8
ASCII
RS485/RS232 Communications Interface
PARITY
F
SET\SERL SE05
Range: Enumerated - see below
Selects the Parity for the MODBUS protocol.
Enumerated Value
:
Parity
0 : NONE
1 : ODD
2 : EVEN
REPLY DELAY
F
SET\SERL SE06
Range: 0 to 200
The time in milliseconds between the drive receiving the complete request from the
communications master (PLC/PC) and replying to this request.
OP PORT PROTOCOL
F
SET\SERL SE07
Range: Enumerated - see below
Selects the protocol to be used by the keypad port on the front of the drive. When EIBISYNC
ASCII is selected, BAUD RATE is 19200 and PARITY is EVEN.
Enumerated Value
:
Protocol
0 : AUTOMATIC - checks for keypad or EI ASCII
1 : KEYPAD
2 : EIBISYNC ASCII
3 : MODBUS
4 : FIELDBUS
P3 PORT PROTOCOL
F
SET\SERL SE08
Range: Enumerated - see below
Selects the protocol to be used by the RS232 programming port on the drive's control board.
When EIBISYNC ASCII is selected, BAUD RATE is 19200 and PARITY is EVEN.
Enumerated Value
:
Protocol
0 : AUTOMATIC - checks for keypad or EI ASCII
1 : KEYPAD
2 : EIBISYNC ASCII
3 : MODBUS
4 : FIELDBUS
RS485 PORT PROTOCOL
F
SET\SERL SE09
Range: Enumerated - see below
This parameter is not available on the 650V Frame 1, 2 & 3. For these frame sizes, use
"OP PORT PROTOCOL" to select the protocol for the comms option.
Selects the protocol to be used by the RS485 programming port on the drive's control board.
Enumerated Value
:
Protocol
0 : AUTOMATIC
1 : KEYPAD (not applicable)
2 : EIBISYNC ASCII
3 : MODBUS
4 : FIELDBUS
SWITCH OP PORT
F
SET\SERL SE10
Range: FALSE / TRUE
This parameter is not available on the 650V Frame 1, 2 & 3.
When TRUE, the keypad port on the front of the drive is disabled when the communications
equipment is connected to the RS232 programming port on the drive's control board.
When FALSE, the RS485 programming port is disabled when the communications equipment is
connected to the RS232 programming port. Both ports are on the drive's control board.
SWAP WORD ORDER
Range: FALSE / TRUE
Controls the word order used with 32-bit data access with the Modbus RTU protocol.