

Page 3: ...Refrigerating Specialties Division 3...

Page 4: ...Refrigerating Specialties Division 4 Parker Hannifin Corporation Refrigerating Specialties Division 2445 South 25th Avenue Broadview IL 60155 3891 Telephone 708 681 6300 Fax 708 681 6306...

Page 5: ...the power sources listed above but it is necessary to BE SURE THE SHUNT PLUG ABOVE TB3 IS IN THE CORRECTION POSITION With the Shunt Plug in the left hand position 120 VAC is revealed at the right hand...

Page 6: ...Refrigerating Specialties Division 6...

Page 7: ...level LOWERS to set point de energized on rise ELL R3 Can be set to activate at any level from 0 100 Differential fixed at approximately 4 Relay energized as liquid level RISES to set point de energi...

Page 8: ...Refrigerating Specialties Division 8 Electronic Liquid Level Kits 204643...

Page 9: ...NG OPERATING LEVEL The Level Control operates one relay with the ability to adjust its differential to as much as 98 or as little as 2 of its HIGH LEVEL SETTING Each Auxiliary Switch also operates one...

Page 10: ...Refrigerating Specialties Division 10...

Page 11: ...efect in workmanship and materials for a period of one year from date of shipment from the factory This warranty is in force only when these products are properly installed field assembled maintained...

Page 12: ...he left of the LED Digital display The chip that converts the incoming voltage to a signal for the Bar Graph has malfunctioned Replace Display Board Assembly part number 203393 Safe Operation See Also...

Reviews: