DGP-848 Control Panel

 

3

Figure 3: Digiplex Control Panel PCB Layout

For UL/C-UL warnings and requirements, see Warnings on page 60.

For the hardwire 
connections, see Single 
Zone Connections 
on 
page 6. and Double 
Zone Connections 
on 
page 7..

When installing the combus wires in a noisy 
environment, or when connecting the combus across 
separate buildings, you must use a shielded cable. 
Refer to Connecting the Combus in Noisy 
Environments 
on page 6.

The combus supports a maximum of 95 modules. 
Although external power supplies can be used to 
provide power to modules connected far from the 
control panel, the final module on the combus should 
not be more than 3000 feet (914m) away. 

Before adding any module to the control panel, 
make sure you shut down the panel by removing 
AC power and the battery. 

Four pin connector can be 
used for quick installation of a 
Digiplex keypad or module.

Charging and battery test LED
(every 64 seconds)

“STATUS” LED: Short flash  = Panel OK

Long flash  = TLM Fault
Constant

= Dialer on-line

OFF

= Panel error/off-line

Reset 
jumper

Warning:
Disconnect 
telephone line 
before servicing

Ground 
clamp

Cold 
water pipe 
grounding

AWG#14 single 
conductor solid 
copper wire

To metallic 
enclosure

To provide maximum lightning 
protection, we strongly 
recommend having separate 
earth connections for the dialer 
and zone ground terminals.

COMBUS

AUX POWER
Refer to transformer requirements below for Auxiliary Power Output. 
Also, refer to Calculating Power Requirements on page 4. To 
connect additional wiring to auxiliary power, use the red (+) and 
black (-) keypad connectors. Auxiliary power will shut down if current 
exceeds 1.1A.

Transformer Requirements:

minimum: 16VAC 20VA

Auxiliary Supply can provide:

typical: 600mA
max.: 700mA

Usable Battery Charge Currents: 350mA

Warning: Improper connection may 
result in damage to the system.

Warning: During power up, the panel 
will perform a module scan that lasts 
between 30 and 120 seconds.

BELL OUTPUT
will shut down if 
current exceeds 3A.

PGM1: 100mA
PGM2: 50mA
PGM3: 50mA (opt)
PGM4: 50mA (opt)

PGM5 
(optional 
5A relay)

Optional connector 
can be used to 
recharge another 
battery in the 
system.

Warning:
Disconnect the 
battery before 
replacing the 
fuse.

A 40VA transformer is required when 
selecting the 850 mA battery charge 
current. Using a 20VA transformer with 
a battery charge current of 850mA may 
damage the system.

Connection for Self-contained Bell/Siren

The sum of the 
current drawn from 

the BELL and AUX 

must be limited to 2.0A. 
Exceeding this limit will 
overload the panel power 
supply and lead to complete 
system shutdown.

Summary of Contents for Digiplex DGP-848

Page 1: ...Digiplex Control Panel DGP 848 V4 1 Reference and Installation Manual Includes DGP2 641BL RB Installation Instructions DGP 848...

Page 2: ......

Page 3: ...ch Features 20 Exit Delay 20 Keypad Lock out Feature 20 Maximum Bypass Entries 21 Display Bypass If Armed 21 Bell Squawk 21 Ring back 21 Switch To Stay Arming 21 Always Force Arm When Regular Arming 2...

Page 4: ...Access Levels 42 Schedules 42 Holiday Programming 42 Logging Access Control Events 42 Global Access Door Features 43 WinLoad Software 44 Answering Machine Override 44 Ring Counter 44 Panel Identifier...

Page 5: ...ne combus for up to 95 modules All modules have Plug and Play capability Connect modules up to 3000ft 914m from the panel Full supervision and sabotage proof technology without additional wiring Up to...

Page 6: ...nds If the battery is disconnected if its capacity is too low or if the battery voltage drops to 10 5 volts or less when there is no AC the Battery Trouble message will appear in the Trouble Display A...

Page 7: ...To metallic enclosure To provide maximum lightning protection we strongly recommend having separate earth connections for the dialer and zone ground terminals COMBUS AUX POWER Refer to transformer req...

Page 8: ...ontact Modules DGP2 ZC1 _______ X 30mA __________ mA 1 Zone Expansion Modules DGP2 ZX1 _______ X 30mA __________ mA 4 Zone Expansion Modules APR3 ZX4 _______ X 30mA __________ mA 8 Zone Expansion Modu...

Page 9: ...0ft Magellan Module MG RCV3 A 35mA LCD Keypad DGP2 641BL D 110mA 15m 50ft 7 5m 25ft 7 5m 25ft 15m 50ft Motion Detector Module DGP2 70 E 30mA LED Keypad DGP2 648 F 110 mA LED Keypad DGP2 648 G 110 mA A...

Page 10: ...would exceed the system s capacity For information on how to assign a detection device to a zone in the control panel please refer to Zone Programming on page 11 Before connecting a module to the cont...

Page 11: ...shown in Figure 3 on page 3 2 14 Keyswitch Connections Connect the keyswitches to the keypad control panel or Zone Expansion Module s hardwired input terminals as shown in Figure 9 Once a keyswitch i...

Page 12: ...elay will cause the control panel to transmit the Fire Loop Trouble report if programmed in section 707 To reset unlatch the smoke detector after an alarm verify that the negative of the smoke detecto...

Page 13: ...the right action key Exit on Grafica keypads as many times as needed to return to the desired screen Please note that a module s serial number can be located on the module s PC board or it may already...

Page 14: ...that the write protect jumper is on 3 Enter section 965 to copy the contents of the panel except sections 001 to 048 device serial numbers and 049 to 056 keyswitch serial numbers to the key 966 to co...

Page 15: ...esent zones 1 to 48 respectively Zone Parameters Sections 101 to 148 represent zones 1 to 48 respectively Enter the 8 digit SERIAL NUMBER of the addressable detection device or module that has a hardw...

Page 16: ...ry Delay 1 Timer 230 Entry Delay 2 Timer 231 Entry Delay 3 Timer 232 Entry Delay 4 Timer 233 Please note these are the same timers used for Stay Delay zones see section 4 2 9 on page 13 Entry Delay zo...

Page 17: ...lay 4 Timer in section 233 Please note that the Entry Delay Timers are the same timers used for Entry Delay zones 4 3 Zone Partition Assignment SECTIONS 101 TO 148 SECOND DIGIT 1 TO 4 The control pane...

Page 18: ...digit delay value 010 to 255 seconds into section 200 Fire Zones cannot be set as Intellizones 4 4 7 Delay Alarm Transmission SECTIONS 101 TO 148 OPTION 8 When an alarm condition occurs on a zone wit...

Page 19: ...Panel 15 Table 5 Hebrew Keypad Letter Assignment Table 6 Russian Keypad Letter Assignment Table 7 Special Characters Catalogue Table 8 Hebrew Special Characters Catalogue Table 9 Russian Special Chara...

Page 20: ...t 004 speed 205 Panel Terminal 5 Input 005 speed 206 Panel Terminal 6 Input 006 speed 207 Panel Terminal 7 Input 007 speed 208 Panel Terminal 8 Input 008 speed 209 Panel Doubler 1 Input 009 speed 210...

Reviews: