RS485/RS232 Communications Interface
A/18
B/17
120
Ω
RS485
ON
OFF
SW1
Frames 1-3
Frames C-F
RS485 Communications Option (650V Frames C, D, E & F)
You can create a network of drives by linking a Master (PC/PLC) to one or more 650V drives
fitted with this additional 3-way terminal. It is factory-fitted to the right hand side of the control
board.
Signals from the host 650V drive are converted into RS485, and vice versa, so that information
can be shared between the Master and 650V drive(s).
Wiring is very simple - all connections are SELV (Safe Extra Low Voltage).
RS485 Connections
master to single/multiple slave
9-Way / 25-Way
D-Type
PC/PLC
A
B
To PC/PLC
Chassis
A
B
Scn
650V Drive
with
RS485 option
Connector
A
B
Scn
650V Drive
with
RS485 option
Master
PC/PLC
Drive
Drive
Drive
Wiring Specifications
RS485 Connections
Network Type
2-Wire Shielded Twisted-Pair
Connections
A=RxA/TxA, B=RxB/TxB, Scn = Screen (shield)
Signal Levels
To RS485 Standard
Receiver Input Impedance
¼ Unit Load
Maximum Cable Length
1200m (4000ft)
Maximum Baud Rate
57.6kbaud
Maximum Number of Units
32 including slaves and masters
Terminators
The last drive in a system must have a terminating resistance. All other drives in the system
should not have a terminator.
Frames 1-3 drives require a 120
Ω
terminating resistor
fitting to terminals 17 and 18 on the Control Board
(resistor is
±
1%, minimum ¼ Watt).
Frames C-F drives are fitted with an integral resistor,
switched in and out by switch SW1 on the Control
Board.
IMPORTANT:
Failing to use a terminating resistance may result in
unreliable operation.