![Parker 650V series Technical Manual Download Page 94](http://html.mh-extra.com/html/parker/650v-series/650v-series_technical-manual_755636094.webp)
9-8
Technical Specifications
650V AC Drive
Electrical Ratings (400V Build Variant)
Power Supply = 380-460V ±10%, 50/60Hz
±
5%
Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Model Number
(Europe)
Catalog Number
(North America)
Motor
Power
Output
Current
(A)
Input
Current
(A)
Heatsink
Power
Loss (W)
Total
Power
Loss
(W)
Maximum
Switching
Frequency
(kHz)
Input
Bridge I
2
t
(A
2
s)
Normal Duty
(Output Overload Motoring 110% for 30s)
650V-432160C
11kW
23
26.1
300
350
3
4000
650V/0010/460/..
15Hp
21
22.1
280
320
3
4000
650V-432230C
15kW
30
33.6
440
500
3
4000
650V/0015/460/..
20Hp
27
28.5
410
470
3
4000
650V-432300C
18.5kW
37
44
550
610
3
6000
650V/0020C/460/..
25Hp
34
38
530
580
3
6000
FRAME D :
Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac
input. Prospective short circuit current 10kA.
* For UL Listed products rated at 30kW/40Hp, a supply voltage of 460V is required. The higher
current ratings are applicable to non UL applications only.
Heavy Duty
(Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650V-432310D
15kW
31
34.8
420
480
3
4000
650V/0020/460/..
20Hp
31
28.5
400
460
3
4000
650V-432380D
18.5kW
38
40.5
545
605
3
6000
650V/0025/460/..
25Hp
38
34.2
515
575
3
6000
650V-432450D
22kW
45
47.2
670
730
3
6000
650V/0030/460/..
30Hp
45
40
640
700
3
6000
650V-432590D
30kW
59
66
760
860
3
15000
650V/0040D/460/..
40Hp
52
56
740
830
3
15000
Normal Duty
(Output Overload Motoring 110% for 30s)
650V-432310D
18.5kW
38
40.5
545
605
3
4000
650V/0020/460/..
25Hp
38
34.2
515
575
3
4000
650V-432380D
22kW
45
47.2
670
730
3
6000
650V/0025/460/..
30Hp
45
40
640
700
3
6000
650V-432450D
30kW
59
61
760
860
3
6000
650V/0030/460/..
40Hp
52
51
740
830
3
6000
650V-432590D
37kW
73
84
920
1030
3
15000
650V/0040D/460/..
50Hp
65
68
890
980
3
15000