Hyperchill-Precision  Control     ICE015-057

2 Introduction

Th

  ese water coolers are monoblock units for the production of cooled 

water in a closed circuit.
Th

  e fan, pump and compressor motors are equipped with a thermal 

protector that protects them against possible overheating.

2.1 Transport

Th

  e packed unit must remain:

a)  Upright;
b)  Protected against atmospheric agents;
c)  Protected against impacts.

2.2 Handling

Use a fork-lift  truck suitable for the weight to be lift ed, avoiding any 
type of impact

2.3 Inspection

a)  All the units are assembled, wired, charged with refrigerant and oil 

and tested in the factory;

b)  On receiving the machine check its condition: immediately notify 

the transport company in case of any damage; 

c)  Unpack the unit as close as possible to the place of installation.

2.4 Storage

a)  Keep the unit packed in a clean place protected from damp and 

bad weather.

b)  Do not stack the units;
c)  Follow the instructions given on the package.

3 Installation

Y

For correct installation, follow the instructions given in par.7.2, 7.3 

and 7.7.

For the correct application of the warranty terms, follow the 

instructions given in the start-up report, fi ll it in and send it back to 
Seller

!

 

Liquids to be chilled

Th

  e liquids to be chilled must be compatible with the materials used.

Examples of liquids used are water or mixtures of 

water and ethylene 

or propylene glycols.

Th

  e liquids to be chilled must not be fl ammable. 

If the liquids to be chilled contain hazardous substances (e.g. ethylene/
propylene glycol), any liquid discharged from a leakage area must be 
collected, because it is harmful to the environment.  When draining 
the hydraulic circuit, comply with the current regulations and do not 
disperse the contents in the environment.

3.1 Operating space

Leave a space of 1.5 m around the unit. 
Leave a space of at least 2 metres above the refrigerator in models with 
vertical emission of condensation air.

3.2 Versions

Air-cooled version

Axial fans (A)

Do not create cooling air recirculation situations. 
Do not obstruct the ventilation grilles.
Th

  e ducting of extracted air is not recommended for versions with 

axial fans.

Centrifugal version (C)

Always ensure a minimum counterpressure on the delivery of
fans, ducting the individual hot air outlets.

Water- cooled version (W)

If the water to the condenser is in open circuit, install a mesh fi lter on 
the condensation water inlet.
Please note that for special cooling water types such as demineral-
ized, deionized or distilled it is necessary to contact the manufacturer 
to verify which kind of condenser should be used since the standard 
material may not be suitable.

3.3 Water circuit

3.3.1 

Checks and connection

Before connecting the chiller and fi lling the water circuit, check 

that all the pipes are clean. If not, wash them out thoroughly. 

If the plumbing circuit is of the closed type, under pressure it is 

advisable to install a safety valve set to 6 bar. 

Always install mesh fi lters on the water inlet and outlet pipelines.

If the hydraulic circuit is intercepted by automatic valves, protect 

the pump with an anti-hammering system.

If the hydraulic circuit is emptied for shut-down periods we 

recommend that you add lubricating fl uid to the pump’s impeller to 
avoid the risk of blockage when it is re-started.    In case the impeller is 
blocked then you should unblock it manually.
Remove the rear cover of the pump and carefully turn the plastic fan.   
If the impeller is stuck then remove the fan and turn the impeller shaft  
directly. Aft er un-blocking the impeller re-assemble the fan and cover.

Preliminary checks

1)  Check that any shut-off  valves in the water circuit are open.
2)  In the case of a closed water circuit, check that an expansion tank 

of suitable capacity has been installed. See paragraph 3.3.3.

Connection

1)  Connect the water cooler to the inlet and outlet piping, using the 

special connections located on the back of the unit.
We recommend the use of fl exible unions to reduce system rigidity.

2)  Fill the water circuit using the fi tting provided on the rear of the 

chiller (

).

3)  Th

  e tank is equipped with a breather valve that should be operated 

manually when fi lling the tank. Also, if the hydraulic circuit has high 
points, install a vent valve at the highest points.

4)  We recommend that taps are installed on the inlet and outlet pipes, 

so that the unit can be excluded for maintenance when necessary.

5)  If the chiller works with an open tank, the pump must be installed 

on intake to the tank and on delivery to the chiller.

Subsequent checks

1)  Check that the tank and the circuit are completely full of water and 

that all the air has been expelled from the system.

2)  Th

  e water circuit must always be kept full. For this reason, carry 

out periodic checks and top the circuit up if necessary, or install an 
automatic fi lling kit.

3.3.2 

Water and ethylene glycol

If installed outdoors or in an unheated indoor area, it is possible that 
the water in the circuit may freeze if the system is not in operation dur-
ing the coldest times of the year.
To avoid this hazard:

a)  Equip the chiller with suitable antifreeze protection devices, avail-

able from the manufacturer as optional accessories;

b)  Drain the system via the drain valve if the chiller is to remain idle 

for a prolonged period;

c)  Add an appropriate quantity of antifreeze to the water in circula-

tion (see table).

Sometimes the temperature of the outlet water is so low as to require 
the addition of ethylene glycol in the following percentages.

Outlet water

temperature  [°C]

Ethylene glycol

(% vol.)

Ambient

temperature

4

5

-2

2

10

-5

0

15

-7

-2

20

-10

-4

25

-12

-6

30

-15

3.3.3 Expansion 

tank

To avoid the possibility of an increase or decrease in the volume of the 
fl uid due to a signifi cant change in its temperature causing damage to 
the machine or the water circuit, we recommend installing an expan-
sion tank of suitable capacity.
Th

  e expansion tank must be installed on intake to the pump on the 

rear connection of the tank.

Summary of Contents for Hyperchill ICE015

Page 1: ...Hyperchill 50Hz Precision control ICE015 ICE022 ICE029 ICE039 ICE046 ICE057 DATE 25 02 2016 Rev 25 CODE 398H271673 IT Manuale d uso EN User Manual ES Manual de uso DE Benutzer Handbuch ...

Page 2: ......

Page 3: ...mponenti ATTENZIONE Il costruttore si riserva il diritto di modificare le informazioni contenute nel presente manuale senza alcun preavviso Ai fini di una completa ed aggiornata informazione si raccomanda all utente di consultare il manuale a bordo unità 1 4 Rischi residui L installazione l avviamento lo spegnimento la manutenzione della macchina devono essere tassativamente eseguiti in accordo co...

Page 4: ...è consigliabile installare una valvola di sicurezza tarata a 6 bar Y Si consiglia di installare sempre dei filtri a rete sulle tubazioni di ingresso e uscita acqua Y Nel caso in cui il circuito idraulico sia intercettato da valvole auto matiche proteggere la pompa con sistemi anti colpo d ariete Y Nel caso il circuito venga svuotato per fermate prolungate si con siglia di aggiungere del fluido lub...

Page 5: ...inale In di tale magnetotermico deve essere uguale a FLA e la curva di intervento di tipo D 5 Valore massimo dell impedenza di rete 0 274 ohm Controlli successivi Assicurarsi che la macchina e le apparecchiature ausiliarie siano state messe a terra e protette contro cortocircuiti e o sovraccarichi Una volta che l unità è stata collegata e l interruttore generale a monte è stato chiuso dando così t...

Page 6: ...ella pompa utilizzando il manometro leggere P1 e P0 e i valori limite di pressione Pmax e Pmin riportati sulla targa dati della pompa P1 pressione con pompa ON P0 pressione con pompa OFF Pmin P1 P0 Pmax Esempio n 1 Condizioni circuito chiuso a pressione P0 di 2 bar dati targa pompa Pmin 1bar Pmax 3bar regolare l uscita valvola per una pressione di 3bar P1 5Bar Esempio n 2 Condizioni circuito apert...

Page 7: ... con set SEA attivazione pompa da B3 sonda ambiente con setARA resistenza e pompa con attivazione separata 4 4 8 2 Modalità attivazione resistenza antigelo AbrA 0 Attivazione solo con scheda in On 1 Attivazione anche con scheda in Off 2 Attivazione anche con scheda in Off Durante il funziona mento della resistenza c è l attivazione della pompa 4 5 Gestione parametri 4 5 1 Regolazione temperatura v...

Page 8: ...enzione preventiva Per garantire nel tempo la massima efficienza ed affidabilità del chiller eseguire a Z ogni 4 mesi pulizia alette condensatore e verifica assorbi mento elettrico compressore entro valori di targa b Zannualmente versione W in caso di incrostazioni interne al condensatore immettere e far circolare apposito liquido detergente b Z ogni 3 anni installazione kit manutenzione ogni 3 an...

Page 9: ...REFRIGERANTE INTASATO SOSTITUIRE IL FILTRO ALETTE DEL CONDENSATORE SPORCHE PULIRE LE ALETTE DEL CONDENSATORE SUPERFICIE DEL CONDENSATORE OSTRUITA LIBERARE LA SUPERFICIE FRONTALE DEL CONDENSATORE PORTATA ACQUA INSUFFICIENTE AUMENTARE LA PORTATA DEL FLUIDO DA RAF FREDDARE COMPONENTI COMPRESSORE DETERIORATI RIPARARE O SOSTITUIRE COMPRESSORE PERDITE NEL CIRCUITO IMPIANTO SCARICO VERIFICARE LA PRESENZA...

Page 10: ...Italiano 8 8 Hyperchill Precision Control ICE015 057 ...

Page 11: ...ORTANT The manufacturer reserves the right to modify this manual at any time For the most comprehensive and updated information the user is advised to consult the manual supplied with the unit 1 4 Residual risks The installation start up stopping and maintenance of the machine must be performed in accordance with the information and instruc tions given in the technical documentation supplied and a...

Page 12: ...advisable to install a safety valve set to 6 bar Y Always install mesh filters on the water inlet and outlet pipelines Y If the hydraulic circuit is intercepted by automatic valves protect the pump with an anti hammering system Y If the hydraulic circuit is emptied for shut down periods we recommend that you add lubricating fluid to the pump s impeller to avoid the risk of blockage when it is re s...

Page 13: ...n of the magnetic circuit breaker must be equal to the FLA with an intervention curve type D 5 Max grid impedance value 0 274 ohm Subsequent checks Check that the machine and the auxiliary equipment are earthed and protected against short circuit and or overload Once the unit has been connected and the upstream main switch closed thereby connecting the power supply to the machine the voltage in th...

Page 14: ...sure gauge read P1 and P0 and checking the pressure limit values Pmax and Pmin indicated on the pump data plate P1 pressure with pump ON P0 pressure with pump OFF Pmin P1 P0 Pmax Example n 1 Conditions closed circuit pressure P0 2 bar pump data plate values Pmin 1 bar Pmax 3 bar adjust the valve outlet to give a pressure of 3 bar P1 5 bar Example n 2 Conditions open circuit pressure P0 0 bar pump ...

Page 15: ... B1 with SEAsetting pump activation by B3 ambient sensor with ARA setting heating element and pump with separate activation 4 4 8 2 AbrA antifreeze heater activation mode 0 Activation only when controller is On 1 Activation also when controller is Off 2 Activation also when controller is Off During heater op eration the pump is activated 4 5 Parameter management 4 5 1 Temperature setting see fig 1...

Page 16: ...ered by the warranty 5 2 Preventive maintenance To guarantee lasting maximum chiller efficiency and reliability carry out a Z every 4 months clean the condenser fins and make sure com pressor electrical absorption is within the dataplate values b Zyearly W version in case of encrustations inside the con denser introduce and circulate a specific detergent liquid b Z Every 3 years installation of ki...

Page 17: ...H REFRIGE RANT FILTER CLOGGED RENEW THE FILTER CONDENSER FINS DIRTY CLEAN THE FINS OF THE CONDENSER CONDENSER SURFACES CLOGGED CLEAR THE FRONT SURFACE OF THE CON DENSER INSUFFICIENT WATER FLOW INCREASE THE FLOW RATE OF THE FLUID TO BE COOLED COMPRESSOR COMPONENTS DETERIORATED REPAIR OR REPLACE COMPRESSOR LEAKS IN CIRCUIT SYSTEM DISCHARGED CHECK FOR LEAKS REPAIR CHARGE THE CIRCUIT REFRIGERANT FILTE...

Page 18: ...English 8 8 Hyperchill Precision Control ICE015 057 ...

Page 19: ...o de los componentes ATENCIÓN El fabricante se reserva el derecho de modificar sin previo aviso la información de este manual Para que la información resulte completa se recomienda al usuario consultar el manual a pie de máquina 1 4 Riesgos residuales Las operaciones de instalación puesta en marcha apagado y man tenimiento del equipo deben realizarse de total conformidad con lo indicado en la docu...

Page 20: ...de tipo cerrado bajo presión se acon seja instalar una válvula de seguridad calibrada a 6 bar Y Se recomienda instalar filtros de red en los tubos de entrada y salida del agua Y Si el circuito hidráulico posee válvulas automáticas de corte proteger la bomba con sistemas contra golpe de ariete Y Si se vacía el circuito por paradas prolongadas se recomienda añadir aceite lubricante en el rodete de l...

Page 21: ...mpedancia de red 0 274 ohm Controles sucesivos Comprobar que el equipo y los dispositivos auxiliares estén conectados a tierra y protegidos contra cortocircuitos y sobrecargas Una vez conectado el equipo cuando se cierra el interruptor general de alimentación para energizarlo la tensión en el circuito eléc trico alcanza valores peligrosos Se recomienda la máxima precaución 3 4 2 Alarma general Tod...

Page 22: ...correcto de la bomba utilizando el manómetro leer P1 y P0 y los valores límite de presión Pmáx y Pmín indicados en la placa de datos de la bomba P1 presión con bomba ON P0 presión con bomba OFF Pmín P1 P0 Pmáx Ejemplo n 1 Condiciones circuito cerrado a presión P0 de 2 bar datos de matrícula de la bomba Pmín 1bar Pmáx 3bar regular la salida de la válvula a una presión de 3bar P1 5Bar Ejemplo n 2 Co...

Page 23: ... B3 sonda ambiente con configuración ARA y resistencia activada si la bomba está activada 1 Control termostático de la resistencia y activación de la bom ba desde B3 sonda ambiente con configuración ARA 2 Control termostático de la resistencia desde B1 con con figuración SEA activación de la bomba desde B3 sonda ambiente con configuración ARA y resistencia y bomba con activación separada 4 4 8 2 M...

Page 24: ...po YEn caso de pérdida de refrigerante llame a un técnico experto y autorizado YLa válvula Schrader debe utilizarse sólo en caso de funcionamien to anómalo del equipo de lo contrario los daños causados por una carga incorrecta de refrigerante no serán reconocidos en garantía 5 2 Mantenimiento preventivo Para garantizar la máxima eficacia y fiabilidad del refrigerador hay que a Z ocada 4 meses clim...

Page 25: ...GERANTE ATASCADO SUSTITUIR EL FILTRO ALETAS DEL CONDENSADOR SUCIAS LIMPIAR LAS ALETAS DEL CONDENSADOR SUPERFICIE DEL CONDENSADOR OBSTRUIDA LIBERAR LA SUPERFICIE FRONTAL DEL CONDENSADOR CAUDAL DE AGUA INSUFICIENTE AUMENTAR EL CAUDAL DEL FLUIDO A REFRIGERAR COMPONENTES COMPRESOR DETERIORADOS REPARAR O SUSTITUIR EL COMPRESOR PÉRDIDAS EN EL CIR CUITO INSTALACIÓN DESCARGADA VERIFICAR LA PRESENCIA DE PÉ...

Page 26: ...Español 8 8 Hyperchill Precision Control ICE015 057 ...

Page 27: ...n Spezifikationen und oder deren Bauteile und oder Optionen für die korrekte bzw in vernünftiger Weise vorhersehbare Nutzung der Anlage bzw der Bauteile ausreichen ACHTUNG Der Hersteller behält sich das Recht vor die in dem vorliegenden Handbuch enthaltenen Informationen ohne Vorbe scheid zu ändern Zur vollständigen und aktuellen Information wird empfohlen das mit dem Gerät gelieferte Handbuch auf...

Page 28: ...nfalls muss eine sorgfältige Spülung ausgeführt werden Y Bei unter Druck stehendem geschlossenem Wasserkreislauf empfiehlt sich die Installation eines auf 6 Bar geeichten Sicherheitsven tils Y An den Wassereinlauf und Wasserauslaufleitungen sollten stets geeignete Siebfilter installiert werden Y Wird der Wasserkreis durch automatisch ansprechende Ventile gesperrt ist die Pumpe durch geeignete Wass...

Page 29: ...an angegebenen Stromfestigkeit zu installieren der über eine geeignete Trennschaltleistung bezüglich des Kurzschlussstroms im Aufstellungsbereich der Einheit verfügt Der Nennstrom In des Schutzschalters muss FLA entsprechen und die Auslösekennlinie muss vom Typ D sein 5 Maximaler Netzimpedanzwert 0 274 Ohm Nachfolgende Kontrollen Comprobar que el equipo y los dispositivos auxiliares estén conectad...

Page 30: ...he Para graph 4 5 b Den korrekten Betrieb der Pumpe mit einem Druckmesser P1 und P0 ablesen und die Druckgrenzwerte Pmax e Pmin auf dem Typenschild der Pumpe überprüfen P1 Druck Pumpe ON P0 Druck Pumpe OFF Pmin P1 P0 Pmax Beispiel Nr 1 Bedingungen Geschlossener Kreislauf bei P0 Druck von 2 bar Daten des Pumpenschilds Pmin 1bar Pmax 3bar Den Ventilausgang für einen Druck von 3bar P1 5Bar einstel le...

Page 31: ...stand siehe Abs 4 4 8 2 AbrA U 2 Sollwert Aktivierung B3 ArA U 5 0 4 4 8 1 Funktionsmodalität Frostschutzwiderstand FUA 0 Thermostatregelung des Widerstands durch B1 mit Sollwert SEA Zuschaltung der Pumpedurch B3 Raumsonde mit Sollwert ARA Widerstand bei eingeschalteter Pumpe akti viert 1 Thermostatregelung des Widerstands Einschalten der Pumpe durch B3 Raumsonde mit Sollwert ARA 2 Thermostatregel...

Page 32: ...gseingriff muss kontrolliert werden dass das Gerät nicht mehr gespeist wird YStets Original Ersatzteile des Herstellers verwenden anderenfalls übernimmt der Hersteller keinerlei Haftung bei Fehlbetrieben der Einheit YBei Verlust von Kältemittel ist erfahrenes und autorisiertes Fa chpersonal zu kontaktieren YDas Schrader Ventil ist nur im Fall eines von der Norm ab weichenden Betriebs der Einheit e...

Page 33: ...R STOPFT FILTER ERSETZEN RIPPEN DES KONDENSATORS VERSCHMUTZT RIPPEN DES KONDENSATORS REINIGEN OBERFLÄCHE DES KONDENSATORS BEDECKT BEDECKUNG AN FRONTOBERFLÄCHE DES KONDENSATORS ENTFERNEN WASSER VOLU MENSTROM UN ZUREICHEND VOLUMEN STROM DER ZU KÜHLENDEN FLÜSSIGKEIT ERHÖHEN KOMPONENTEN VERDICHTER ABGENUTZT VER DICHTER RE PARIEREN ODER ERSETZEN VERLUSTE IM KREIS ANLAGE NICHT BEFÜLLT LECKSTELLEN SUCHEN...

Page 34: ...Deutsch 8 8 Hyperchill Precision Control ICE015 057 ...

Page 35: ......

Page 36: ... Corsico MI Italy Sede Operativa Hiross Zander Filtration Division Strada Zona Industriale 4 35020 S Angelo di Piove PD Italy tel 39 049 971 2111 fax 39 049 9701911 Web site www parker com hzd e mail technical support hiross parker com A division of Parker Hannifin Corporation ...

Reviews: