DGP-NE96 Control Panel
3
Figure 3: DGP-NE96 Control Panel Wiring Diagram
AUX Power (Auxiliary):
Refer to the transformer requirements for the
Auxiliary Power Output. Also, refer to the
Power Unit Consumption Table. To connect
additional wiring to auxiliary power, use the
red (+) and black (-) keypad connectors.
Auxiliary power will shut down if the current
exceeds 1.1A.
When installing the combus wires in a noisy environment, or
when connecting the combus across separate buildings, you
must use a shielded cable. Refer to section 2.16.1 on page 7.
PLEASE NOTE:
When powering up the DGP-NE96 control panel (V1.02 or higher), the panel will begin a module scan to verify if all the modules connected to the panel are operational. The scanning
process will take between 30 and 120 seconds to complete depending on the number of modules connected to the control panel. The module scan is complete when the LCD keypad begins to show the
partition status. Only after the module scan is complete will the control panel be fully operational.
PLEASE NOTE
: It is strongly recommended that you test your
system on a weekly basis, and have your system checked by a
qualified technician a minimum of every 3 years.
Please see
on page 57 for applicable UL/
ULC warnings and information.
The combus supports a maximum of 127 modules. Although
external power supplies can be used to provide power to
modules connected far from the control panel, the total
distance of all runs of wire combined cannot exceed 914m
(3000ft). For example, if ten runs of wire measuring 305m
(1000ft) each are connected to the control panel, the total
distance would be 3048m (10, 000ft), which exceeds the
system's capacity.
WARNING: Before adding any module to the control
panel make sure you shutdown the control panel by
removing AC power and the battery.
Door Contact
* if EOL is enabled in the
control panel
*A 1K
9
resistor is
required if the bell is
not equipped with an
internal resistor. The
resistor must be
connected between
the bell's negative (-)
and positive (+) wires.
Position the resistor as
close as possible to
the bell. A resistor is
not required for sirens.
The bell
output will
shut down if
the current
exceeds 3A.
Bell/Siren
1K
9
resistor*
Bell/Siren
1K
9
resistor*
Transformer Requirements:
Minimum:
16.5VAC; 20VA
Auxiliary Supply can provide:
typical 600mA
max. 700mA
Usable Battery Charge
350mA
Currents:
Improper connection may
result in damage to the system.
A 40VA transformer is required
when selecting the 850mA
battery charge current. Using a
20VA transformer with a battery
charge current of 850mA may
damage the system
To provide maximum lightning protection we
strongly recommend having separate earth
connections for the dialer and zone ground
terminals.
AWG#14 single
conductor
solid copper
wire
Ground
clamp
Cold water pipe
grounding
To metallic
enclosure
For the hardwired connections, see
Combus
CAUTION: Disconnect
the battery before
replacing the fuse.
Optional connector can
be used to recharge
another battery in the
system or to the
connect a secondary
battery.
WARNING!
Do not connect a DGP2-TM1
Time Module to the
"MEM KEY/TM1" connector.
Connecting a DGP2-TM1 will
create time errors within the
panel and features that use the
control panel's internal clock
(ex.: Auto-arming) will not
function correctly.
Reset Jumper
Same ground
connections as the panel,
but do not connect the
DGP2-ZX4's ground directly
to the control panel's
ground.
For the hardwired
connections, see
Four pin connector can
be used for quick
installation of a keypad
or module.
Built-in RTC
See also the "
MEM
KEY
/
TM
1"
connector warning.
Red "
LINE
#1" and "
LINE
#2" LEDs:
Illuminated
- If the control panel is using a telephone line, the panel
will display which line it is using by illuminating a telephone line LED.
If the control panel is using Line 1, the "
LINE
#1
" LED will be
illuminated. If the control panel is using Line 2, the "
LINE
#2
" LED
will be illuminated.
Red "
STATUS
" LED:
Flashing
- Indicates proper operation.
Fast Flash
- Indicates a control panel failure.
Off
- Control panel error.
12Vdc 7Ah Rechargeable
Acid/Lead or Gel Cell
Backup Battery
Charging and battery test LED
(every 64 seconds).
Summary of Contents for DIGIPLEX DGP-NE96
Page 2: ......