background image

DGP-NE96 Control Panel

 3

Figure 3: DGP-NE96 Control Panel Wiring Diagram

AUX Power (Auxiliary):

Refer to the transformer requirements for the 
Auxiliary Power Output. Also, refer to the 
Power Unit Consumption Table. To connect 
additional wiring to auxiliary power, use the 
red (+) and black (-) keypad connectors. 
Auxiliary power will shut down if the current 
exceeds 1.1A.

When installing the combus wires in a noisy environment, or 
when connecting the combus across separate buildings, you 
must use a shielded cable. Refer to section 2.16.1 on page 7.

PLEASE NOTE:

 When powering up the DGP-NE96 control panel (V1.02 or higher), the panel will begin a module scan to verify if all the modules connected to the panel are operational. The scanning 

process will take between 30 and 120 seconds to complete depending on the number of modules connected to the control panel. The module scan is complete when the LCD keypad begins to show the 
partition status. Only after the module scan is complete will the control panel be fully operational.

PLEASE NOTE

: It is strongly recommended that you test your 

system on a weekly basis, and have your system checked by a 
qualified technician a minimum of every 3 years.

Please see 

UL and ULC Warnings 

on page 57 for applicable UL/

ULC warnings and information.

The combus supports a maximum of 127 modules. Although 
external power supplies can be used to provide power to 
modules connected far from the control panel, the total 
distance of all runs of wire combined cannot exceed 914m 
(3000ft). For example, if ten runs of wire measuring 305m 
(1000ft) each are connected to the control panel, the total 
distance would be 3048m (10, 000ft), which exceeds the 
system's capacity.

WARNING: Before adding any module to the control 
panel make sure you shutdown the control panel by 
removing AC power and the battery.

Door Contact

* if EOL is enabled in the 
   control panel

*A 1K

9

 resistor is 

required if the bell is 
not equipped with an 
internal resistor. The 
resistor must be 
connected between 
the bell's negative (-) 
and positive (+) wires. 
Position the resistor as 
close as possible to 
the bell. A resistor is 
not required for sirens.

The bell 
output will 
shut down if 
the current 
exceeds 3A.

Bell/Siren

1K

9

resistor*

Bell/Siren

1K

9

resistor*

Transformer Requirements:

 Minimum:

16.5VAC; 20VA

Auxiliary Supply can provide:

typical 600mA
max. 700mA

Usable Battery Charge 

350mA

Currents: 

Improper connection may 
result in damage to the system.

A 40VA transformer is required 
when selecting the 850mA 
battery charge current. Using a 
20VA transformer with a battery 
charge current of 850mA may 
damage the system

To provide maximum lightning protection we 
strongly recommend having separate earth 
connections for the dialer and zone ground 
terminals.

AWG#14 single 
conductor 
solid copper 
wire

Ground 
clamp

Cold water pipe 
grounding

To metallic 
enclosure

For the hardwired connections, see 

Single Zone Input 

Connections 

on page 6 and 

Double Zone Connections 

on page 6.

Combus

CAUTION: Disconnect 
the battery before 
replacing the fuse.

Optional connector can 
be used to recharge 
another battery in the 
system or to the 
connect a secondary 
battery.

WARNING!

Do not connect a DGP2-TM1 
Time Module to the
"MEM KEY/TM1" connector. 
Connecting a DGP2-TM1 will 
create time errors within the 
panel and features that use the 
control panel's internal clock 
(ex.: Auto-arming) will not 
function correctly.

Reset Jumper

         Same ground 
connections as the panel, 
but do not connect the 
DGP2-ZX4's ground directly 
to the control panel's 
ground.
For the hardwired 
connections, see 

Single 

Zone Input Connections 

on 

page 6 an

Double Zone 

Connections 

on page 6.

Four pin connector can 
be used for quick 
installation of a keypad 
or module.

Built-in RTC

See also the "

MEM

 

KEY

/

TM

1"

connector warning.

Red "

LINE

#1" and "

LINE

#2" LEDs:

Illuminated

 - If the control panel is using a telephone line, the panel 

will display which line it is using by illuminating a telephone line LED. 
If the control panel is using Line 1, the "

LINE

#1

" LED will be 

illuminated. If the control panel is using Line 2, the "

LINE

#2

" LED

will be illuminated. 

Red "

STATUS

" LED:

Flashing

 - Indicates proper operation.

Fast Flash

 - Indicates a control panel failure.

Off

 - Control panel error.

12Vdc 7Ah Rechargeable 
Acid/Lead or Gel Cell 
Backup Battery

Charging and battery test LED 
(every 64 seconds).

Summary of Contents for DIGIPLEX DGP-NE96

Page 1: ...V1 5 96 Zone Expandable Security and Access Control Panel DGP NE96 Reference and Installation Manual DGP NE96 www paradox ca...

Page 2: ......

Page 3: ...e 16 Restrict Arming on Module Troubles 16 Timed Auto Arming 16 No Movement Auto Arming 17 Auto Arming Options 17 Switch To Stay Arming 17 Always Force Arm when Regular Arming 17 Follow Zone Switches...

Page 4: ...evels 36 Access Schedules 36 Backup Schedules 37 Holiday Programming 37 Schedule Tolerance Window 37 Door Access Mode 37 Code Access 37 Card and Code Access 37 Skip Exit Delay When Arming With Access...

Page 5: ...the CTR 21 approval are available as an option only 1 1 Features Digital combus Provides constant power supervision and two way communication between the control panel and all its modules Supports up...

Page 6: ...a 12Vdc 4Ah rechargeable acid lead or gel cell backup battery YUASA model NP7 12 recommended as shown in Figure 3 on page 3 Connect the backup battery after applying AC power When installing verify pr...

Page 7: ...resistor as close as possible to the bell A resistor is not required for sirens The bell output will shut down if the current exceeds 3A Bell Siren 1K9 resistor Bell Siren 1K9 resistor Transformer Re...

Page 8: ...ion Module DGP2 ZX1 _______ X 14PU __________ PU 4 Zone Hardwire Module APR3 ZX4 _______ X 28PU __________ PU 8 Zone Hardwire Module APR3 ZX8 _______ X 28PU __________ PU Wireless Module OMN RCV3 ____...

Page 9: ...rdwired input terminals for use with traditional hardwired non combus door contacts smoke detectors and or motion detectors The control panel also supports several hardwire zone expansion modules Devi...

Page 10: ...nsion Plug in Device DGP2 ZX4 provides four additional hardwired input terminals 8 zones with ATZ enabled It connects directly to the control panel through its on board EXPANSION connector as shown in...

Page 11: ...ote Not to be used with UL Listed systems 2 17 2 ESL CleanMe Installation The DGP NE96 control panel supports ESL smoke detectors that have the CleanMe feature Connect ESL smoke detectors like the sta...

Page 12: ...ored in the RTC every hour If the times are different the DGP NE96 will reset its internal clock to the time saved in the RTC The RTC uses a 3V lithium battery CR2032 with a battery life of 11 years C...

Page 13: ...he next section Press the right action key Exit to revert to the preceding step or press the left action key Clear to erase the current data 3 4 1 Feature Select Programming Most of the options are pr...

Page 14: ...d to it Enter the module s 3 digit INPUT NUMBER where the hardwire device is connected NOTE For addressable PIRs door contacts and keypads no input is required Zone Definition First Digit Zone Partiti...

Page 15: ...ters through the entry point to disarm the system 4 3 4 Instant Zones SECTIONS 0101 TO 0196 FIRST DIGIT 4 When an armed Instant zone opens the control panel immediately generates an alarm Instant zone...

Page 16: ...ction 4 3 4 on page 11 When a Stay Delay zone is armed using the Stay or Instant arming methods and the zone is triggered the control panel will not generate an alarm until the programmed Stay Delay e...

Page 17: ...e into effect until the Input Speed elapses The control panel will not display and or respond to an open zone until the Input Speed elapses to prevent glitches from causing an alarm or unnecessary rep...

Page 18: ...tion using the Maintained Keyswitch turn the switch from the ON to the OFF position To disarm a partition set the keyswitch in the ON position The selected Keyswitch Option see section 5 4 on page 15...

Page 19: ...ing the security system into eight completely independent systems Therefore each keyswitch must be assigned to one partition as shown in Figure 17 on page 14 For details on Partitioning see section 11...

Page 20: ...le if options 1 2 and 5 are ON in section 3035 the control panel prevents arming if it detects an AC or battery failure on the control panel or on a module connected to the combus 6 9 Timed Auto Armin...

Reviews: