Programming Your Application
6-9
650V AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::TRIP Menu
DISABLE LOOP
Disables LOST I LOOP trip (4-20mA)
0= TRIP ENABLED
1= TRIP DISABLED
1
AIN2 OVERLOAD Disables the overload trip (Terminal 3)
As
S
LOOP
0
DISABLE STALL
Disables STALL trip
As
S
LOOP
0
DISABLE MOTOR
OVERTEMP
Disables the motor thermistor trip
As
S
LOOP
0
INVERSE TIME
Disables the inverse time trip
As
S
LOOP
1
DYNAMIC BRAKE
RESISTOR
Disables the dynamic brake resistor trip
As
S
LOOP
1
DYNAMIC BRAKE
SWITCH
Disables the dynamic brake switch trip
As
S
LOOP
1
SPEED FEEDBACK Disables the speed feedback trip
As
S
LOOP
0
OVERSPEED
Disables the overspeed trip
As
S
LOOP
0
DISPLAY
(KEYPAD)
Disables the display (keypad) trip
As
S
LOOP
0
DC LINK RIPPLE
F
Disables the DC link ripple trip
As
S
LOOP
0
SET::SERL Menu
REMOTE COMMS
SEL
F
Selects the type of remote communications mode:
0 : FALSE, and in REMOTE mode then control is
from the terminals.
1 : TRUE, and in REMOTE mode then control is
from the communications.
0=FALSE
1=TRUE
0
COMMS
TIMEOUT
F
Se
ts the maximum time allowed between
refreshing the COMMS COMMAND parameter.
The drive will trip if this time is exceeded. Set the
time to 0.00 seconds to disable this feature.
0.0 to 600.0s
0.0s
COMMS
ADDRESS
F
The drives identity address.
Note: if set to 0, it will only respond to broadcast
messages.
0 to 255
0
BAUD RATE
F
Selects the Baud Rate for the MODBUS protocol.
0 : 1200
1 : 2400
2 : 4800
3 : 7200
4 : 9600
5 : 14400
6 : 19200
7 : 38400
8 : 57600
4
PARITY
F
Selects the Parity for the MODBUS protocol.
0= NONE
1= ODD
2= EVEN
0
REPLY DELAY ms The time in milliseconds between the drive
receiving the complete request from the
communications master (PLC/PC) and replying to
this request.
0 to 200
5
OP PORT
PROTOCOL
F
Selects the protocol to be used by the keypad port
on the front of the drive. When EIBISYNC ASCII is
selected, BAUD RATE is 19200 and PARITY is
EVEN. FIELDBUS is reserved for future use.
0= AUTOMATIC
1= KEYPAD
2=EIBISYNC ASCII
3= MODBUS
4= FIELDBUS
0