background image

 

DGP-NE96 Control Panel

 7

2.16 Combus Connections

Modules can connect anywhere on the 4-wire combus, which can support 
up to 127 modules. Connect in a star and/or daisy chain configuration as 
shown in Figure 3 on page 3. The total distance of all runs of wire cannot 
exceed 914m (3000ft). For example, if ten runs of wire measuring 305m 
(1000ft) each are connected to the control panel, the total distance would 
be 3048m (10,000ft), which exceeds the system’s capacity. To assign a 
detection device to a zone in the control panel, see 

Zone Programming

 on 

page 10

Before connecting a module to the combus, remove AC and 
battery power from the control panel.

2.16.1 Connecting the Combus in Noisy Environments

When installing the combus wires in proximity to high electrical 
interferences such as neon lights, motors, high-voltage wiring, 
transformers, or if connecting the combus across separate buildings, you 
must use shielded cables. Connect the shielded cable as detailed below:

Within the Same Building:

 Strip the outer jacket at one end of the 

shielded cable to expose the shield and connect the shield to the control 
panel ground (not the dialer ground), while leaving the shield at the other 
end of the cable open (floating).

Across Separate Buildings:

 Strip the outer jacket at one end of the 

shielded cable to expose the shield. In the same building that houses the 
control panel, connect the exposed shield to a cold water pipe or any other 
earth ground available, while leaving the shield at the other end of the cable 
open (floating). The same configuration applies for any subsequent 
building.

2.17 Fire Circuits

Connect the smoke detectors using any of the following methods. Assign 
the smoke detectors connected to the control panel or zone expansion 
input terminals to a zone and define the zone's parameters as a Fire Zone 
(see section 4 on page 10).

2.17.1 Smoke Detector Installation (2-Wire)*

PGM1 can be defined as a 2-wire 
smoke detector input (see section 
10.6).
 Connect the 2-wire smoke 
detectors as shown in Figure 8 using a 
1k

 EOL resistor. If a line short 

occurs or the smoke detector 
activates, whether the system is 
armed or disarmed, the control panel 
will generate an alarm. If the line is 
open, the “Zone Fault” trouble 
indication appears in the Trouble 
Display and the report code is sent to 
the monitoring station, if programmed.

*

 

UL Note:

 Not to be used with UL Listed systems.

2.17.2 ESL CleanMe

® 

Installation

The DGP-NE96 control panel supports ESL smoke detectors that have the 
CleanMe

®

 feature. Connect ESL smoke detectors like the standard smoke 

detectors shown in Figure 8. Avoid connecting more than 20 ESL smoke 
detectors. When an ESL smoke detector sends a CleanMe signal, the 
control panel will generate a Zone Fault trouble and, if programmed, will 
transmit the Fire Loop report code to the monitoring station. The trouble will 
be cleared if there is no CleanMe signal for 255 seconds. If an alarm 
occurs, the trouble will be cleared until it is detected again.

2.17.3 Smoke Detector Installation (4-Wire)

Recommended: System Sensor model 
2112/24D smoke detectors. Connect the 
4-wire smoke detectors and a relay as 
shown in Figure 9. To comply with UL955, 
install the 4-wire smoke detectors with 18 
gauge wire. If power is interrupted, the 
relay causes the control panel to transmit 
the Fire Loop Trouble report programmed 
in section 

[2906]

To reset (unlatch), connect the smoke 
detector’s negative (-) to a PGM. Then 
program the PGM with the “Smoke 
Detector Power Reset” activation event 
(see section 10.1 on page 29; Event 
Group #067, start # 004, end # 004) to 
interrupt power to the smoke detector for 
four seconds when the 

[

CLEAR

]

 and 

[

ENTER

keys are pressed and held for two 

seconds.

If ATZ is enabled (see see section 4.2 on page 11), do not use the 
extra input (doubled zone). For example, in this example input 
13 cannot be used.

2.18 Telephone Line Connections

Depending on the installation, the telephone lines can be connected directly 
to the control panel or through a CA38A or RJ31 as shown in Figure 10
The secondary telephone line terminals (optional) can be used as a backup 
telephone line. If the Event Call Direction process fails and the control panel 
is unable to communicate with the monitoring station through the main line, 
the control panel will switch to the second line and repeat the Event Call 
Direction process (see section 8.8 on page 25).

UL Note:

 Installer must verify line seizure after every installation

Figure 10: Telephone Line Connection Examples

Figure 8: 

2-Wire Detectors

Note: It is recommended that the smoke 
detectors be connected in a daisy chain 
configuration.

PGM1 becomes
input# 255

Smoke detectors

1K

9

EOL

N.O. contacts 

Figure 9: 4-Wire Detectors

Note: It is recommended that the 
smoke detectors be connected in a 
daisy chain configuration.

DGP-NE96
Dialer

2nd line

Main line

Ground 
clamp

Example 2:

Example 1:

DGP-NE96
Dialer

Ground 
clamp

2nd line

Main line

Summary of Contents for DIGIPLEX DGP-NE96

Page 1: ...V1 5 96 Zone Expandable Security and Access Control Panel DGP NE96 Reference and Installation Manual DGP NE96 www paradox ca...

Page 2: ......

Page 3: ...e 16 Restrict Arming on Module Troubles 16 Timed Auto Arming 16 No Movement Auto Arming 17 Auto Arming Options 17 Switch To Stay Arming 17 Always Force Arm when Regular Arming 17 Follow Zone Switches...

Page 4: ...evels 36 Access Schedules 36 Backup Schedules 37 Holiday Programming 37 Schedule Tolerance Window 37 Door Access Mode 37 Code Access 37 Card and Code Access 37 Skip Exit Delay When Arming With Access...

Page 5: ...the CTR 21 approval are available as an option only 1 1 Features Digital combus Provides constant power supervision and two way communication between the control panel and all its modules Supports up...

Page 6: ...a 12Vdc 4Ah rechargeable acid lead or gel cell backup battery YUASA model NP7 12 recommended as shown in Figure 3 on page 3 Connect the backup battery after applying AC power When installing verify pr...

Page 7: ...resistor as close as possible to the bell A resistor is not required for sirens The bell output will shut down if the current exceeds 3A Bell Siren 1K9 resistor Bell Siren 1K9 resistor Transformer Re...

Page 8: ...ion Module DGP2 ZX1 _______ X 14PU __________ PU 4 Zone Hardwire Module APR3 ZX4 _______ X 28PU __________ PU 8 Zone Hardwire Module APR3 ZX8 _______ X 28PU __________ PU Wireless Module OMN RCV3 ____...

Page 9: ...rdwired input terminals for use with traditional hardwired non combus door contacts smoke detectors and or motion detectors The control panel also supports several hardwire zone expansion modules Devi...

Page 10: ...nsion Plug in Device DGP2 ZX4 provides four additional hardwired input terminals 8 zones with ATZ enabled It connects directly to the control panel through its on board EXPANSION connector as shown in...

Page 11: ...ote Not to be used with UL Listed systems 2 17 2 ESL CleanMe Installation The DGP NE96 control panel supports ESL smoke detectors that have the CleanMe feature Connect ESL smoke detectors like the sta...

Page 12: ...ored in the RTC every hour If the times are different the DGP NE96 will reset its internal clock to the time saved in the RTC The RTC uses a 3V lithium battery CR2032 with a battery life of 11 years C...

Page 13: ...he next section Press the right action key Exit to revert to the preceding step or press the left action key Clear to erase the current data 3 4 1 Feature Select Programming Most of the options are pr...

Page 14: ...d to it Enter the module s 3 digit INPUT NUMBER where the hardwire device is connected NOTE For addressable PIRs door contacts and keypads no input is required Zone Definition First Digit Zone Partiti...

Page 15: ...ters through the entry point to disarm the system 4 3 4 Instant Zones SECTIONS 0101 TO 0196 FIRST DIGIT 4 When an armed Instant zone opens the control panel immediately generates an alarm Instant zone...

Page 16: ...ction 4 3 4 on page 11 When a Stay Delay zone is armed using the Stay or Instant arming methods and the zone is triggered the control panel will not generate an alarm until the programmed Stay Delay e...

Page 17: ...e into effect until the Input Speed elapses The control panel will not display and or respond to an open zone until the Input Speed elapses to prevent glitches from causing an alarm or unnecessary rep...

Page 18: ...tion using the Maintained Keyswitch turn the switch from the ON to the OFF position To disarm a partition set the keyswitch in the ON position The selected Keyswitch Option see section 5 4 on page 15...

Page 19: ...ing the security system into eight completely independent systems Therefore each keyswitch must be assigned to one partition as shown in Figure 17 on page 14 For details on Partitioning see section 11...

Page 20: ...le if options 1 2 and 5 are ON in section 3035 the control panel prevents arming if it detects an AC or battery failure on the control panel or on a module connected to the combus 6 9 Timed Auto Armin...

Reviews: