The Keypad
5-5
650V AC Drive
Hold down the keys opposite:
Power-up the drive, continue
to hold for at least 1 second
hold
Special Menu Features
How To Change a Parameter Value
You can change the values of parameters stored in the
and
menus. Refer to Chapter
6: “Programming Your Application” – Configurable Parameters for further information.
•
View the parameter to be edited and press
to display the parameter’s value.
•
Select the digit to be changed (pressing the
key moves the cursor from right to left).
•
Use the
keys to adjust the value. Hold the key momentarily to adjust the value
marginally, or hold the key to make rapid changes; the rate of change varies with the time
held.
•
Press
to return to the parameter display. The new value is stored.
•
Resetting to Factory Defaults (2-button reset)
Power-up the drive whilst holding the keys as
shown to return to factory default settings.
This loads Application 1. Then press the
key.
Changing the Default Operating Frequency
Power-up the drive whilst holding the keys as
shown to display the Engineers Menu.
IMPORTANT:
This menu contains sensitive parameters
that can dramatically alter the running of
the drive.
This displays parameter
E
0.01. Press the
key to navigate to
E
0.02. Press the
key to
edit the parameter: 0 = 50Hz (default), 1 = 60Hz. Select the required frequency then press the
key.
Power-down the drive. No change has been made to the active configuration at this point. To
save the change to parameter
E
0.02, you must now perform a 2-button reset (as above). Please
note that this will return the drive to its factory default settings for the selected default
frequency.
Hold down the keys opposite:
Power-up the drive, continue
to hold for at least 1 second
HOLD