background image

12 

Reference & Installation Manual

4.3.10 24Hr Water Zones*

S

ECTIONS

 [0101] 

TO

 [0196]: F

IRST

 

DIGIT

 = A

When a 24Hr Water zone opens, whether it is armed or disarmed, the 
control panel will immediately generate an alarm. The SIA FSK reporting 
format includes specific codes to identify the alarm as a Water Alarm. 

4.3.11 24Hr Freeze Zones*

S

ECTIONS

 [0101] 

TO

 [0196]: F

IRST

 

DIGIT

 = B

When a 24Hr Freeze zone opens, whether it is armed or disarmed, the 
control panel will immediately generate an alarm. The SIA FSK reporting 
format includes specific codes to identify the alarm as a Freeze Alarm. 

* UL Note:

 UL Listed compatible devices shall be used for UL systems. For 

UL Listed systems, this type of zone shall be programmed as a silent auxiliary 
alarm.

4.3.12 Delayed 24Hr Fire Zone 

(Not to be used with UL Listed systems)

S

ECTIONS

 [0101] 

TO

 [0196]: F

IRST

 

DIGIT

 = C

The Delayed 24Hr Fire Zone definition from Figure 15 on page 12 is 
commonly used in residential homes where a smoke detector often 
generates false alarms (i.e. cigarette smoke, burning bread, etc.). A zone 
programmed as Fire becomes normally open (will not function as normally 
closed) and requires an EOL resistor.

The keypads must be assigned to the same partition as the 
Delayed 24Hr Fire zone for the buzzer to activate. 

Figure 15: Delayed 24Hr Fire Zone

4.3.13 Standard 24Hr Fire Zone

S

ECTIONS

 [0101] 

TO

 [0196]: F

IRST

 

DIGIT

 = D

A zone programmed as Fire becomes normally open (will not function as 
normally closed) and requires an EOL resistor. 
When a Standard 24Hr Fire Zone triggers, the control panel can:
• send a 

Zone Alarm

 report code (see section 8.2.1 on page 22). 

• send a 

Fire Loop Trouble Report

 (see section 8.2.11 on page 23) if a 

tamper/wiring fault occurs on a Fire Zone. A “Zone Fault Trouble” will 
also appear in the keypad's Trouble Display.

• generate a Fire alarm, which is always audible, regardless of other 

settings. Fire alarms generate an intermittent signal (see Figure 16).

Figure 16: Bell/Siren Output During Fire Alarm

4.3.14 Stay Delay Zone

S

ECTIONS

 [0101] 

TO

 [0196]: F

IRST

 

DIGIT

 = E 

AND

 F

When a Stay Delay zone is armed using the Regular or Force arming 
methods, the control panel processes the zone as an Instant zone (see 
section 4.3.4 on page 11). When a S
tay Delay zone is armed using the Stay 
or Instant arming methods and the zone is triggered, the control panel will 
not generate an alarm until the programmed Stay Delay elapses. A zone 
defined as Stay Delay 1 follows the Entry Delay 1 Timer of its assigned 
partition. Likewise, a zone defined as Stay Delay 2 follows the Entry Delay 
2 Timer of its assigned partition. To program the Entry Delay Timers, refer 
to 

Entry Delays 1 and 2

 on page 11. 

For example, if zone 1 in Partition 5 is defined as Stay Delay 1, the timer 
will follow the amount programmed in [3511].

4.4 Zone Partition Assignment

S

ECTIONS

 [0101] 

TO

 [0196]: S

ECOND

 

DIGIT

 = 1 

TO

 8

A control panel can be divided into eight completely independent systems 
(see section 11.9 on page 31). Assign each zone to one partition (see 
Figure 13 on page 10). 

4.5 Zone Options

The zone options from Figure 13 on page 10 are described below. 

4.5.1 Auto Zone Shutdown

S

ECTIONS

 [0101] 

TO

 [0196]: O

PTION

 [1]

(Default = 000) When option 

[1]

 is disabled, the control panel generates an 

alarm when an armed zone is breached even if the same zone opens 
repeatedly during the same alarm, which may cause several reportings and 
further activation of the bell output. When option

 [1]

 is enabled, the control 

panel will stop regenerating alarms on the zone during the same armed 
period once the Auto Zone Shutdown Limit is reached. The Auto Zone 
Shutdown Limit resets every time the partition that is assigned to the 
corresponding zone is armed. To program the Auto Zone Shutdown Limit, 
key in the desired 3-digit counter (000 to 255) into section corresponding to 
the desired partition (000 = disabled):

4.5.2 Bypass Zones

S

ECTIONS

 [0101] 

TO

 [0196]: O

PTION

 [2]

(Default = enabled) Only zones with option 

[2] 

enabled can be Manually 

Bypassed (see section 15.7 on page 40). Fire Zones cannot be bypassed.

Latch alarm and transmit 
report code as described 
in section 4.3.13

Delayed Fire Zone 

Triggered

Bell/siren silenced. Delay report 

transmission an additional 90s.

Activate bell/siren output & delay 

report transmission for 30s.

Has the zone 

closed within 

30s?

Yes

Yes

Yes

Yes

No

No

No

No

Has a 2

nd

 

Delayed Fire 

Zone opened 

in 30s?

Any key on 

keypad 

pressed 

within 30s?

Problem 

corrected?

END

Alarm Disabled

Partition 1: 

[3114]

Partition 5: 

[3514]

Partition 2: 

[3214]

Partition 6: 

[3614]

Partition 3: 

[3314]

Partition 7: 

[3714]

Partition 4: 

[3414]

Partition 8: 

[3814]

Summary of Contents for DIGIPLEX DGP-NE96

Page 1: ...V1 5 96 Zone Expandable Security and Access Control Panel DGP NE96 Reference and Installation Manual DGP NE96 www paradox ca...

Page 2: ......

Page 3: ...e 16 Restrict Arming on Module Troubles 16 Timed Auto Arming 16 No Movement Auto Arming 17 Auto Arming Options 17 Switch To Stay Arming 17 Always Force Arm when Regular Arming 17 Follow Zone Switches...

Page 4: ...evels 36 Access Schedules 36 Backup Schedules 37 Holiday Programming 37 Schedule Tolerance Window 37 Door Access Mode 37 Code Access 37 Card and Code Access 37 Skip Exit Delay When Arming With Access...

Page 5: ...the CTR 21 approval are available as an option only 1 1 Features Digital combus Provides constant power supervision and two way communication between the control panel and all its modules Supports up...

Page 6: ...a 12Vdc 4Ah rechargeable acid lead or gel cell backup battery YUASA model NP7 12 recommended as shown in Figure 3 on page 3 Connect the backup battery after applying AC power When installing verify pr...

Page 7: ...resistor as close as possible to the bell A resistor is not required for sirens The bell output will shut down if the current exceeds 3A Bell Siren 1K9 resistor Bell Siren 1K9 resistor Transformer Re...

Page 8: ...ion Module DGP2 ZX1 _______ X 14PU __________ PU 4 Zone Hardwire Module APR3 ZX4 _______ X 28PU __________ PU 8 Zone Hardwire Module APR3 ZX8 _______ X 28PU __________ PU Wireless Module OMN RCV3 ____...

Page 9: ...rdwired input terminals for use with traditional hardwired non combus door contacts smoke detectors and or motion detectors The control panel also supports several hardwire zone expansion modules Devi...

Page 10: ...nsion Plug in Device DGP2 ZX4 provides four additional hardwired input terminals 8 zones with ATZ enabled It connects directly to the control panel through its on board EXPANSION connector as shown in...

Page 11: ...ote Not to be used with UL Listed systems 2 17 2 ESL CleanMe Installation The DGP NE96 control panel supports ESL smoke detectors that have the CleanMe feature Connect ESL smoke detectors like the sta...

Page 12: ...ored in the RTC every hour If the times are different the DGP NE96 will reset its internal clock to the time saved in the RTC The RTC uses a 3V lithium battery CR2032 with a battery life of 11 years C...

Page 13: ...he next section Press the right action key Exit to revert to the preceding step or press the left action key Clear to erase the current data 3 4 1 Feature Select Programming Most of the options are pr...

Page 14: ...d to it Enter the module s 3 digit INPUT NUMBER where the hardwire device is connected NOTE For addressable PIRs door contacts and keypads no input is required Zone Definition First Digit Zone Partiti...

Page 15: ...ters through the entry point to disarm the system 4 3 4 Instant Zones SECTIONS 0101 TO 0196 FIRST DIGIT 4 When an armed Instant zone opens the control panel immediately generates an alarm Instant zone...

Page 16: ...ction 4 3 4 on page 11 When a Stay Delay zone is armed using the Stay or Instant arming methods and the zone is triggered the control panel will not generate an alarm until the programmed Stay Delay e...

Page 17: ...e into effect until the Input Speed elapses The control panel will not display and or respond to an open zone until the Input Speed elapses to prevent glitches from causing an alarm or unnecessary rep...

Page 18: ...tion using the Maintained Keyswitch turn the switch from the ON to the OFF position To disarm a partition set the keyswitch in the ON position The selected Keyswitch Option see section 5 4 on page 15...

Page 19: ...ing the security system into eight completely independent systems Therefore each keyswitch must be assigned to one partition as shown in Figure 17 on page 14 For details on Partitioning see section 11...

Page 20: ...le if options 1 2 and 5 are ON in section 3035 the control panel prevents arming if it detects an AC or battery failure on the control panel or on a module connected to the combus 6 9 Timed Auto Armin...

Reviews: