Operating the Drive
650V AC Drive
Autotuning the Drive
IMPORTANT:
You MUST carry out an Autotune if you intend to use the drive in Sensorless Vector
Mode. If you are using it in Volts/Hz control an Autotune is not necessary.
The Autotune procedure identifies some of the more obscure characteristics about your motor,
and automatically loads them into the drive.
Follow the procedure below to complete the Autotune. When the Autotune is finished, refer to
"Tuning the Drive to Your System", page 4-5.
1 Stationary or Rotating Autotune?
Will the motor spin freely during the Autotune, i.e. not connected to a load?
•
If it can spin freely, use a Rotating Autotune (preferred)
•
If it cannot spin freely, use a Stationary Autotune
Action
Requirements
Rotating Autotune
Preferred method
Spins the motor up to the
maximum speed set by the
user to identify all necessary
motor characteristics
Motor must spin freely
during Autotune
Stationary Autotune
Only used when the motor
cannot spin freely during the
Autotune feature
Motor does not spin during
Autotune. A limited set of
motor characteristics are
identified
You must enter the correct
value of magnetising current
Do not subsequently operate
the drive above base speed
2 Performing the Autotune
AUTOTUNE MODE
0
Select the Autotune operating mode
AUTOTUNE ENABLE
0
Enables the Autotune feature. Refer to
"The Autotune Feature" below.
Performing a Rotating Autotune
Check that the motor can rotate freely in the forward direction. Ensure also that the motor is
unloaded. Ideally, the motor shaft should be disconnected. If the motor is connected to a gearbox
this is ok, provided that there is nothing on the output of the gearbox which could load the
motor.
1.
Set MAX SPEED (
P
2) to the maximum speed at which you will operate the drive in normal
operation. The Autotune will characterise the motor up to 30% above this speed. If you
later wish to run faster than this, you will need to carry out another Autotune.
2.
Set the AUTOTUNE MODE (
S
CL20) parameter to ROTATING (1).
3.
Set AUTOTUNE ENABLE (
S
CL21) to 1 (TRUE), and start the drive. The drive will carry
out a Rotating Autotune, indicated by the Run and Stop led’s flashing on the blank cover
when fitted, or by flashing
on the keypad. This may take several minutes, during
which the motor will be accelerated to maximum speed and then brought to a stop. When
complete, the drive is returned to the stopped condition and the AUTOTUNE ENABLE
parameter is reset to 0 (FALSE).
Performing a Stationary Autotune
Before starting the stationary Autotune, you
MUST
enter the value of magnetising current for
the motor (
S
CL14). This may be available on the motor nameplate. If not, you may need to
contact the motor supplier.
1.
Set the AUTOTUNE MODE (
S
CL20) parameter to STATIONARY (0).
2.
Set AUTOTUNE ENABLE (
S
CL21) to 1 (TRUE), and start the drive. The drive will carry
out a Stationary Autotune, injecting current into the motor but not turning the shaft. The
Run and Stop led’s will flash on the blank cover when fitted, or
will flash on the
keypad. When complete, the drive is returned to the stopped condition and the AUTOTUNE
ENABLE parameter is reset to 0 (FALSE).