19
DeviceNet Communications Interface
Click OK.
4.
Download the completed configuration into the PLC, ensure that the PLC is in the PROG
mode. For example, the SLC-500 has a keyswitch to select this. Then go online to the
DeviceNet network by clicking the Online button:
The system will scan the online network and add a status flag against each device as
appropriate. From the Network menu, select Download to Network. Confirm this when
prompted and then the status indicator will show download progress:
When the download is complete, the PLC will save the new configuration. Now switch the
PLC to RUN mode. Data will start being transferred between PLC and drive. Configuration
of the scanner is now complete.