28
DeviceNet Communications Interface
INTEGER Type Connector
Data from PLC
Data to 890
From BOOL to INTEGER
False
True
0x0000 0000
0x0000 0001
From SINT to INTEGER
-128 to 127
-128 to 127
From INT to INTEGER
-32,768 to 32,767
-32,768 to 32,767
From DINT to INTEGER
-2,147,483,648 to
2,147,483,547
-2,147,483,648 to
2,147,483,547
From USINT to
INTEGER
0 to 255
0 to 255
From UINT to INTEGER
0 to 65,535
0 to 65,535
From UDINT to
INTEGER
0 to 4,294,967,295
0 to 2,147,483,647
limits apply
From REAL to INTEGER
32-bit IEEE floating-point
-2,147,483,648 to
2,147,483,547
Fractional part rounded
Data from 890
Data to PLC
From INTEGER to BOOL
Zero
Non-zero
True
False
From INTEGER to SINT
-2,147,483,648 to
2,147,483,647
-128 to 127
limits apply
From INTEGER to INT
-2,147,483,648 to
2,147,483,647
-32768 to 32767
limits apply
From INTEGER to DINT
-2,147,483,648 to
2,147,483,647
-2,147,483,648 to
2,147,483,647
From INTEGER to
USINT
-2,147,483,648 to
2,147,483,647
0 to 255
limits apply
From INTEGER to UINT
-2,147,483,648 to
2,147,483,647
0 to 65,535
limits apply
From INTEGER to
UDINT
-2,147,483,648 to
2,147,483,647
0 to 2,147,483,647
limits apply
From INTEGER to REAL
-2,147,483,648 to
2,147,483,647
32-bit IEEE floating-point