Refrigerating Specialties Division

7

Schematic Notes (Fig. 5):

1. This “typical” drawing is conceptual, and is not intended for use

as an installation or design drawing. R/S assumes no
responsibility for any implementation of the details or concepts
reflected by this drawing.

2. Wiring shown in dash-line box integral to ELL-3 Controller. All

other wiring installed in field, to suit application and design.

3. No attempt made herein to isolate control circuits, define location

of enunciators or pilot lights, distinguish between enclosures,
etc. All applicable codes to be observed.

4. CONTROLLER RELAY FUNCTION, DISPOSITION

All relays shown in de-energized (normal) position.  All LED -pilots
on ELL energized when relays are energized.

ELL-R1: Operating liquid level, adjustable differential, can be

set to any liquid level or differential, energized as liquid
level drops to lower level setting, de-energized when
liq

uid level rises to upper level setting.

ELL-R2:

C

an be set to activate at any level from 0 - 100%.

Differential fixed at approximately 4%. Relay energized
as liquid level LOWERS to set point; de-energized on
rise.

ELL-R3: Can be set to activate at any level from 0 - 100%.

Differential fixed at approximately 4%. Relay energized
as liquid level RISES to set-point; de-energized on fall.

ELL-R4: Can be set to activate at any level from 0 - 100%.

Differential fixed at approximately 4%. Relay energized
as liquid level LOWERS to set-point; de-energized on
rise.

ELL-R5: Can be set to activate at any level from 0 - 100%.

Differential fixed at approximately 4%. Relay energized
as liquid level RISES to set-point; de-energized on fall.

5. Alternative applications and logic supported by employing

combinations of ELL relays and additional control relays are
infinite. Transfer systems, intercoolers, chillers, and others will
require their own specific control circuit designs.

Specifications

Power Required

Liquid Temperature Range

Probe Head

Storage Temperature

120/240V 60 Hz

-150° to 212° F

Max. Rated Pres. (MRP)

Range (all parts)

110/220V 50 Hz

-100° to 100° C

450 psig (31 bar)

-55° to 165° F

10VA

-48° to 74° C

Controller Enclosure

Controller Ambient Temp. Range

Probe Cable Voltage

Relay Contact Rating

NEMA 4X (Outdoor use)

-22° to 122° F

Max. 15 V DC

10amps120VSPDT

-30° to 50° C

Probe Head

Probe Head Enclosure

Ambient Temp. Range

Outdoor use

-50° to 131° F

-46° to 55° C

Summary of Contents for ELL-1

Page 1: ...a self contained relay s All adjustments for level set points are made at the Controller which is installed remotely from the Probe Assembly The liquid level is shown on the face of the Controller by...

Page 2: ...e installed as shown in Fig 2 The position and orientation of the column must be appropriate to the specific application and installation criteria The Pipe Column must always be in a vertical position...

Page 3: ...Refrigerating Specialties Division 3...

Page 4: ...Refrigerating Specialties Division 4 Parker Hannifin Corporation Refrigerating Specialties Division 2445 South 25th Avenue Broadview IL 60155 3891 Telephone 708 681 6300 Fax 708 681 6306...

Page 5: ...the power sources listed above but it is necessary to BE SURE THE SHUNT PLUG ABOVE TB3 IS IN THE CORRECTION POSITION With the Shunt Plug in the left hand position 120 VAC is revealed at the right hand...

Page 6: ...Refrigerating Specialties Division 6...

Page 7: ...level LOWERS to set point de energized on rise ELL R3 Can be set to activate at any level from 0 100 Differential fixed at approximately 4 Relay energized as liquid level RISES to set point de energi...

Page 8: ...Refrigerating Specialties Division 8 Electronic Liquid Level Kits 204643...

Page 9: ...NG OPERATING LEVEL The Level Control operates one relay with the ability to adjust its differential to as much as 98 or as little as 2 of its HIGH LEVEL SETTING Each Auxiliary Switch also operates one...

Page 10: ...Refrigerating Specialties Division 10...

Page 11: ...efect in workmanship and materials for a period of one year from date of shipment from the factory This warranty is in force only when these products are properly installed field assembled maintained...

Page 12: ...he left of the LED Digital display The chip that converts the incoming voltage to a signal for the Bar Graph has malfunctioned Replace Display Board Assembly part number 203393 Safe Operation See Also...

Reviews: