background image

Reference & Installation Manual

2  

Installation

2.1 Recommended Installation Procedure

In order to facilitate installation, we recommend connecting the modules in 
small groups and verifying the system after every group is connected, 
instead of verifying the system only after all modules are connected.

1. Install the control panel.
2. Connect a small group of modules, including a keypad, to the combus.
3. Connect the battery and then connect the AC power. Enter section 

[4000]

 to verify if all the connected modules’ serial numbers appear 

(see section 11.19 on page 32). If all the modules appear in section 
[4000], only the Clock Loss trouble and/or Bell Absent trouble should 
appear on the keypad. Verify the connection if a module does not 
appear in section [4000], or if a module trouble occurs.

4. If another group of modules needs to be connected, disconnect AC 

power and the battery, and then continue the installation by following 
steps 2, 3 and 4.

5. If modules were removed from the combus, enter 

[4005]

 to remove 

them from the panel’s memory (see section 11.18 on page 32).

6. Connect an LCD keypad at various points farthest from the control 

panel and use the keypad’s built-in voltmeter to verify the combus’s 
voltage (refer to the 

Digiplex (DGP-NE96) LCD Keypad Reference & 

Installation Manual

).

2.2 Location & Mounting

Before mounting the cabinet, push the five white nylon mounting studs into 
the back of the cabinet. Pull all cables into the cabinet and prepare them for 
connection before mounting the circuit board into the back of the cabinet. 
Select an installation site that is not easily accessible to intruders and leave 
at least 2" around the panel box to permit adequate ventilation and heat 
dissipation. The installation site should be dry and close to an AC source, 
ground connection and telephone line connection.

2.3 Earth Ground

Connect the zone and dialer ground terminals from the control panel to the 
enclosure and cold water pipe or grounding rod as per local electrical codes.

For maximum lightning protection, use separate earth grounds 
for the zone and dialer grounds (see Figure 3 on page 3). 

2.4 AC Power

Use a 16.5Vac (50/60Hz) transformer with a minimum 20VA rating to 
provide sufficient AC power. For increased power use a transformer with a 
40VA rating. 

For UL Listed systems, use model #BE156240CAA. For CSA 

listed systems, use model #BE116240AAA.

 Do not use any switch-

controlled outlets to power the transformer. Connect the transformer as 
shown in Figure 3 on page 3.

Do not connect the transformer or the backup battery until all 
wiring is completed.

PLEASE NOTE: When powering up the DGP-NE96 control panel 
(V1.02 or higher), the panel will begin a module scan to verify if 
all the modules connected to the control panel are operational. 
The scanning process will take between 30 and 120 seconds to 
complete depending on the number of modules connected to 
the control panel. The module scan is complete when the 
keypad begins to show the partition status. Only after the 
module scan is complete will the control panel be fully 
operational.

2.5 Backup Battery

To provide power during power loss, connect a 12Vdc 4Ah rechargeable 
acid/lead or gel cell backup battery (YUASA model #NP7-12 
recommended) as shown in Figure 3 on page 3. Connect the backup 
battery after applying AC power. When installing, verify proper polarity, as 
reversed connections will blow the battery fuse. For details on how to set 
the Battery Charge Current to either 350mA or 850mA, see section 11.5 on 
page 30
.

2.5.1 Battery Test

The control panel conducts a dynamic battery test under load every 64 
seconds. If the battery is disconnected, if its capacity is too low or if the 
battery voltage drops to 10.5 volts or less when there is no AC, the “Battery 
Trouble” message will appear in the Trouble Display. At 8.5 volts, the panel 
shuts down and all outputs close.

2.6 Auxiliary Power Terminals

The auxiliary power supply can power the motion detectors, keypads and 
other accessories in the security system. A fuseless circuit protects the 
auxiliary output against current overload and automatically shuts down if 
the current exceeds 1.1A. Auxiliary power will resume once the overload 
condition has restored. For details on available output power, please refer 
to Figure 3 on page 3. To calculate power consumption, see 

Calculating 

Power Requirements

 on page 4.

2.7 Bell/Siren Output

The 

BELL

+ and 

BELL

- terminals power bells and/or other warning devices 

that require a steady voltage output during an alarm. The bell output 
supplies 12Vdc upon alarm and can support one 30-watt or two 20-watt 
sirens. The bell output uses a fuseless circuit and will automatically shut 
down if the current exceeds 3A. If the load on the 

BELL

 terminals returns to 

normal (

3A), the control panel will re-instate power to the 

BELL

 terminals. 

When connecting sirens, please verify correct polarity as shown in Figure 3 
on page 3. PGM2 and PGM3 are r
elays rated at 5A each and can be used 
to power bells and/or other warning devices by programming them as a 
bell/siren outputs (see section 10 on page 29)

When the bell output is not used, the “Bell Absent” message 
appears in the Trouble Display. To avoid this, connect a 1k

 

resistor across the bell output. UL Note: The keypads must be 
programmed to beep with all troubles.

2.8 Programmable Outputs

The control panel comes standard with 
PGM1 to PGM3. When a specific event or 
condition occurs in the system, a PGM can 
be programmed to reset smoke detectors, 
activate strobe lights, open/close garage 
doors and much more. For details on how to 
program the PGMs, refer to section 10. 

PGM1 is 100mA (max.) normally open 
output. PGM2 and PGM3 are 5A relay 
outputs that can be normally open or 
normally closed. If the current draw on 
PGM1 is to exceed the current output, we 
recommend using a relay as shown in 
Figure 1. PGM1 can be programmed as a 2-
wire smoke detector input (see section 
2.17.1 on page 7 and section 10.6 on page 29)
.

2.9 Keyswitch Connections 

(not verified by UL)

Connect the keyswitches to the keypad, 
control panel, or Zone Expansion Module's 
hardwired input terminals as shown in Figure 
2. Once a ke
yswitch is connected, it must be 
assigned a keyswitch zone and its parameters 
must be defined as described in 

Keyswitch 

Programming

 on page 14.

2.10 Access Control Connections

For all access control explanations and connection drawings, refer to 

Access Control: System Features

 on page 36.

Figure 1: PGM & Relay

Figure 2: Keyswitch

Summary of Contents for DIGIPLEX DGP-NE96

Page 1: ...V1 5 96 Zone Expandable Security and Access Control Panel DGP NE96 Reference and Installation Manual DGP NE96 www paradox ca...

Page 2: ......

Page 3: ...e 16 Restrict Arming on Module Troubles 16 Timed Auto Arming 16 No Movement Auto Arming 17 Auto Arming Options 17 Switch To Stay Arming 17 Always Force Arm when Regular Arming 17 Follow Zone Switches...

Page 4: ...evels 36 Access Schedules 36 Backup Schedules 37 Holiday Programming 37 Schedule Tolerance Window 37 Door Access Mode 37 Code Access 37 Card and Code Access 37 Skip Exit Delay When Arming With Access...

Page 5: ...the CTR 21 approval are available as an option only 1 1 Features Digital combus Provides constant power supervision and two way communication between the control panel and all its modules Supports up...

Page 6: ...a 12Vdc 4Ah rechargeable acid lead or gel cell backup battery YUASA model NP7 12 recommended as shown in Figure 3 on page 3 Connect the backup battery after applying AC power When installing verify pr...

Page 7: ...resistor as close as possible to the bell A resistor is not required for sirens The bell output will shut down if the current exceeds 3A Bell Siren 1K9 resistor Bell Siren 1K9 resistor Transformer Re...

Page 8: ...ion Module DGP2 ZX1 _______ X 14PU __________ PU 4 Zone Hardwire Module APR3 ZX4 _______ X 28PU __________ PU 8 Zone Hardwire Module APR3 ZX8 _______ X 28PU __________ PU Wireless Module OMN RCV3 ____...

Page 9: ...rdwired input terminals for use with traditional hardwired non combus door contacts smoke detectors and or motion detectors The control panel also supports several hardwire zone expansion modules Devi...

Page 10: ...nsion Plug in Device DGP2 ZX4 provides four additional hardwired input terminals 8 zones with ATZ enabled It connects directly to the control panel through its on board EXPANSION connector as shown in...

Page 11: ...ote Not to be used with UL Listed systems 2 17 2 ESL CleanMe Installation The DGP NE96 control panel supports ESL smoke detectors that have the CleanMe feature Connect ESL smoke detectors like the sta...

Page 12: ...ored in the RTC every hour If the times are different the DGP NE96 will reset its internal clock to the time saved in the RTC The RTC uses a 3V lithium battery CR2032 with a battery life of 11 years C...

Page 13: ...he next section Press the right action key Exit to revert to the preceding step or press the left action key Clear to erase the current data 3 4 1 Feature Select Programming Most of the options are pr...

Page 14: ...d to it Enter the module s 3 digit INPUT NUMBER where the hardwire device is connected NOTE For addressable PIRs door contacts and keypads no input is required Zone Definition First Digit Zone Partiti...

Page 15: ...ters through the entry point to disarm the system 4 3 4 Instant Zones SECTIONS 0101 TO 0196 FIRST DIGIT 4 When an armed Instant zone opens the control panel immediately generates an alarm Instant zone...

Page 16: ...ction 4 3 4 on page 11 When a Stay Delay zone is armed using the Stay or Instant arming methods and the zone is triggered the control panel will not generate an alarm until the programmed Stay Delay e...

Page 17: ...e into effect until the Input Speed elapses The control panel will not display and or respond to an open zone until the Input Speed elapses to prevent glitches from causing an alarm or unnecessary rep...

Page 18: ...tion using the Maintained Keyswitch turn the switch from the ON to the OFF position To disarm a partition set the keyswitch in the ON position The selected Keyswitch Option see section 5 4 on page 15...

Page 19: ...ing the security system into eight completely independent systems Therefore each keyswitch must be assigned to one partition as shown in Figure 17 on page 14 For details on Partitioning see section 11...

Page 20: ...le if options 1 2 and 5 are ON in section 3035 the control panel prevents arming if it detects an AC or battery failure on the control panel or on a module connected to the combus 6 9 Timed Auto Armin...

Reviews: