6-10
Programming Your Application
650V AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::SETP Menu
JOG ACCEL TIME As
P
4, for Jog
0.0 to 3000.0s
1.0
JOG DECEL TIME As
P
5, for Jog
0.0 to 3000.0s
1.0
RAMP TYPE
Selects the ramp type
0=LINEAR
1=S
0
S RAMP JERK
Rate of change of acceleration of the curve in units
per second³
0.01 to 100.00 s3
10.00
S RAMP
CONTINUOUS
When TRUE and the S ramp is selected, forces a
smooth transition if the speed setpoint is changed
when ramping. The curve is controlled by the S
RAMP JERK parameter. When FALSE, there is an
immediate transition from the old curve to the new
curve
0=FALSE
1=TRUE
1
MIN SPEED
MODE
Selects a mode to determine how the drive will
follow a reference: Proportional : minimum limit,
Linear : between minimum and maximum.
0=PROP.W/MIN.
1=LINEAR (used by
the 601 product)
0
SKIP FREQUENCY
1
This parameter contains the centre frequency of
skip band 1 in Hz
0.0 to 240.0 Hz
0.0
SKIP FREQUENCY
BAND 1
The width of skip band 1 in Hz
0.0 to 60.0 Hz
0.0
SKIP FREQUENCY
2
This parameter contains the centre frequency of
skip band 2 in Hz
0.0 to 240.0 Hz
0.0
SKIP FREQUENCY
BAND 2
The width of skip band 2 in Hz
0.0 to 60.0 Hz
0.0
AUTO RESTART
ATTEMPTS
Determines the number of restarts that will be
permitted before requiring an external fault reset
0 to 10
0
AUTO RESTART
DELAY
Determines the delay between restart attempts for
a trip included in AUTO RESTART TRIGGERS and
AUTO RESTART T. The delay is
measured from all error conditions clearing
0.0 to 600.0 s
10.0
AUTO RESTART
TRIGGERS
Allows Auto Restart to be enabled for a selection of
trip conditions.
Refer to Chapter 6: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
0x0000 to 0xFFFF
0x0000
AUTO RESTART
T
Allows Auto Restart to be enabled for a selection of
trip conditions.
Refer to Chapter 6: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
0x0000 to 0xFFFF
0x0000
DB ENABLE
Enables operation of the dynamic braking.
0=FALSE
1=TRUE
1
DB RESISTANCE
The value of the load resistance.
1 to 1000
product
code
dependent
DB POWER
The power that the load resistance may continually
dissipate.
0.1 to 510.0 kW
product
code
dependent
DB OVER-RATING Multiplier that may be applied to DB POWER for
power overloads lasting no more than 1 second.
1 to 40
25
TORQUE
FEEDBACK
Shows the estimated motor torque, as a
percentage of rated motor torque.
—
.xx %
—
.xx %
TORQUE LEVEL
This parameter sets the value of load at which AT
LOAD becomes TRUE. AT LOAD is selectable by
the digital inputs. Refer to
S
OP21 and
S
OP31.
100% = rated torque for the motor.
-300.0 to 300.0 %
100.0 %