Parker 650V series Product Manual Download Page 1

650V 

Frame 1, 2 & 3

HA467649U003 Issue 1
Product Manual

 

   

Lefflersgatan 1, SE-754 50 Uppsala, SWEDEN   

+46 (0)18-65 70 00   

+46 (0)18-10 74 78   [email protected]   www.regal.se 

 

Summary of Contents for 650V series

Page 1: ...650V Frame 1 2 3 HA467649U003 Issue 1 Product Manual Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 2: ...Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 3: ...notice to make amendments or correct omissions Parker SSD Drives cannot accept responsibility for damage injury or expenses resulting therefrom WARRANTY Parker SSD Drives warrants the goods against de...

Page 4: ...rning requirements of the application are met The user must analyze all aspects of the application follow applicable industry standards and follow the information concerning the product in the current...

Page 5: ...rtification for the Inverter Component Relevant Apparatus Unit fitted Wall mounted Enclosure Application Area The equipment described is intended for industrial motor speed control utilising DC motors...

Page 6: ...All control and signal terminals are SELV i e protected by double insulation Ensure all external wiring is rated for the highest system voltage Thermal sensors contained within the motor must have at...

Page 7: ...eration 4 2 Remote Control Operation 4 2 Set up as an Open loop drive V F Mode 4 3 Set up using the Sensorless Vector Mode 4 3 Tuning the Drive to Your System 4 5 CHAPTER 5 THEKEYPAD 5 1 Controlling t...

Page 8: ...9 TECHNICALSPECIFICATIONS 9 1 Understanding the Product Code 9 1 Environmental Details 9 3 Power Details 9 3 Electrical Ratings 9 4 Supply Short Circuit Rating 9 5 User Relay 9 5 Analog Inputs Output...

Page 9: ...Marking for EMC Who is Responsible 10 3 EMC Compliance 10 3 Certificates 10 4 CHAPTER 11 SERIALCOMMUNICATIONS 11 1 Connection to the P3 Port 11 1 CHAPTER 12 APPLICATIONS 12 1 The Default Application...

Page 10: ...Contents Contents Page Cont 8 Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 11: ...tching frequencies and a unique Quiet Pattern control system that minimises audible noise from the motor Note Do not attempt to control motors whose rated current is less than 50 of the drive rated cu...

Page 12: ...1 2 Getting Started 650V AC Drive Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 13: ...ive assembly 7 Control terminals 2 Keypad 8 Volt free relay contacts 3 DIN clip fixing bracket 9 Product rating label 4 Terminal cover 10 Motor thermistor terminals 5 Power terminals 11 RS232 programm...

Page 14: ...2 2 An Overview of the Drive 650V AC Drive Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 15: ...998 the unit must be mounted inside a control cubicle that requires a tool for opening The cubicle should provide 15dB attenuation to radiated emissions between 30 100MHz Mount the drive vertically on...

Page 16: ...pplication are shown in Chapter 12 and can be made to suit your system Referring to the Connection Diagram Follow the instructions for Local Control Wiring as detailed above Install using minimum conn...

Page 17: ...L2 N 1 220 240V ac Frame 1 Power Terminal Variations 3 380 460V ac Refer to Chapter 12 Applications for specific control wiring for each Application Frame 2 3 380 460V ac Wiring Instructions IMPORTAN...

Page 18: ...B Thermistor Connection to motor thermistor It is good practice to protect motors by fitting temperature sensitive resistors A typical resistance up to a reference temperature of 125 C is 200 rising r...

Page 19: ...g torque for Frame 3 power connections is 20 lb in 2 26Nm Protect the incoming mains supply using the specified fuse or RCD circuit breaker Type B IMPORTANT We do not recommend the use of circuit brea...

Page 20: ...over A standard P3 lead Parker SSD Part Number CM057375U300 which is used to connect the Keypad to the drive Two self tapping screws are provided with the Keypad Remove the protective film from the ga...

Page 21: ...arts for the Remote Keypad Tools Required No 2 Posidrive screwdriver Assembly Procedure Cutout Dimensions An actual size template is provided with the Keypad 6052 Mounting Kit Figure 3 1 Mounting Dime...

Page 22: ...ng the Functional Earth terminal RS485 Connections RS232 Connections master to single multiple slave master to single slave only Tx Rx 0V 9 Way or 25 Way D Type Connector PC PLC 9 Way 25 Way D Type PC...

Page 23: ...oftware Product Manual available on the Parker SSD Drives website www SSDdrives com Note This Option can only be used on drives using software version 4 1 or higher Encoder Connections The drive is on...

Page 24: ...motor cable The choke is for use on the following drive Phase Drive Nominal Input Voltage V Drive Power kW hp Rated Current Aeff Rated Inductivity mH Choke Part Number 3 400 0 37 0 5 6 4 88 CO467763U0...

Page 25: ...to be tied high or low If the motor thermistor terminals are not connected to a motor thermistor connect these terminals together Check external run contacts are open Check external speed setpoints ar...

Page 26: ...se Alternatively swap two of the motor phases WARNING Disconnect the mains supply first The installation of your drive is now complete The drive will operate as an open loop drive It is programmed to...

Page 27: ...ption CONTROL MODE Set to SENSORLESS VEC 1 This parameter contains the main method of motor control used by the drive and by default is set to VOLTS HZ To operate in Sensorless Vector Mode the drive n...

Page 28: ...eally the motor shaft should be disconnected If the motor is connected to a gearbox this is ok provided that there is nothing on the output of the gearbox which could load the motor 1 Set MAX SPEED P...

Page 29: ...s a of MAX SPEED ACCEL TIME 10 0 s Set the time taken for the 650V to ramp up from zero to MAX SPEED DECEL TIME 10 0 s Set the time taken for the 650V to ramp down from MAX SPEED to zero JOG SETPOINT...

Page 30: ...4 6 Operating the Drive 650V AC Drive Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 31: ...rol mode Local or Remote Control Controlling the Drive using the Keypad Control Key Definitions Key Operation Description Escape Navigation Displays the previous level s menu Parameter Returns to the...

Page 32: ...cation Selection You can navigate immediately to the APPLICATION parameter P 1 from power up as shown opposite Then press the key to display the current Application Press again to allow the parameter...

Page 33: ...equency in Hertz SPEED SETPOINT The set point as a percentage of MAX SPEED DC LINK VOLTS Vac rms x 2 dc link Volts when motor stopped MOTOR CURRENT The current load value in Amps To see the following...

Page 34: ...24 Anout 2 value CONF DIN1 Digin 1 destination DIN2 Digin 2 destination DIN3 Digin 3 destination DIN4 Digin 4 destination DIN5 Digin 5 destination DIN6 Digin 6 destination DIN7 Digin 7 destination DOP...

Page 35: ...whilst holding the keys as shown to return to factory default settings This loads Application 1 Then press the key Changing the Default Operating Frequency Power up the drive whilst holding the keys...

Page 36: ...s will cause the drive to start Check RUN and JOG inputs are low Changing Direction in Local Control When the drive is running in Local Control the direction of rotation of the motor shaft can be chan...

Page 37: ...activated Go to Press 2 Enter new password using for example Enter current password using for example Enter current password using for example 3 Press repeatedly until top of menu is reached Remote S...

Page 38: ...5 8 The Keypad 650V AC Drive Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 39: ...Parameters They are not reset by changing Application using parameter P 1 all other parameters are reset to default values VF Parameters indicated with VF are only visible when the drive is in VF Volt...

Page 40: ...ge of the MAX SPEED parameter 100 0 to 100 0 10 0 RUN STOP MODE RAMPED The motor speed is reduced to zero at a rate set by DECEL TIME P 5 A 2 second DC pulse is applied at end of ramp COAST The motor...

Page 41: ...he lower end of the speed range OUTPUT VOLTS FREQUENCY f B 25 100 BOOST f B BASE FREQUENCY 0 INCREASING INCREASED TORQUE CONSTANT POWER RANGE FLUXING NORMAL FLUXING 0 00 to 25 00 product code dependen...

Page 42: ...TRUE Eliminates light load speed variations in V F Fluxing Mode 0 FALSE 1 TRUE 1 VOLTAGE CONTROL MODE VF NONE no attempt is made to control the PWM modulation depth for variations in dc link voltage F...

Page 43: ...r model no load line current as determined by the Autotune or taken from the motor nameplate 0 01 to 999 99 A product code dependent POWER M SV This parameter contains the motor nameplate power 0 00 t...

Page 44: ...per second x proportional gain torque percent 0 00 to 300 00 product code dependent SPEED INT TIME F M SV This is the integral time constant of the speed loop A speed error which causes the proportio...

Page 45: ...LE OFFSET X INPUT TYPE UNPROCESSED 0 to 100 of selected TYPE 0 0 10V 1 0 5V 2 0 20mA 3 4 20mA 3 DIN 1 VALUE F The TRUE or FALSE input after any inversion 0 FALSE 1 TRUE 0 DIN 2 VALUE F The TRUE or FAL...

Page 46: ...PPED 3 RUNNING 4 AT ZERO 5 AT SPEED 6 AT LOAD 7 READY 0 NONE 1 HEALTH 2 TRIPPED 3 RUNNING 4 AT ZERO 5 AT SPEED 6 AT LOAD 7 READY ANOUT 1 SOURCE F ANOUT 2 SOURCE F ANALOG OUTPUT 0 NONE 1 DEMAND 2 CURRE...

Page 47: ...s the maximum time allowed between refreshing the COMMS COMMAND parameter The drive will trip if this time is exceeded Set the time to 0 00 seconds to disable this feature 0 0 to 600 0s 0 0s COMMS ADD...

Page 48: ...hat will be permitted before requiring an external fault reset 0 to 10 0 AUTO RESTART DELAY Determines the delay between restart attempts for a trip included in AUTO RESTART TRIGGERS and AUTO RESTART...

Page 49: ...L R JOG DIR 0000 0010 0020 0030 0040 0050 0060 0070 0080 0090 00A0 00B0 00C0 00D0 00E0 00F0 ENABLED ENABLED ENABLED ENABLED ENABLED ENABLED ENABLED ENABLED ENABLED ENABLED ENABLED ENABLED ENABLED ENAB...

Page 50: ...ines must be set to match the type of encoder being used Incorrect setting of this parameter will result in an erroneous speed measurement 100 to 10000 100 ENC SPEED SCALE F This parameter allows the...

Page 51: ...a Digital Output For example to use terminal 10 as an output select S DOP2 to be 1 2 3 4 5 or 6 For instance you could set parameter S DOP2 to 3 to have the output go high 24V whenever the motor is r...

Page 52: ...put A Method for Setting up the PI Gains The gains should be set up so that a critically damped response is achieved for a step change in setpoint An underdamped or oscillatory system can be thought o...

Page 53: ...equencies Parameters S ST11 to S ST14 control two programmable skip frequencies that can prevent the drive from operating at frequencies that cause mechanical resonance in the load Enter the value of...

Page 54: ...refer to the 650V Software Product Manual on our web site www SSDdrives com Frequency Dependent Parameters These parameter values marked with in the Application diagrams are dependent upon the drive s...

Page 55: ...1750 RPM MOTOR VOLTAGE MOTOR DATA 1160 MAX SPEED REFERENCE 57 50Hz 60Hz MOTOR CONNECTION MOTOR DATA 124 STAR STAR The correct value is selected for the size of drive refer to the Power Dependent Param...

Page 56: ...OWER DYNAMIC BRAKING 78 0 1 kW 0 1 kW 0 1 kW 0 1 kW 0 1 kW 0 1 kW FREQUENCY INJ BRAKING 577 9 0 Hz 9 0 Hz 9 0 Hz 9 0 Hz 9 0 Hz 9 0 Hz DEFLUX TIME INJ BRAKING 710 0 1 s 0 1 s 0 1 s 0 1 s 0 1 s 0 1 s BA...

Page 57: ...0 Hz 9 0 Hz 9 0 Hz DEFLUX TIME INJ BRAKING 710 0 1 s 0 1 s 0 1 s 0 1 s 0 1 s 0 1 s BASE VOLTS INJ BRAKING 739 100 00 100 00 100 00 100 00 100 00 100 00 DC LEVEL INJ BRAKING 581 3 0 3 0 3 0 3 0 3 0 3...

Page 58: ...DEFLUX TIME INJ BRAKING 710 0 5 s 0 5 s 0 5 s 0 5 s BASE VOLTS INJ BRAKING 739 100 00 100 00 100 00 100 00 DC LEVEL INJ BRAKING 581 3 0 3 0 3 0 3 0 DC PULSE INJ BRAKING 579 2 0 s 2 0 s 2 0 s 2 0 s FIN...

Page 59: ...Trip Condition All trips must be reset before the drive can be re enabled A trip can only be reset once the trip condition is no longer active i e a trip due to a heatsink over temperature will not re...

Page 60: ...used the trip Remove the overload condition refer to Chapter 5 P 12 7 CURRENT LOOP A current of less than 1mA is present when 4 20mA setpoint is selected Look for a wire break 8 MOTOR STALLED The moto...

Page 61: ...The motor is drawing too much current 100 at zero output frequency FIXED BOOST level set too high 22 10V FAULT 10V fault 10V REF overload warning terminal 4 10mA maximum 25 DC LINK RIPPLE The dc link...

Page 62: ...constant is too small Check the value of nameplate rpm 41 MAX RPM DATA ERR This error is reported when the MAX SPEED RPM is set to a value outside the range for which Autotune has gathered data Autot...

Page 63: ...100 9 10 BRAKE RESISTOR 0x0200 9 11 BRAKE SWITCH 0x0400 9 12 DISPLAY KEYPAD 0x0800 9 13 LOST COMMS SCI 0x1000 9 14 CONTACTOR FBK CNTC 0x2000 9 15 SPEED FEEDBACK 0x4000 9 S ST24 AUTO RESTART TRIGGERS I...

Page 64: ...ps BRAKE SWITCH ANIN FAULT MOTOR STALLED and INVERSE TIME In the same way the AUTO RESTART TRIGGERS parameter set to 04A0 would represent OVERSPEED ANIN FAULT DESAT OVER I and 10V FAULT Fault Finding...

Page 65: ...osure Do not allow packaging chips to enter the unit Disposal This product contains materials which are consignable waste under the Special Waste Regulations 1996 which complies with the EC Hazardous...

Page 66: ...8 2 Routine Maintenance and Repair 650V AC Drive Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 67: ...2 3 3 2123 3 4 16 4 5 16 4 3 2164 3 400 460v 3phase 43 0 37 1 5 0 5 1 5 2 1150 2 0 55 2 0 0 75 2 0 2 1200 2 0 75 2 5 1 2 5 2 1250 2 1 1 3 5 1 5 3 5 2 1350 2 1 5 4 5 2 4 5 2 1450 2 2 2 5 5 3 5 5 2 1550...

Page 68: ...650V Generic product 2 XXXX Four characters specifying the power output in Hp 00F3 0 3Hp 00F5 0 5Hp 00F7 0 75Hp 0001 1Hp 01F5 1 5Hp 0002 2Hp 0003 3Hp 0005 5Hp 0007 7Hp 0010 10Hp 3 XXX Three numbers sp...

Page 69: ...N50178 1998 Vibration Test Fc of EN60068 2 6 10Hz f 57Hz sinusoidal 0 075mm amplitude 57Hz f 150Hz sinusoidal 1g 10 sweep cycles per axis on each of three mutually perpendicular axis Safety Pollution...

Page 70: ...r kW hp Surge Current peak rms for 10ms A A Output Current 40 o C A ac Maximum Power Loss W 1 1 1 5 24 17 13 8 5 5 65 1 5 2 0 25 18 16 0 7 0 82 FRAME 2 3 Phase IT TN 400V Drive Power kW hp Input Curre...

Page 71: ...CO352783 RL 01202 2 50 12 3 6 0kW 10Hp CO352785 RL 01802 1 50 18 3 7 5kW 10Hp CO352785 RL 01802 1 50 18 User Relay RL1A RL1B Maximum Voltage 250Vac Maximum Current 4A Sample Interval 10ms Analog Inpu...

Page 72: ...terminals 6 10 11 Cabling Requirements for EMC Compliance Power Supply Cable Motor Cable Brake Resistor Cable Signal Control Cable Cable Type for EMC Compliance Unscreened Screened armoured Screened...

Page 73: ...prevent injury from burning Recommended Brake Resistors The following brake resistors are available from Parker SSD Drives Brake Resistor Value Frame 2 200 100W CZ467714 500 60W CZ467715 Frame 3 28 50...

Page 74: ...2 3 0 4 0 Fundamental Voltage V 230 230 230 230 230 230 230 230 230 Typical Motor Efficiency 85 85 85 85 85 85 85 85 85 Harmonic No RMS Current A 1 7 4 7 5 7 8 8 2 9 0 10 3 TBA TBA TBA 3 1 4 0 2 1 9...

Page 75: ...9 5 12 9 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 0 6 0 9 1 2 1 8 2 4 3 5 4 7 6 2 8 3 11 1 7 0 6 0 9 1 2 1 7 2 3 3 3 4 3 5 5 7 3 9 5 9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 0 5 0 8 1 0 1 5 1...

Page 76: ...1 1 5 2 2 3 0 4 0 Fundamental Voltage V 230 230 230 230 230 230 230 230 230 Typical Motor Efficiency 85 85 85 85 85 85 85 85 85 Harmonic No RMS Current A 1 1 3 2 0 2 9 3 9 5 7 7 8 TBA TBA TBA 3 1 3 1...

Page 77: ...2 6 9 9 5 12 7 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 0 6 0 9 1 2 1 8 2 4 3 6 4 7 6 3 8 4 11 0 7 0 6 0 9 1 2 1 7 2 3 3 3 4 3 5 7 7 4 9 5 9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 0 5 0 8 1 0...

Page 78: ...9 12 Technical Specifications 650V AC Drive Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 79: ...d State Motor Overload Protection These devices provide Class 10 motor overload protection The maximum internal overload protection level current limit is 150 for 30 seconds An external motor overload...

Page 80: ...T TN 230V Input Current 5kA Drive Power kW hp A Supply Fuse Rating A 10 x 38mm 0 25 0 3 4 2 10 0 37 0 5 6 2 10 0 55 0 75 7 9 10 0 75 1 0 10 5 15 FRAME 2 1 Phase IT TN 230V Input Current 5kA Drive Powe...

Page 81: ...hen the unit is classed as relevant apparatus In this situation the responsibility for certification rests with Parker SSD Drives The Declaration of Conformity is included at the end of this Chapter 2...

Page 82: ...EMC compliance when the unit is used as a component We Parker SSD Drives address as below declare under our sole responsibility that the above Electronic Products when installed and operated with ref...

Page 83: ...mpliance when the unit is used as a component We Parker SSD Drives address as below declare under our sole responsibility that the above Electronic Products when installed and operated with reference...

Page 84: ...10 6 Certification for the Drive 650V AC Drive Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 85: ...rotocol Contact Parker SSD Drives for further information The P3 port is located under the terminal cover and can be used for pc configuration or to remote mount a RS232 keypad P3 Port A standard P3 l...

Page 86: ...11 2 Serial Communications 650V AC Drive Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 87: ...most applications How to Load an Application In the menu go to and press the key twice The Applications are stored in this menu Use the keys to select the appropriate Application by number Press the...

Page 88: ...EMAND FWD REV P9 IP13 AIN1 TYPE SEQUENCING LOGIC 0 CONSTANT TORQUE 1 VARIABLE TORQUE P7 BASE FREQ P13 V BOOST P11 V FSHAPE frequency 0 0 1 0 V 1 0 5 V IP23 AIN2TYPE 0 0 10 V 1 0 2 0 3 4 20mA 0 NONE 1...

Page 89: ...or general purpose applications It provides push button or switched start stop control The setpoint is the sum of the two analogue inputs AIN1 and AIN2 providing Speed Setpoint Speed Trim capability L...

Page 90: ...SPEED RAMP P2 MAX SPEED P3 MIN SPEED CURRENT LIMIT P4 ACCEL TIME P5 DECEL TIME PWM CONTROL V F SHAPING CT VT V F V F I FDBK V F SPEED DEMAND FWD REV SEQUENCING LOGIC 0 CONSTANT TORQUE 1 VARIABLE TORQU...

Page 91: ...run forward REMOTE REVERSE 0 V remote forward 24V remote reverse DIN2 DIN1 24V run forward 24V DOUT3 relay 0V not used Control Terminal COAST STOP 24V coast to stop 0 V drive may run AUTO RUN 24V run...

Page 92: ...ODE P9 STOP MODE RL1 A RL1 B Use Relay R 0 CONSTANT TORQUE 1 VARIABLE TORQUE P7 BASE FREQ P13 V BOOST P11 V F SHAPE 50 60Hz base frequency P2 MAX SPEED P3 MIN SPEED 1 2 3 4 5 6 7 8 9 10 11 12 13 0 NON...

Page 93: ...levels These are selected using DIN2 DIN3 and DIN4 refer to the Truth Table below Edit parameters AP2 to AP8 on the keypad to re define the speed levels of PRESET 1 to PRESET 7 Reverse direction is a...

Page 94: ...DBK V F 0 CONSTANT TORQUE 1 VARIABLE TORQUE P7 BASE FREQ P13 V BOOST P11 V F SHAPE 50 60Hz base frequency RAM P P4 ACCEL TIME P5 DECEL TIME SPEED DEMAND FWD REV MIN MAX SPEED START STOP RAISE LOWER RE...

Page 95: ...potentiometer Digital inputs allow the setpoint to be increased and decreased between limits The limits and ramp rate can be set using the keypad The Application is sometimes referred to as Motorised...

Page 96: ...D 2CURRENT 3 PID ERROR 4 RAISE LOWER DIN 1 User Relay R L1A RL1B R 1 2 3 4 5 6 7 8 9 10 11 12 13 I GAIN P GAIN SETPOINT 3 0 NONE 1 HEALTH 2 TRIPPED 3 RUNNING 4 AT ZERO 5 AT SPEED 6 7 AT LOAD EASY TUNI...

Page 97: ...6 5 4 3 2 1 RL1A RL1B 13 12 11 WIRE SINGLE STARTING DOUT3 relay Control Terminal DEMAND 0 V 0 10V 100 4 mA 0 20 mA 100 RELAY SOURCE HEALTH i e 0 V not healthy 0 3 1 1 A or V 4 20mA default source 0 V...

Page 98: ...12 12 Applications 650V AC Drive Application 6 Auxilliary Comms Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 99: ...k Function Bit 4 Jog Bit 3 Trip reset Bit 2 Reverse Bit 1 Enable Bit 0 Run forward AP03 Tag 598 Mask Diagnostic Bit 13 At speed Bit 12 Zero speed Bit 11 Ramping Bit 10 Fan running Bit 9 Healthy Bit 8...

Page 100: ...12 14 Applications 650V AC Drive Lefflersgatan 1 SE 754 50 Uppsala SWEDEN 46 0 18 65 70 00 46 0 18 10 74 78 info regal se www regal se...

Page 101: ...Parvex 8 Avenue du Lac B P 249 21007 Dijon Cedex Tel 33 0 80 42 41 40 Fax 33 0 80 42 41 23 USA Parker Hannifin Corporation SSD Drives 9225 Forzyth Park Drive Charlotte North Carolina 28273 Tel 1 704 5...