MODBUS
43
RS485/RS232 Communications Interface
MODBUS RTU Parameter Mapping
1. MODBUS RTU Prime Set
Mnemonic
Description
Range (HEX values)
Access
9901
Instrument Identity 0650, 1650 or 2650
0650 = 650 Frames 1, 2 & 3
1650 = 650V Frames 1, 2 & 3
2650 = 650V Frames C, D, E & F
Read Only
9902 Main
Software
Version
0000 to FFFF
Read Only
9903 6051
Software
Version
0000 to FFFF
(0000 if not fitted)
Read Only
9904 Comms
Interface
Software Version
0000 to FFFF
Read Only
9908 Bootloader
Software Version
0000 to FFFF
Read Only
9909
Last Tag Number
0000 to FFFF
Read Only
2. Command/Status
Mnemonic
Description
Range (HEX values)
Access
9911 Command
see below (!1)
Write Only
9912
State
see below (!2)
Read Only
9913
Save Command
see below (!3)
Write Only
9914
Save State
see below (!4)
Read Only
!1 : Command
Write-only: used to modify the state of the drive and to load configuration data from
non-volatile memory.
HEX Value Description
7777
Reset Command. Acknowledges failed restore. Loads and saves
default Product Code and default Configuration (Application 1).
0101
Restores Saved Configuration from drive’s non-volatile memory.
0110
Restores Default Configuration (Application 0)
0111
Restores Default Configuration (Application 1)
0112
Restores Default Configuration (Application 2)
0113
Restores Default Configuration (Application 3)
0114
Restores Default Configuration (Application 4)
0115
Restores Default Configuration (Application 5)
4444
Exit Configuration Mode
5555
Enter Configuration Mode
!2 : State
Read-only: used to determine the major state of the drive.
HEX Value Description
0000
Initialising. (Powering up )
0001
Corrupted Product Code and Configuration
0002 Corrupted
Configuration
0003 Restoring
Configuration
0004 Re-Configuring
Mode
0005
Normal Operation Mode
Summary of Contents for 6513