![Parker 650V series Product Manual Download Page 44](http://html2.mh-extra.com/html/parker/650v-series/650v-series_product-manual_3741148044.webp)
6-6
Programming Your Application
650V AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
NEG TORQUE
LIMIT
F
This parameter sets the maximum allowed level of
negative motor torque.
-500.0 to 500.0%
-200.0%
STALL TRIP TYPE
F
This parameter determines whether the stall trip
operates on motor torque or motor current.
FALSE = TORQUE, TRUE = CURRENT
0= FALSE
1= TRUE
1
SPEED PROP
GAIN
F
M
SV
Sets the proportional gain of the loop.
Speed error (revolutions per second) x proportional
gain = torque percent.
0.00 to 300.00
product
code
dependent
SPEED INT TIME
F
M
SV
This is the integral time constant of the speed loop.
A speed error which causes the proportional term
to produce a torque demand T, will cause the
integral term to also ramp up to a torque demand
T after a time equal to “speed int time”.
1 to 15000ms
product
code
dependent
SPEED POS LIMIT
F
SV
This sets the upper limit of the speed demand.
-110.00 to 110.00% 110.00%
SPEED NEG LIMIT
F
SV
This sets the lower limit of the speed demand.
-110.00 to 110.00% -110.00%
Lefflersgatan 1, SE-754 50 Uppsala, SWEDEN
+46 (0)18-65 70 00
+46 (0)18-10 74 78 [email protected] www.regal.se