![Parker 650V series Technical Manual Download Page 116](http://html.mh-extra.com/html/parker/650v-series/650v-series_technical-manual_755636116.webp)
10-8
Certification for the Drive
650V AC Drive
FRAME E
Terminal acceptance range: 6-1/0 AWG
Model Catalog Code
for North America
Power Input
AWG
Power Output
AWG
Brake Output
AWG
230V Build Variant: 220-240V ±10%
HEAVY DUTY
650V/0030/230/..
2
3
6
NORMAL DUTY
650V/0030/230/..
1/0
1
6
400V Build Variant: 460V ±10%
HEAVY DUTY
650V/0040/460/..
4
4
8
650V/0050/460/..
4
3
6
650V/0060/460/..
3
2
4
NORMAL DUTY
650V/0040/460/..
4
3
8
650V/0050/460/..
3
2
6
650V/0060/460/..
1
1
4
FRAME F
Terminal acceptance range: 2AWG-250kcmil
Model Catalog Code
for North America
Power Input
AWG
Power Output
AWG
Brake Output
AWG
230V Build Variant: 220-240V ±10%
HEAVY DUTY
650V/0040/230/..
1
1
4
650V/0050/230/..
2/0
2/0
3
650V/0060/230/..
3/0
3/0
2
NORMAL DUTY
650V/0040/230/..
2/0
2/0
4
650V/0050/230/..
3/0
3/0
3
650V/0060/230/..
4/0
250kcmil
2
400V Build Variant: 460V ±10%
HEAVY DUTY
650V/0075/460/..
1
1
4
650V/0100/460/..
2/0
2/0
2
650V/0125/460/..
3/0
3/0
1
650V/0150/460/..
4/0
4/0
1
NORMAL DUTY
650V/0075/460/..
2/0
2/0
4
650V/0100/460/..
3/0
3/0
2
650V/0125/460/..
4/0
4/0
1
650V/0150/460/..
4/0
4/0
1