![Parker 650V series Technical Manual Download Page 20](http://html.mh-extra.com/html/parker/650v-series/650v-series_technical-manual_755636020.webp)
Installing the Drive
3-3
650V AC Drive
Through-Panel Mount Product/Application (Frame C)
(Europe: IP2x, USA/Canada: Open Type).
The drive, without the top cover fitted, can be mounted in a suitable cubicle.
J
Control
Heat
Sink
K
L
M
FORCED AIR FLOW
panel
N
P
Figure Chapter 3 -4 Air Clearance for a Through-Panel Mount Product/Application
Model Recognition
Clearances for Through-Panel Mount
Standard Product (mm)
Through-Panel
Dimensions
J
K
L
M
N
P
Frame C
20
15
70
70
Through-Panel Mount
Bracket Assembly (Frame C)
The through-panel kit is available as a separate
item, part number LA465034U003.
Through-panel mounting a drive in a cubicle
allows you to use a smaller cubicle because
much of the heat generated by the drive is
dissipated outside the cubicle.
•
Cut the panel aperture to the dimensions
given in the drawing at the end of this
chapter.
•
Screw the top and bottom brackets to the
drive as shown, torque to 3Nm. When in
position, these complete a mating face for the
panel around the drive.
•
Fit the top and bottom self-adhesive gasket
material to the brackets making sure that the
gasket covers the gap between the bracket
and heatsink along the top and bottom edge
of the drive.
•
Fit a gasket to each side of the drive to
complete the gasket seal. Ensure a complete
seal is made; 2 extra side gaskets are
provided.
•
Offer up the drive to the panel and secure.
Refer to Through-Panel Cutout Details,
page 3-9.
p a n e l