Parker 8903/DN Technical Manual Download Page 19

13

 

DeviceNet Communications Interface 

 

3.

 

Click in the 

Type

 field to choose the required PLC type on Register 1, for example. 

 

4.

 

Set up all the input/output registers in a similar way. 

5.

 

Right click on a row to insert, move or delete a register. 

6.

 

The Baudrate can be selected to be 125k, 250k or 500k.  

7.

 

The MAC Id can be selected in the range 0 – 125. 

  NOTE 

 

The Baudrate and MAC Id set in DSE will only be used if all the switches on the 

DeviceNet Option are set to ON. 

If the software set MAC Id is set to zero and the switches on the DeviceNet Option are all 

set to ON, the option is disabled and will not appear on the DeviceNet network. 

DSE Data Types 

Data Type 

Description 

Range 

LOGIC 

Logic 

False (F) and True (T) 

INTEGER 

32-bit signed integer  

-2,147,483,648 to 2,147,483,647 

VALUE 

32-bit fixed point value  

-32768.0 to 32767.9999 

DeviceNet PLC Data Types 

Data Type 

Description 

Range 

PLC Size  

BOOL 

8-bit Boolean 

False (0x00) and True (0x01) 

1 byte 

SINT 

8-bit signed integer 

-128 to 127 

1 byte 

INT 

16-bit signed integer 

-32,768 to 32,767 

2 bytes 

DINT 

32-bit signed integer 

-2,147,438,648 to 2,147,483,647 

4 bytes 

USINT 

8-bit unsigned integer 

0 to 255 

1 byte 

UINT 

16-bit unsigned integer 

0 to 65,535 

2 bytes 

UDINT 

32-bit unsigned integer 

0 to 4,294,967,295 

4 bytes 

REAL 32-bit 

IEEE-754 

floating-point value 

1.19209290e-38 to 
3.438  

4 bytes 

Conversion of DSE Type < > DeviceNet Type 

The DSE fieldbus connectors are each assigned a DeviceNet PLC "Type" as described in "Step 
1.3: Configuring the Fieldbus Connectors" on page 12. The conversion between the DSE type 
and the PLC type is performed automatically (refer to Appendix B : DSE/DeviceNet Conversion 
Rules, page 26). 

Any PLC type can be assigned to a fieldbus connector  

Summary of Contents for 8903/DN

Page 1: ...nt it may be necessary without notice to make amendments or correct omissions Parker Hannifin ltd Automation Group SSD Drives Europe cannot accept responsibility for damage injury or expenses resultin...

Page 2: ...all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the application follow applicable industry standards and follow th...

Page 3: ...for your own information Unit used as a refer to Certification for the Inverter Component Relevant Apparatus Unit fitted Wall mounted Enclosure Application Area The equipment described is intended for...

Page 4: ...or the product s operation are correctly installed All control and signal terminals are SELV i e protected by double insulation Ensure all external wiring is rated for the highest system voltage Therm...

Page 5: ...hing Fieldbus Connectors 11 Step 1 3 Configuring the Fieldbus Connectors 12 DSE Data Types 13 DeviceNet PLC Data Types 13 Conversion of DSE Type DeviceNet Type 13 DeviceNet Status Information 14 Step...

Page 6: ......

Page 7: ...a rates supported 125k 250k and 500k baud Up to 255 polled or explicit DSE input registers Up to 255 polled cyclic or explicit DSE output registers Product Order Code Not fitted order code 8903 DN 00...

Page 8: ...h Options fitted Installation To Remove the Control Board 1 Remove the blanking plates each secured by a single screw 1 that fits over the option slots 1 2 Loosen the top and bottom screws from the ha...

Page 9: ...s shown The legs of the connector will protrude through into the connector on the other side of the Option 2 Press the assembly into the TOP connector adjacent to terminals X13 X14 and X15 on the Cont...

Page 10: ...slots Push until the back edge of the Control Board PCB locates with the connectors in the drive 2 Tighten in position using the top and bottom screws in the handles of the Control Board 3 Screw the...

Page 11: ...r 24 Blue white Power wires Twisted pair 15 Black red Twisted pair 22 Black red Shield Foil braid with drain wire 18 bare Each pair shielded separately in aluminized mylar Combined pair shielded Foil...

Page 12: ...ould be chosen to equal as closely as possible the characteristic impedance of the cable Important Failing to fit terminating resistors correctly may result in unreliable operation For more informatio...

Page 13: ...on MAC ID and Baud Rate are set by software If the DSE DeviceNet function block is instantiated then this has precedence over the MMI 8903 DN Front View DIP Switch Binary Value Function Example 1 25 0...

Page 14: ...t of the DeviceNet Option or set by the DNET block in the DSE configuration Note if the MAC ID is zero the connection to the network is disabled CONNECTION STATE Read only Range Enumerated see below T...

Page 15: ...witches Enumerated Value HARDWARE 0 FALSE Baudrate set by DSE configuration 1 TRUE Baudrate set by hardware BAUDRATE SOFT Read only Range Enumerated see below The Baudrate set by software i e the DSE...

Page 16: ...using DSE Step 1 1 Inserting a DeviceNet Function Block Display your configuration page Click on the Block menu at the top of the screen 1 Move the cursor down to select 890 Comms and select DeviceNe...

Page 17: ...lue Output FB Val to Int Output Input connector the data is sent from PLC 890 Output connector the data is sent from 890 PLC The fieldbus connectors must be added before they will appear in the Device...

Page 18: ...plicit An Output may be configured to be either Polled COS Cyclic or Explicit To configure the input and output connectors you have placed in the configuration 1 Click on above the list that the Input...

Page 19: ...o 2 147 483 647 VALUE 32 bit fixed point value 32768 0 to 32767 9999 DeviceNet PLC Data Types Data Type Description Range PLC Size BOOL 8 bit Boolean False 0x00 and True 0x01 1 byte SINT 8 bit signed...

Page 20: ...to the MAC Id set in the function block configuration if the switches on the Option have set the Address The function block also provides two status outputs that can be wired to CONN STATUS and DEV ST...

Page 21: ...manufacturer s instructions 1 Import the EDS file and graphic icon for the 890 using the RSNetWorx EDS Wizard These files to select are dn_890 eds dn_890 ico and can be downloaded from www ssddrives...

Page 22: ...16 DeviceNet Communications Interface Make a connection between the scanner and the drive Double click on the icon for the scanner node Now click on the Scanlist tab...

Page 23: ...h can be connected The right hand window shows a list of devices currently connected To connect the 890 drive at at address 05 select it as shown and then click The 890 drive moves to the right hand w...

Page 24: ...EDS file selects Polled I O with 8 Input bytes and 5 Output bytes This needs to be change to what is required For example if Polled I O is required with just 2 Output bytes then enter as below Click O...

Page 25: ...e Online button The system will scan the online network and add a status flag against each device as appropriate From the Network menu select Download to Network Confirm this when prompted and then th...

Page 26: ...sponse is an I O message that the Slave transmits back to the master when the Poll Command is received Within the Slave the two messages are received transmitted by a single Connection Object It can b...

Page 27: ...Byte Parameter Data Format 0 1 2 3 REFERENCE REMOTE SETPOINT PREF 101 01 IEEE 754 32 bit floating point 4 REFERENCE REVERSE PREF 101 11 0x00 FALSE 0x01 TRUE Polled Outputs size 8 bytes Byte Parameter...

Page 28: ...the mode and cycle time are defined by the PLC The 890 supports a single Assembly Object for COS Cyclic Output This is configured using DSE The example above defines an Assembly Object consisting of...

Page 29: ...68 Cyclic Outputs 0x64 100 Fixed Parameter Set Object 0x01 to 0xFF 1 to 255 0x01 to 0x1F 1 31 Fixed Parameter Set of the 890 drive Instance Block ID Attribute Parameter Number 0x65 101 User Defined Re...

Page 30: ...is mapped to be a Polled Input Polled Output Cyclic Output Explicit Input or Explicit Output Also its size and encoding are selected The Instance number selects either Input or Output register and th...

Page 31: ...e STRING SSD DRIVES AC8903 DN 8 State USINT 0 1 2 3 4 5 CONNECTION state NON EXISTENT DEVICE SELF TESTING STANDBY OPERATIONAL MAJOR RECOVERABLE FAULT MAJOR UNRECOVERABLE FAULT DeviceNet Object Class 0...

Page 32: ...en ON Red ON Green ON Colour LED Indication Description MODULE LED OFF OFF No Power GREEN ON Device operational GREEN OFF FLASH Device in Stand by RED ON Unrecoverable Fault RED OFF FLASH Recoverable...

Page 33: ...ero Non zero False True From INT to LOGIC Zero Non zero False True From DINT to LOGIC Zero Non zero False True From USINT to LOGIC Zero Non zero False True From UINT to LOGIC Zero Non zero False True...

Page 34: ...bit IEEE floating point 2 147 483 648 to 2 147 483 547 Fractional part rounded Data from 890 Data to PLC From INTEGER to BOOL Zero Non zero True False From INTEGER to SINT 2 147 483 648 to 2 147 483 6...

Page 35: ...it IEEE floating point 32 768 0 to 32 767 9999 Data from 890 Data to PLC From VALUE to BOOL Zero Non zero False True From VALUE to SINT 32 768 0 to 32 767 9999 128 to 127 limits apply rounding applies...

Page 36: ...on and conditions of sale 20358 Photos and screenshots updated Standardised Safety pages over 3 pages Product Code added new coding Replaced TechCard with Option and Replaced DSE 890 with DSE Page 12...

Reviews: